TempTracker mod+ Hybrid Installation and Operation Manual
45
HTC# 059105-00D
Modula
tI
on -
o
utdoor
r
eset - B
ac
net V
ar
Ia
B
le l
Ist
Hybrid
r
eset
o
bject I
d
o
bject
type
o
bject
n
ame
u
nits
Value
d
efinition
Min
Max
Model
Device Object
MODEL
Serial Number
Device Object
SNUMBER
Version
Device Object
VERSION
Operation Mode
100
MUL
TIST
ATE-V
ALUE
OPMODE
1
6
1=Modulation Reset, 2=Staging Reset, 3=Hybrid Reset, 4=Modulation Setpoint, 5=Staging Setpoint, 6=Hybrid EMS
Outdoor
Temperature
200
ANALOG-V
ALUE
ODTEMP
Degree F
32000=OPEN,3201=SHOR
T
System
Temperature
300
ANALOG-V
ALUE
SYSSEN
Degree F
32000=OPEN,3201=SHOR
T
Output Status
400
ANALOG-V
ALUE
OPTST
AT
0
0x1FFFF
Each Bit represents one of the possible 16 relays. Bit 0 represents Relay1, Bit 16 represents Relay16. 0 = Relay OFF
, 1 = Relay ON
Control Status
500
MUL
TIST
ATE-V
ALUE
CST
AT
1
13
1=SHUTDOWN,2=NO
TST
AT
CALL,3=PROVE F
AILURE,4=SHUTDOWN
BY
EMS,5=W
AITING FOR PROVE,6=SENSOR F
AUL
T,7=LAST
ST
AGE
HOLD,8=DHW CALL,9=SUMMER,10=BOOST
MODE,1
1=SYSTEM
RUNON,12=SETBACK MODE,13=OUTDOOR CUT
OFF
Season
600
MUL
TIST
ATE-V
ALUE
SEA
1
2
1= Winter
, 2= Summer
Reset Ratio
700
MUL
TIST
ATE-V
ALUE
RR
1
11
1 =1.00 OD = 4.00 Sys,2 =1.00 OD = 3.00 Sys,3 =1.00 OD = 2.00 Sys,4 =1.00 OD = 1.50 Sys,5 =1.00 OD = 1.25 Sys,6 =1.00 OD = 1.00 Sys,,7 =1.25 OD = 1.00 Sys,8 =1.50 OD = 1.00 Sys,9 =2.00 OD = 1.00 Sys,10 =3.00 OD = 1.00 Sys,1
1 = 4.00 OD = 1.00 Sys
Of
fset
800
ANALOG-V
ALUE
OFF
Degree F
-50
50
Integer V
alues Only (-1,0,1,2…)
Outdoor Cutof
f
900
ANALOG-V
ALUE
CO
Degree F
19
101
Integer V
alues Only (19,20,21…)
Min W
ater
Temp
1000
ANALOG-V
ALUE
MINW
Degree F
50
180
Integer V
alues Only (50,51,52…)
Max W
ater
Temp
1100
ANALOG-V
ALUE
MAXW
Degree F
70
220
Integer V
alues Only (70,71,72…)
Setback
1200
ANALOG-V
ALUE
SB
Degree F
0
75
Integer V
alues Only (0,1,2…)
Purge Delay
1300
ANALOG-V
ALUE
PDL
Y
Minutes
.1
10
.1 thru .9 after Integer V
alues Only (1,2,3…)
System Runon
1400
ANALOG-V
ALUE
RUNON
Minutes
0
360
Integer V
alues Only (0,1,2…)
Rotation
Time
1500
ANALOG-V
ALUE
R
TTIME
Hours
1
1440
Hours since last rotation Integer V
alues Only (1,2,3…)
Standby
Time
1600
ANALOG-V
ALUE
STBYDL
Y
Minutes
1
60
Integer V
alues Only (1,2,3…)
Last Stage Hold
1700
ANALOG-V
ALUE
LSTHOLD
Degree F
0
30
Integer V
alues Only (0,1,2…)
Con Lead Stage
1800
MUL
TIST
ATE-V
ALUE
CLEAD
1
16
Represent the current lead boiler for the condensing group
None Con Lead Stage
1900
MUL
TIST
ATE-V
ALUE
NCLEAD
1
16
Represent the current lead boiler for the non-condensing group
Gain
2000
MUL
TIST
ATE-V
ALUE
GAIN
1
10
Lag Delay
2100
ANALOG-V
ALUE
LAGDL
Y
Minutes
0
60
Integer V
alues Only (0,1,2…)
Soft of
f
2200
ANALOG-V
ALUE
SOFF
Seconds
0
60
Integer V
alues Only (0,1,2…)
Set
Time
2300
ANALOG-V
ALUE
PTIME
Minutes
1
1440
Time since midnight Integer V
alues Only (0,1,2…)
Day Schedule
2400
ANALOG-V
ALUE
DSCHED
Minutes
1
1440
Time since midnight Integer V
alues Only (0,1,2…)
Night Schedule
2500
ANALOG-V
ALUE
NSCHED
Minutes
1
1440
Time since midnight Integer V
alues Only (0,1,2…)