20

shut-off. Close isolation valves and remove water pip-
ing from the in/out header on the heater. Drain the
heater and any piping of all water that may experience
below-freezing temperatures.

Pool/Spa Water Chemistry

Water Hardness

Water hardness is mainly due to the presence of cal-
cium and magnesium salts dissolved in the water. The
concentration of these salts is expressed in mg/l, ppm
or grains per gallon, as a measure of relative hardness
of water. Grains per gallon is the common reference
measurement used in the U.S. water heater industry.
Hardness expressed as mg/L or ppm may be divided
by 17.1 to convert to grains per gallon. Water may be
classified as very soft, slightly hard, moderately hard
or hard based on its hardness number. The salts in
water will precipitate out when the water is heated and
will cause accelerated lime and scale accumulation on
a heat transfer surface.

Raypak water heaters can operate lime/scale-free
using potable water with a hardness not exceeding 25
grains per gallon. Proper operation is achieved by set-
ting the temperature rise/water flow per the guidelines
in the installation instructions. If the hardness of the
water exceeds the maximum level of 25 grains per gal-
lon special measures must be taken to adjust flow and
temperature rise. Water should be softened to a hard-
ness level no lower than 5 grains per gallon. Water
softened as low as 0 to 1 grain per gallon may be
under-saturated with respect to calcium carbonate
resulting in water that is aggressive and corrosive.

pH of Water

pH is a measure of relative acidity, neutrality or alka-
linity. Dissolved minerals and gases affect water’s pH.
The pH scale ranges from 0 to 14. Water with a pH of
7.0 is considered neutral. Water with a pH lower than
7 is considered acidic. Water with a pH higher than 7
is considered alkaline. A neutral pH (around 7) is desir-
able for most potable water applications. Corrosion
damage and water heater failures resulting from water
pH levels of lower than 6 or higher than 8 are non-war-
rantable. The ideal pH range for water used in a
storage tank or a copper water heater system is 7.2 to
7.8.

NOTE:

Chemical imbalance can cause severe

damage to your heater and associated equipment. 

Total Dissolved Solids

Total dissolved solids (TDS) is the measure of all min-
erals and solids that are dissolved in the water. The
concentration of total dissolved solids is usually ex-
pressed in parts per million (ppm) as measured in a
water sample. Water with a high TDS concentration
will greatly accelerate lime and scale formation in the
hot water system. Most high TDS concentrations will
precipitate out of the water when heated. This can
generate a scale accumulation on the heat transfer
surface that will greatly reduce the service life of a
water heater. This scale accumulation can also
impede adequate flow of water and may totally block
the water passages in the tubes of the heat exchang-
er. A heat exchanger that is damaged or blocked by
lime/scale accumulation must be replaced. Failure of a
water heater due to lime scale build up on the heating
surface is non-warrantable. The manufacturer of the
water heater has no control of the water quality, espe-
cially the TDS levels in your system. Total dissolved
solids in excess of 2,500 ppm will accelerate lime and
scale formation in the heat exchanger. Heat exchang-
er failure due to total dissolved solids in excess of
2,500 ppm is a non-warrantable condition. Raypak
offers basic temperature guidelines for operation of a
potable water heater on normal to moderate levels of
hardness and solids but levels of hardness and total
dissolved solids beyond normal limits for operation will
require special setup and operation.

Gas Supply

Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve lo-
cated outside the heater jacket. It is recommended
that a union be installed in the gas supply piping adja-
cent to the heater for servicing. A pounds-to-inches
regulator must be installed to reduce the gas supply
pressure to  a maximum of 10.5 in. WC for natural gas
and 13.0 in. WC for propane gas. The regulator should
be placed a minimum distance of 10 times the pipe
diameter up-stream of the heater gas controls. Refer
to Table I for maximum pipe lengths.

NOTE:

Failure of a heat exchanger due to lime

scale build-up on the heating surface, low pH or
other chemical imbalance is non-warrantable.

DANGER:

Make sure the gas on which the heater

will operate is the same type as specified on the
heater’s rating plate.

Содержание HIDELTA 992B

Страница 1: ...o do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your...

