Shut gas and power off to the unit, close the system

off and drain the heater.  Remove the draft diverter.
Remove the access panel and jacket top.  Lift flue
collector off.  Remove “V” baffles over tube(s) to be
replaced.  If no pipe unions have been provided, use the
header as a union, remove the flange nuts off the inlet-
outlet header, break gas connection and slide heater
away from piping to allow room to work.  Pull wedge clips
out of control wells and remove sensing bulbs.  Remove
flange nuts of the return header and remove header.  Lift
heat exchanger straight up and out.

Inspect “O” ring seals at this time.  Unless severed,

they are reusable.  The tube may be cut out with a
hacksaw or hammer and chisel adjacent to both tube
sheets, leaving studs in the tube sheets.  Then proceed
to collapse studs in the tube sheets with a chisel or
screwdriver.  Use caution not to cut into the tube sheet.
Replacement tubes will have the fins stripped off longer
on one end.  The long end is inserted into the opening of
the tube sheet first; then the short end is fitted through the
opposite tube sheet.  If the tube ends become dented or
bent, straighten at least (4) inches back from the tube and
by means of a tapered punch.

Insert tube roller into tube opening up to stop against

tube, then push center rod in until roller is tight.  Be careful
to keep replacement tube squared up 1/8” outside each
tube sheet.  A loose tube will sometimes pull toward the
roller.  Attach drill motor to tube roller, holding it straight
and level.  Proceed to expand tube until the tool begins to
grab.  At this point, 1/2” to 1” should be expose on the tool
shank.  Reverse drill motor or wrench out by hand.  Care
should be exercised to avoid applying excessive torque
during rolling operation and to avoid thinning out any part
of the tube wall excessively over 015’.  Use same
procedure at the opposite end of the tube.

Apply line pressure test, and re-roll, if necessary,

before reassembly of the heater.

DESOOTING PROCEDURE

CAUTION: 

SOOT IS COMBUSTIBLE.  EXERCISE

EXTREME CARE.

Soot will clog areas between fins and cause eventual

tube failure.  Any sign of soot at the base of the burners
or around the outer jacket indicates a need for cleaning.

1. Remove top and flue collector from cabinet.
2. Remove “V” baffles from heat exchanger.
3. Remove burner drawer. (See burner tray

removal).

4. Take garden hose and wash heat exchanger,

making sure soot is removed from between
fins. (Avoid excessive water against
refractory).

5. Reassemble-When heater is fired, some steam

will form from wet refractory.  This is normal.

NOTE:  

In extreme cases it may be necessary to remove

the heat exchanger completely for cleaning.  The
simplest method is steam cleaning at the local car
wash.  DO NOT WIREBRUSH.

COMBUSTION CHAMBER REMOVAL

To remove combustion chamber, you must first have

removed the heat exchanger.  Unbolt metal combination
chamber retainer from top and remove combustion
chamber panels individually.

REFACTORY PANELS TOP VIEW

CONTROL IMMERSION WELL REPLACEMENT

Remove top, sensing bulb and clip.  Collapse well tube

at the open end with a chisel,  push through into header
and remove the header.  Insert a new well and roll into
place.  If a roller is not available, solder.

IMMERSION WELL

Fig. # 8126.0

UNITHERM GOVERNOR (U.G.) REPLACEMENT

1. Shut water, gas and electricity off, close valves

and relieve pressure.

2. Drain heat exchanger.
3. Loosen and remove (2) bolts that secure U.G.

Assembly to header.

4. Remove U.G. Assembly with gasket.
5. Reverse above procedure to re-install.

INLET/OUTLET
HEADER

 UNITHERM

U.G. GASKET

 GOVERNOR

Fig. #8224.0

To test the operation of the Unitherm Governor, place

in hot water (over 100°F) and watch for movement against
spring.  If there is not movement, replace unit.

Содержание 514-824

Страница 1: ...on may result causing property damage personal injury or death WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performe...

Страница 2: ... NOT EXCEED 5 PPM Occasional chemical shock dosing of the poolm or spa water should not damage the heater providing the water is balanced Automaticchemicaldosingdevicesandsaltchlorinatorsareusuallymoreefficient in heated water unless controlled they can lead to excessive chlorine level which can damage your heater Furtheradviceshouldobtainedfromyourpoolorspabuilder accreditedpoolshop or chemical s...

