Raypak DELTA LIMITED 989B-2339B Скачать руководство пользователя страница 6

Catalog No.:  2000.471C 

Effective:  03-15-14 

Replaces:  01-01-14

 

Job:  

         

 

Engineer:  

         

 

 

Contractor:  

         

 

 

Prepared By:  

         

 

 Date:   

         

   

Model:   

         

 

  Indoor/Outdoor:   

         

 

   MBTUH Input:   

         

 

 

 

100% Factory Fire Tested  

Efficiency: 84% 

Maximum Outlet Temperature: 230°F 

Minimum Non-Condensing Inlet Temperature: 105°F 

Thermal Shock Proof Heat Exchanger 

Limited Twenty-Year Thermal Shock Warranty 

Limited Ten-Year Closed-System Heat Exchanger  
Warranty 

PolyTuf Powder Coated Cabinet 

No Combustible Floor Shield Required 

Fan-Assisted 

Patented Burner Security Blanket 

 

Heat Exchanger 

  H Stamp 

  Headers 

 Glass-Lined Cast Iron – Standard  
 Bronze – Option A-1 

  ASME Inspected and Stamped 

160 PSIG Working Pressure 

  National Board Approved 

  Fin Tubing 

 Copper – Standard  
 Cupro Nickel – Option A-3 

  ASME Steel Tube Sheet 

  Silicone High Temp O-Rings 

  ASME Pressure Relief Valve 

 60 PSIG – Standard  
 30 PSIG – Optional  

  Temperature and Pressure Gauge 

  Water Connections 

 Left – Standard  
 Right – Option A-6 

 

Controls 

  120V, 60Hz, 1 Phase Power  

Supply 

  120/24V 60Hz Transformer 

  100% Shut-Off/Lockout 

  Hot Surface Ignition 

  Remote Flame Sensor 

  High Limit Control, Manual Reset 

  On/Off Power Switch 

  Manual Shut-Off, Front-Mounted Switch 

  Flow Switch 

  Blocked Vent Pressure Switch 

  Combustion Air Proving Switch 

  Pump Time Delay Relay 

  Status Display Lights 

Gas Train 

  Manual Gas Shut-Off Valve(s) 

  Combination Valves 

  Low Gas Pressure Switch, Manual 

  Firing Stages 

 2-Stage: Model 989B 
 3-Stage: Model 1259B 
 4-Stage: Models 1529B-2339B  

  Fuel 

 Natural Gas  
 Propane Gas 

  Design Certified - ANSI 

Z21.13/CSA 4.9 

 

 

Burner 

  Ultra-Low NOx: Less than  

20 PPM 

 

Construction 

  Indoor/Outdoor Construction 

  Enclosed Front Controls 

  CSA Low Lead Certified ≤ .25 Pb 

 

Venting 

  Vent Location 

 Top, Outdoor – Standard 
 Top, Indoor – Option D-20 
 Rear – Option D-14 

  Vent Termination Cap  

 Outdoor D-11 
 Indoor, Horizontal D-15 
 Indoor, Vertical (by others) 

  Extractor – Optional  

 By others 
 Not required 

Temperature Controls 

  B-6 

Aquastat, 2-Stage (100-200ºF) 

  B-__  TempTracker Digital Controller, 

2-Stage (Loose) 

  B-__  TempTracker Digital Controller, 

4-Stage (Loose) 

  B-__  TempTracker Mod+ Hybrid (2-

16 Boilers) 

  B-60  Stage Interface 

 

Options  

  C-6 

Ignition Module, Manual Reset 

  F-10  Low Water Cut-Off, Remote 

Probe 

  I-1 

High Limit Control, Auto Reset 

  P-      Pump:            HP, 120V,  

1

, 60Hz 

 

 

 Cast Iron 

 Bronze 

 Mounted 

 Loose 

 

 

 Front 

 Rear 

  P-      Cold Water Start  

(See 2000.48) 

  S-2 

High Gas Pressure Switch, 
Manual 

  X-1 

SureRack™ Kit 

  X-2 

SureRack Add-on 

                       

 

 

Regulatory Agency Requirements 

            

 

 

Delta Limited™ - Type H 

    Space Heating/Hot Water Boiler 

Models 989B-2339B 

 

Shown with outdoor  

air inlet and pump covers 

Proudly Made in the U.S.A. 

 

Delta Limited models not approved for use in California 

H9-1529B

Содержание DELTA LIMITED 989B-2339B

Страница 1: ...1 3 SUBMITTALS A Product data sheet including dimensions rated capacities shipping weights accessories B Wiring diagram C Warranty information D Installation and operating instructions 1 4 QUALITY ASS...

Страница 2: ...C Burners 1 The tubular burners shall have multiport radial gas orifices punched ports and slots be capable of quiet ignition and extinction without flashback at the orifice and be manufactured from...

Страница 3: ...edition Category I 2 When routed horizontally the boiler s flue material and size shall meet or exceed the requirements as specified for Category III in the National Fuel Gas Code ANSI Z223 1 NFPA 54...

Страница 4: ...t is controlled by a system matched PID control that injects the correct amount of cold water directly into the boiler loop to maintain a minimum inlet temperature The PID controller temperature senso...

Страница 5: ...c and full load gas supply pressure 4 Gas manifold and blower air pressure C Submit copy of start up report to Architect and Engineer 3 3 TRAINING A Provide factory authorized service representative t...

Страница 6: ...r Proving Switch Pump Time Delay Relay Status Display Lights Gas Train Manual Gas Shut Off Valve s Combination Valves Low Gas Pressure Switch Manual Firing Stages 2 Stage Model 989B 3 Stage Model 1259...

Страница 7: ...6 12 1520 Pump not included Natural Gas Only Dimensions are in inches Rates shown are for natural or propane gas and elevations up to 4 500 feet For installation above 4 500 feet please contact manufa...