Страница 2: ...2 Rev 7 reflects the following Changes to Fig 3 on page 6 the UDB Diagnostic Board and UDB Fault History sections on page 44 the Wiring Diagrams on pages 50 and 51...

Страница 3: ...16 Gas Supply 20 Electrical Power Connections 22 Field Wiring Connection 23 Venting 25 Changing the Flue Outlet 27 Venting Installation Tips 28 Venting Configurations 28 Outdoor Installation 33 Contr...

Страница 4: ...defects or other reproductive harm WARNING Risk of electrical shock More than one disconnect switch may be required to deenergize the equipment before servicing CAUTION Operation of this heater in low...

Страница 5: ...only per Raypak s standard war ranties Model Identification The model identification number and heater serial number are found on the heater rating plate located on the lower right outside jacket of...

Страница 6: ...6 OPTIONAL FLUE CONNECTION Component Locations Fig 1 Component Locations Back Fig 2 Component Locations Left Side Panels removed for clarity Fig 3 Component Locations Front...

Страница 7: ...o 1 1A 2 3 4 1 2 3 4 1 2 3 4 992B 6 3 2 1 1 2 1 2 3 54 82 100 1262B 5 3 3 3 1 1 2 1 2 3 1 2 3 4 36 57 79 100 1532B 6 4 4 3 1 1 2 1 2 3 1 2 3 4 35 59 82 100 1802B 6 4 5 5 1 1 2 1 2 3 1 2 3 4 30 50 75 1...

Страница 8: ...stream and read the thermometer NOTE When this water heater is supplying general purpose hot water for use by individuals a thermostatically controlled mixing valve for reducing point of use water te...

Страница 9: ...turn the wheel to the desired setting See Fig 4 CAUTION Hotter water increases the risk of scald ing There is a hot water scald potential if the thermostat is set too high Fig 4 Temperature Controlle...

Страница 10: ...e 4 ft 1 2m below or to side of opening 1 ft 30 cm above opening 3 ft 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above pav...

Страница 11: ...alled location without movement or removal of the heater Service clearances less than the minimums may require removal of the heater to service either the heat exchanger or the burner tray In either c...

Страница 12: ...oint com municating with the outdoors The total cross sectional area shall be at least 1 in 2 of free area per 20 000 BTUH 111 mm2 per kW of total input rating of all equipment in the room when the op...

Страница 13: ...han 100 in 2 645 cm2 One opening shall commence within 12 in 305 mm of the top and one opening shall commence within 12 in 305 mm of the bottom of the enclosure The mini mum dimension of air openings...

Страница 14: ...must be drawn from the air outside of the building the mechanical equip ment room must communicate directly with the outdoors of not less than 1 in 2 for each 30 000 BTUH mm2 per kW of total rated inp...

Страница 15: ...nections to the heater and the rest of the system prior to operation This is particularly true for hydronic systems using expensive glycol based anti freeze Raypak recommends conducting the hydrostati...

Страница 16: ...valve Cold Water Run Cold water run differs from cold water start in that the system water entering the heater remains below 105 F 41 C continuously Typically this is the case in swim ming pool heatin...

Страница 17: ...lation of the heater water during the cooling cycle It is highly recommend ed that the piping be insulated Air Separation Expansion Tank All heaters should be equipped with a properly sized expansion...

Страница 18: ...6 132 19 0 2 26 9 2072B 30 116 14 8 2 21 0 27 132 19 0 2 26 9 27 132 19 0 2 26 9 2342B 30 132 21 4 2 29 3 30 132 21 4 2 29 3 30 132 21 4 2 29 3 Table H Domestic Water Heater Flow Rate Requirements Poo...

Страница 19: ...ening the valve will increase the temperature and closing the valve will decrease the temperature 5 If this process does not raise the inlet water tem perature to 105 F and Valve A is fully open then...

Страница 20: ...severe damage to your heater and associated equipment Total Dissolved Solids Total dissolved solids TDS is the measure of all min erals and solids that are dissolved in the water The concentration of...

Страница 21: ...sure the gas piping is protected from physical damage and freezing where required Reversing Gas Supply Connection Reversing the standard fuel connection from the left hand to the right hand side is a...