Страница 3: ...RECEIVING EQUIPMENT 7 SECTION2 GENERALSPECIFICATION 7 SECTION3 INSTALLATIONINSTRUCTIONS 8 Base Installation 8 Clearances 9 CombustionAir 9 VentingConnections Outdoor 11 Gas Supply Connections 12 Plumbing for Water Connections 14 Electrical Wiring 15 WiringDiagrams 19 SECTION 4 SERVICING INSTRUCTIONS 19 General Location of Controls 19 Controls Adjustments Replacements 23 SECTION 5 TROUBLESHOOTING G...

Страница 4: ...IONS SYSTEMS A This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand B BEFORE OPERATING smell all around the appli ance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch...

Страница 5: ...POSITION THE ON POSITION GAS INLET Fig 8220 0 7 Wait fire 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 8 For Models 514 724 Turn gas control knob counter clockwise to On For Model 824 Turn main gas shut off and pilot shut off valves clockwise to on 9...

Страница 6: ... is suggested for young children 2 Drinking of alcoholic beverages before or during spa or hot tub use can cause drowsiness which could lead to unconsciousness and subsequently result in drowning 3 Pregnant Women Beware Soaking in water over 102 F 39 C can cause fetal damage during the first three months of pregnancy resulting in the birth of a braindamaged or deformed child Preg nant women should...

Страница 7: ...om the carton and if it is damaged report the damage to the carrier immediately On occasion we ship some items loose Be sure that you receive the number of packages indicated on the Bill of Lading When ordering parts you must specify model and serial number of heater When ordering under warranty conditions you must also specify date of installation Raypak recommends that this manual be reviewed th...

Страница 8: ... from or one 1 foot above any door window or gravity inlet to a building The top surface of the heater shall be at least three 3 feet above any forced air inlet or intake ducts located within ten 10 feet horizontally Installation must be in accordance with local codes or in the absence of local codes with the latest edition of the National Fuel Gas Code ANSI Z223 1 and National Electrical Code ANS...

Страница 9: ...624 627 824 825 b All air from outdoors When air is supplied directly from outside of build ing each opening shall valve a minimum net free square inches as noted Model Square Inches 514 128 624 157 724 182 824 207 VENTING CONNECTIONS VENTTERMINAL Outdoor STEP 1 Loweroutdoor Stackless topontounit Positiontopso it is centered on unit from side to side and front to rear STEP 2 Tighten the 4 screws S...

Страница 10: ... while the other appliances remain ing connected to the common venting system are not in operation a Seal any unused openings in the common ventingsystem b Visually inspect the venting system for proper size and horizontal pitch and deter mine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condition c Insofar as is practical close all build...

Страница 11: ...gas connections shall be leak tested before placing the appliance in operation Use soapy water for leak test Do NOT use open flame NOTE Do not use teflon tape on gas line pipe thread A flexible sealant is recommended A minimum of 7 W C and a maximum of 14 W C upstream pressure under load and no load conditions must be provided for natural gas or a minimum of 12 W C and a maximum of 14 for propane ...

Страница 12: ...CAUTION NEVER install PVC directly into heater Four feet of copper or high temperature pipe and two elbows are required between the heater and the PVC connections Fig 8129 0 12 Whenlocalcodespermittheuseoflessthanfourfeet hightemperaturepipingortwoelbows provisionsshould be made to always shut the heater off a minimum of 15 minutes prior to pump shut down in order to carry away residualheatandprev...

Страница 13: ...formance pump size larger than two HP will exceed this flow rate This valve is required to complement the function of the automatic bypass valve particularly when starting the heater in winter or early spring when the spa or pool temperature is down below 55 F It also serves to eliminate needless pressure drop through the heat and accompanying reduction in the flow rate to the spa jets etcetera FR...

Страница 14: ...a dual voltage trans former for 120V or 240V input power hookup 14 S8600 IGNITION CONTROL Fig 8929 1 For 120 V input power to the unit connect the black wire to the L1 or hot leg of the power supply Connect the white wire to the L2 or neutral leg of the power supply Attach the wire nut to the red wire There should be no connection to the red wire for 120V operation Fig 9240 For 240 V input power t...

Страница 15: ...15 ...

Страница 16: ...16 151965 824 825 000 BTUH ...

Страница 17: ...17 152141 514 724 512 000 THRU 726 000 BTUH 5 ...

Страница 18: ...18 152142 824 825 000 BTUH 6 ...

Страница 19: ...MECHANICAL THERMOSTAT Fig 8060 1 TYPICALCOMFORTABLE SPATEMPERATURE RANGE KNOBSTOP RING SET SCREW TYPICAL COMFORTABLE POOL TEMPERATURE RANGE Fig 8104 0 KNOBSTOPADJUSTMENT If desired a higher setting of the thermostat can be obtainedbyadjustingtheknobstopringonthedialplate Loosenthesetscrew adjusttheknobstopforthehigher desiredtemperaturesettingandretightenthesetscrew 19 SECTION4 SERVICINGINSRUCTION...

Страница 20: ...eheater makes banging noises In these cases the pump must be run at high speed when heating the water CAUTION Do not operate the heater without the function of a properly adjusted pressure switch HIGHLIMITS Theheaterisequippedwithtwoautomatichighlimits Set to operate at 135 F and 140 F NOTE An erratic high limit is often characteristic of internal heat exchanger problem i e scale build up U G oper...

Страница 21: ...on panels 4 Loosen bolts and disconnect flange nuts on inlet outlet header loosen union s at gas pipe and slide boiler away from piping until stud clear the header 5 Remove heat exchanger corner brackets 6 Remove combustion chamber slips at the four corners of the heat exchanger 7 Lift heat exchanger straight up using caution not to damage refractory 8 Reverse above procedure to reinstall TUBECLEA...

Страница 22: ...idthinningoutanypart of the tube wall excessively over 015 Use same procedure at the opposite end of the tube Apply line pressure test and re roll if necessary before reassembly of the heater DESOOTINGPROCEDURE CAUTION SOOT IS COMBUSTIBLE EXERCISE EXTREME CARE Sootwillclogareasbetweenfinsandcauseeventual tube failure Any sign of soot at the base of the burners or around the outer jacket indicates ...

Страница 23: ... Lowgaspressure Insects or debris clogging burnerintakeports Broken refractory caused by shippingdamageorimpropercombustion Excessive sooting of heat exchanger Calculatetemperaturein hr Filternotrunninglongenough Dirtyfilter Gas line or meter undersized SOLUTION Check movement by putting in hot water 110 F or higher If no movement replace Locate the restriction and remove Flush system and clean Re...

Страница 24: ...ce heat exchanger and maintain chemistry properly See pressure switch adjustment Replacerefractory Determine cause of sooting and correct Bypassingtoomuchwater U G notfunctioning Overacid Overacid Heaterrunningafterpumpshutsoff Refractorydamage Sootedheater Liming Leaking at well Leaking at heat exchanger Gasketbrittleandleaking overheated 24 ...

Страница 25: ...ff pilot gas if pilot fails to light To reset interrupt power to heater Intermittent Pilot System TROUBLESHOOTING HONEYWELL S8600 NOTE Before troubleshooting familiarize yourself with the startup and checkout procedure Check line voltage power low voltage transformer limit controller thermostat control ler and wiring Pull ignition lead and check spark at module SparkOkay YES Check ignition cable g...

Страница 26: ... under standard companywarrantiesmustbeproperlytaggedwithRAYPAK returnpartstag completelyfilledinwiththeheaterserial number model number etc and shipped to the Com pany freight prepaid If determined defective by the Company and within warranty the part will be returned in kind or equal substitution freight collect Credit will not be issued Raypak Inc 31111 Agoura Road Westlake Village CA 91361 ...

Страница 27: ...this page is empty ...

Страница 28: ...28 PILOTASSEMBLY ELECTRONICIGNITION PILOTASSEMBLY STANDINGPILOT Fig 9293 Fig 9294 ...

Страница 29: ...29 ...

Страница 30: ...30 ...

Страница 31: ......

Страница 32: ...RAYPAK INC 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 FAX 800 872 9725 Litho in U S A www raypak com ...

Отзывы: