Heat Exchanger Reversal Procedure
(Capron Resin Header Models)
1. Remove right and left side access panels (
Figure 1).
2. Disconnect wires at high limit, AGS (automatic gas shutoff), and pressure switch on the inlet/outlet header
(
Figure 2).
3.
Electronic Ignition Heaters:
Remove the thermostat temperature sensor by loosening the compression-
fitting nut (
Figure 3).
Reroute the sensor to the left side of the heater.
4.
Millivolt Heaters:
Remove the temperature sensor bulb and retainer clip from the sensor well (
Figure 4).
Reroute the sensor bulb to the left side of the heater.
5. Remove (12) bolts holding the inlet/outlet and return headers to the tube sheets. Clean off tube sheet area
where the gasket seats. Also clean off the header and its gasket. Apply a non-petroleum based lubricant
to the gasket such as Aqua Lube. Reattach the headers to the opposite sides, making sure they are installed
in an upright position (
Figure 5). Do not over tighten.
Torque should not exceed 7 ft/lbs.
6. Reconnect high limit, AGS, and pressure switch wires.
7.
Electronic Ignition Heaters:
Insert the temperature sensor in the compression fitting and tighten 1/2 turn
past hand tight.
8.
Millivolt Heaters:
Insert sensor bulb and retainer clip into sensor well.
9. Allow for water flow through the heater and check for leaks.
10. Reattach access panels to the opposite sides.
For ASME Models call your factory representative.
18
ACCESS PANEL
Fig. #1
Fig. #2
PRESS SWITCH
AGS
HI-LIMIT
Содержание P-R185A to P-R405A, C-R185A to
Страница 19: ...Fig 4 Fig 5 Fig 3 JACO FITTING BULB CLIP RE INSTALLED IN OUT HEADER ON OPPOSITE SIDE 19 ...
Страница 22: ...WIRING DIAGRAM IID UNITS atmospheric 22 ...
Страница 23: ...WIRING DIAGRAM IID UNITS Low NOx 23 ...
Страница 35: ...35 ...
Страница 37: ...37 ...
Страница 39: ...39 ...
Страница 40: ...40 ...
Страница 41: ...41 ...