Страница 22: ...ons must follow these codes National Electrical Code and any other national state provincial or local codes or regulations hav ing jurisdiction Safety wiring must be NEC Class 1 Heater must be electri...

Страница 23: ...ponents damaged by improper electrical installation are not covered by warranty 4 Provide overload protection and a disconnect means for equipment serviceability as required by local and state code 5...

Страница 24: ...4 Stage Wiring Connection Installer action is required to electrically enable your heater to operate after making the power connections You must make a closed contact connection on Stage 1 connector...

Страница 25: ...AM Fig 25 2 Stage Tankstat SINGLE STAGE TANKSTAT STAGE 1 CONNECTION ATTACH STAGE 1 CONNECTIONS ON HEATER TO THE SINGLE STAGE TANKSTAT AS SHOWN IN THE DIAGRAM ABOVE Fig 26 Single Stage Tankstat Venting...

Страница 26: ...ge or personal injury 3 Gases may form a white vapor plume in winter The plume could obstruct a window view if the ter mination is installed near windows 4 Prevailing winds in combination with below f...

Страница 27: ...require a 4 ft clearance between the ends of vent caps located on the same horizontal plane Canadian Installations Refer to latest edition of B149 Installation code A vent shall not terminate 1 Direct...

Страница 28: ...ncy CAUTION The silicone vent gaskets must be prop erly reinstalled to prevent flue gas leakage Replace any torn or worn vent gaskets WARNING Examine the venting system at least once a year Check all...

Страница 29: ...Seal any unused opening in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and verify there is no block age restriction leakage corrosion or other...

Страница 30: ...ft in length If horizontal run exceeds 70 equivalent ft an appropri ately sized extractor must be used Each elbow used is equal to 10 ft of straight pipe This will allow installa tion in one of the f...

Страница 31: ...orizontal Through the Wall The total length of the through the wall flue cannot exceed 40 equivalent ft in length for the flue outlet Each elbow used is equal to 10 ft of straight pipe This will allow...

Страница 32: ...ted for use with Category III gas burning heaters such as the AL29 4C stainless steel vents offered by Heat Fab Inc 800 772 0739 Protech System Inc 800 766 3473 Z Flex 800 654 5600 or American Metal P...

Страница 33: ...Do not locate adjacent to any window door walk way or gravity air intake The vent must be located a minimum of 4 ft horizontally from such areas 4 Install above grade level and above normal snow level...

Страница 34: ...are verified to ensure that it is safe to operate the heater The safety compo nents wired into the diagnostic board are low water cut off optional blocked vent switch man ual vent temp switch optional...

Страница 35: ...ont status panel 31 A 24 VAC signal is also sent to the TH terminal located on the ignition module 32 Once the 24 VAC TH signal is received at the ignition module the internal contacts between F1 and...

Страница 36: ...pin 3 of the stage 2 connections on the CPW board 51 After closure of the stage 2 contacts Gas valve 2 is energized 52 The stage 2 LED on the status display board is now illuminated 53 Power is appli...

Страница 37: ...e control compartment is now powered If the switch is ON and there is no call for heat CFH the heater is in standby mode 20 After the standby switch is placed into the ON position a 24 VAC signal is s...

Страница 38: ...up before opening gas valve 1 again The standard ignition module will attempt ignition a maximum of three times prior to ignition lockout 48 If ignition module one locks out a signal will be sent to...

Страница 39: ...ond time delay relay will not allow the alarm to sound unless a safety or limit circuit stays ener gized for more than 5 seconds 12 Power is applied to terminal P1 1 of the Universal Diagnostics Board...

Страница 40: ...dicate the fault 38 A 24 VAC signal is now sent to the blower LED s on the status board 39 Power is applied to the optional equipment inter lock connection normally jumpered 40 The 24 VAC signal is th...

Страница 41: ...d by a 120 VAC signal from S 1 on ignition module 2 for approximately 30 seconds The hot surface ignit er must draw greater than 3 1 amps while being energized or ignition lockout will occur after thr...

Страница 42: ...call for heat 3 Flashes Ignition lockout 4 Flashes Low igniter current 5 Flashes Low 24 VAC check control supply voltage 6 Flashes Internal fault Replace module Fig 32 Ignition Module Table N Ignition...

Страница 43: ...tomati cally shuts down the heater if gas supply drops below the factory setting of 5 0 in WC for natural gas and 10 0 in WC for propane gas The high gas pressure switch optional connection mounts dow...

Страница 44: ...ic Board UDB Diagnostic Board This heater is equipped with a diagnostic board which will indicate faults as they occur Refer to the following section for instructions on accessing reviewing and cleari...

Страница 45: ...Hi Delta CAUTION Proper installation of flue venting is criti cal for the safe and efficient operation of the boiler NOTE For additional information on appliance categorization see appropriate code NF...

Страница 46: ...elief valves or other equipment 8 Locate and guard vent termination to prevent acci dental contact by people or pets 9 DO NOT terminate vent in window well stairwell alcove courtyard or other recessed...

Страница 47: ...Steel PVC ABS CPVC 40 75 pressure reading must be between 0 01 and 0 1 in WC as measured 12 in from the appliance flue outlet Each elbow used is equal to 10 ft of straight pipe This will allow install...

Страница 48: ...considered in the overall length of the venting system Care must be taken during assembly that all joints are sealed properly and are airtight The vent must be installed to prevent the potential ac c...

Страница 49: ...vertical height exceeds 25 ft consult factory prior to installation Fig 45 Direct Vent Vertical Table R Category II or IV Vertical Venting Vent lengths are based on a lateral length of 2 ft Refer to...

Страница 50: ...50 Wiring Diagram Models 992B 1262B SEE PAGE 24 FOR STAGING OPTIONS...

Страница 51: ...51 Wiring Diagram Models 1532B 2342B...

Страница 52: ...building Immediately call your gas supplier from a neigh bor s telephone Follow the gas supplier s instructions WARNING If you do not follow these instructions exactly a fire or explosion may result c...

Страница 53: ...ailure Failure to do this may burn out 120V 24V transformer or may cause other safety control damage or failure Start Up Blower Adjustment 1 Turn off power 2 Unplug cap at pressure switches and connec...

Страница 54: ...sed pilot to light the burner sections on either side of it The burn er sections on either side of the supervised section pilot are electrically interlocked with the supervised ignition system so as t...

Страница 55: ...restore electrical power to heater Fig 46 Leak Test This completes leak testing for a single Hi Delta mani fold riser Repeat steps 1 8 for each riser Post Start Up Check Check off steps as completed 1...

Страница 56: ...rn on main manual gas valve 7 Wait 5 minutes to clear out any gas Then smell for gas especially near the floor If you then smell gas STOP Follow the steps in the safety informa tion on the front cover...

Страница 57: ...1 800 947 2975 Outside California 1 800 627 2975 Inside California Replace gas valve Are the gas valve settings correct Replace fan relay Replace fan Replace air pressure switch Correct the air settin...

Страница 58: ...e vapors and liquids 4 Check for and remove any obstruction to the flow of combustion or ventilation air to heater 5 Follow pre start up check in the Start up section 6 Visually inspect burner flame I...

Страница 59: ...t a combustion test at full fire Carbon di oxide should be 7 5 to 8 5 at full fire for natural gas and between 9 2 to 9 8 for propane gas Carbon monoxide should be 150 ppm 5 Check coils for 60 cycle h...

Страница 60: ...ontaminated ar eas this may also experience deterioration Products causing contaminated combustion air spray cans containing chloro fluorocarbons permanent wave solutions chlorinated waxes cleaners ch...

Страница 61: ...o water PARTS REPLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if requested with transportation charges prepaid an...

Страница 62: ...al Dissolved Solids TDS must be no greater than 2500 PPM PARTS REPLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if...

Страница 63: ...ght _______ Low Water Cutoff _______________Test Category _________ sketch vent on reverse side Number of Tanks and Size Qty____ _______Gallons Vent Material __________________ Plumbing Size _________...

Страница 64: ..._________________________________________________________ _____________________________________________________________________________________________ ________________________________________________...

Страница 65: ..._________________________________________________________ _____________________________________________________________________________________________ ________________________________________________...

Страница 66: ..._________________________________________________________ _____________________________________________________________________________________________ ________________________________________________...

Страница 67: ...67...

Страница 68: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: