40
Boiler Menu
The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well
as software and hardware information
Table Q: Boiler Menu
Item
Application
Description
IGNITION
All
Current State of Ignition
LIMIT TEMP
All
Current Limit Temperature
AUX TEMP
H MODE 3
Current Auxiliary Temperature
EMS Vdc
All
Current EMS signal in Volts DC
FIRE RATE
All
PIM™ firing rate
SPEED X1000 BLOWER All
Blower speed, Revolutions/Minute
HIGH LIMIT
All
High Limit Setting *
H L OFFSET
All
High Limit Offset *
OPERATOR
All
Operator Limit Potentiometer (PIM™) setting
AUTO DIFF
H MODE 1,2,3
Current auto differential
PUMP PREPt
All
Duration of pump prepurge
BLOW PREPt
All
Duration of blower prepurge
BLOW PREPr
All
Blower % during prepurge
BLOW POSTt
All
Duration of blower postpurge
BLOW POSTr
All
Blower % during postpurge
MIN RATE
All
Minimum modulation rate % during operation *
START RATE
All
Start modulation rate % during ignition *
MAX RATE
All
Maximum modulation rate % during operation *
FLAME CUR
All
Flame current in micro-amps
IGN TYPE
All
PIM™ board type
MASS
All
Thermal mass of the boiler
ID CARD
All
Identifies OEM identity card
PIM™ ID
All
Identifies OEM PIM™ PCB
SW ID
All
PIM™ software identification number
* Fixed values based on ID card
Содержание MVB 504A
Страница 44: ...44 WIRING DIAGRAM Models 504A 2004A ...
Страница 58: ...58 ...
Страница 62: ...62 ...
Страница 63: ...63 ...
Страница 64: ...64 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A ...