PRESSURE SWITCH ADJUSTMENT:
1. With pump and heater on, turn adjustment
knob (clockwise) until a click is heard from the
gas valve.
2. Turn adjustment knob (counter clockwise) 1/4
turn.
3. Turn pump off and on several times. Heater
should shut off immediately. If it does not,
repeat steps above until proper adjustment is
made.
Adjustment Knob
Fig. # 8069.1
Heat Exchanger Height
5' Max.
Heat Exchanger Height
Pool or Spa
Fig. # 8152.0s
NOTE:
If heater is installed outside of the limits shown,
a flow switch must be used in place of the pressure
switch when mounted and wired adjacent to the heater.
TWO SPEED PUMPS
In some cases, the flow on the low-speed is insuf-
ficient to operate the heater. This is apparent when the
pressure switch cannot be further adjusted or if the
heater makes banging noises. In these cases, the
pump must be run at high speed when heating the
water.
CAUTION:
Do not operate the heater without the func-
tion of a properly adjusted pressure switch.
HIGH LIMITS
The heater is equipped with two automatic high
limits. Both are set to open at 135°F.
NOTE:
An erratic high limit is often characteristic of
internal heat exchanger problem, i.e. scale buildup.
Refer to troubleshooting section.
Fig. #9275
HIGH LIMIT REMOVAL
1. Shut off main electrical power switch to heater.
2. Remove inspection panel and box cover.
3. Drain heater.
4. Remove defective high limit and replace with a new
high limit.
5. Reverse above procedure to re-installl.
PILOT SAFETY
PILOT SAFETY
(Millivolt System)
The heaters equipped with the standing pilot (millivolt
system), have pilot generators which act as a safety
device to shut off the flow of gas to the main burners and
the pilot burner in case the pilot flame is extinguished.
The pilot burner must be manually relighted to place the
heater in operation again. Refer to the lighting instruc-
tions provided on the heater label.
PILOT SAFETY
(IID Units) ELECTRIC IGNITION
The heater employs a pilot safety which closes the
main gas valve within 8/10ths of a second whenever the
pilot flame is interrupted. Pilot flame is automatically lit
when the device is powered. Unit performs its own
safety check and opens the main valve only after the
pilot is proven to be lit.
22
5' Max.
Содержание Versa 105B Brass
Страница 2: ......
Страница 19: ...WIRING DIAGRAM I I D UNITS IGNITIONDEVICE HONEYWELL Fig 9250 19 ...
Страница 20: ...WIRING DIAGRAM IID UNITS IGNITIONDEVICE ROBERTSHAW Fig 9251 20 ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 ...