ADJUSTMENTS/REPLACEMENTS OF
COMPONENTS

CAUTION:

 

Label all wires prior to disconnection when

servicing controls.  Wiring errors can cause improper and
dangerous operation.  Verify proper operation after ser-
vicing.

DANGER - SHOCK HAZARD
Make sure electrical power to the heater is disconnect-ed
to avoid potential serious injury or damage to com-
ponents.

GAS VALVE REMOVAL
1.

Shut off gas supply to the heater.  Remove gas
piping to gas valve inlet.

2.

Disconnect wires, pilot tubing and bleed line, if
required.

3.

Turn vertical gas pipe from manifold slightly and
unscrew gas valve.

4.

Reverse above procedure to re-install.

PILOT REMOVAL AND CLEANING
1.

Disconnect pilot tubing at pilot and  sensor/ignitor
wire.  Remove screws holding  pilot bracket to
burner drawer.

2.

Remove pilot and bracket, clean pilot of debris,
small bugs, etc., with wire or small brush.

3.

Replace pilot, pilot tubing, sensor ignition wires
and check for leaks.

BURNER DRAWER REMOVAL
1.

Shut off power and gas supply to the heater.
Disconnect union(s) and pilot tubing, then
 loosen and remove burner hold down screws.

2.

Disconnect wires at gas valve and slide burner
drawer out.

MAIN BURNER AND ORIFICE REMOVAL
1.

 Remove screws and burner hold down bracket.

NOTE: If the heat exchanger is sooted badly, the burner
hold down bracket and spacer can become distorted
from direct flame impingement and this usually necessi-
tates replacement of these parts.

2.

Lift burners from slotted spacer and slide from
orifices.  Clean with a wire brush.

3.

Orifices usually do not need to be replaced.
To clean, run either copper wire or wood
through orifice.  Do not enlarge hole.  To remove
orifice, use a socket wrench and remove the
manifold.  DO NOT overtighten when reinstall-
ing.

30

HIGH LIMIT OR TANKSTAT REMOVAL
1.

Turn off electrical power.

2.

Remove front inspection panel.

3.

Remove wires to high limit and loosen screws
holding high limit to cabinet.

4.

Remove wedge clip holding sensing bulb in
control well.

5.

Remove high limit and install a new one.

6.

Check control operation before leaving job.

FLAME ROLL-OUT SWITCH REPLACEMENT
1.

Shut off electrical power to the heater.

2.

Remove wiring connections to switch.

3.

Remove  screws (2) holding the switch.

4.

Reverse above procedure to re-install.

VENT THERMAL SWITCH REPLACEMENT
1.

Shut off electrical power to the heater.

2.

Remove wiring connections to switch.

3.

Remove the screws (2).

4.

Reverse above procedure to re-install.

IGNITION MODULE REPLACEMENT
1.

Shut off electrical power to the heater.

2.

Remove control cover  screws and open
control compartment.

3.

Disconnect wiring connections to module.

4.

Remove screws (2) holding module.

5.

Reverse above procedure to re-install.

TRANSFORMER REPLACEMENT
1.

Shut off electrical power to the heater.

2.

Remove control cover screws and open control
compartment.

3.

Disconnect wiring connections from
transformer leads.

4.

Remove screws (2) holding transformer.

5.

Reverse above procedure to re-install.

CIRCULATOR REPLACEMENT
1.

Shut off electrical power to the heater.

2.

Shut off water supply and open drain valve
to remove water in the  piping at the pump
level.

CAUTION

To avoid damage to electrical components

keep water  from getting into the control compartments
and gas valve.

3

.

Disconnect wiring and conduit connections to
the pump.

4.

Remove the nuts and bolts at the inlet and
outlet flanges.  Remove old gaskets.

5.

Remove the pump.

6.

Reverse the above procedure to re-install.
Use new gaskets and make sure they are
seated properly when tightening the nuts
and bolts.

Содержание 260-401

Страница 1: ...s of life Refer to this manual Installation and service must be performed by a qualified installer service agency or the gas supplier FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS Do not try to light an...

Страница 2: ...l Wiring 14 Wiring Diagrams 19 4 SERVICING PROCEDURES 19 Sequence of Operation 19 Start Up Procedures 24 Inspection Procedures 25 Repair Section 26 5 TROUBLE SHOOTING GUIDE 30 Adjustments Replacements...

Страница 3: ...answer please contact your local Raypak representative 2 GENERAL SPECIFICATIONS TheRaypakwaterheatersaredesigncertifiedbytheand testedundertherequirementsoftheAmericanNational Standard ANSI Z21 10 3...

Страница 4: ...light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building Leave the building immediately and make sure that every one else leaves also Leave the doors open for venti...

Страница 5: ...injury and may be used as a guide in determining the safest water temperature for your applications Temperature Time to Produce Serious Burn 120 F More than 5 minutes 125 F 1 1 2 to 2 minutes 130 F A...

Страница 6: ...service circulatorreplacement controlreplacement etc CLEARANCE REQUIREMENTS FOR ALL MODELS 1 Minimum clearances from combustible surfaces Floor Front Back Right Left Top Top Flue Indoor Outdoor Vent 1...

Страница 7: ...inches as follows Model Sq In Of Free Area 260 261 66 330 331 84 400 401 100 Location of the openings is the same as in the previous case that is within 12 inches of the top and within 12 inchesofthe...

Страница 8: ...ded 3 Route flue sensor wire harness through the grommet installed in Step 2 Fig 9351 4 Remove door and locate wire from roll out sensor to Hi Limit with the male female connector BeforeInstallationof...

Страница 9: ...aft hood outlet is recommended however when the total vent height is at least ten 10 feet draft hood relief opening to vent terminal the vent pipe size may be reduced as specified in the National Fuel...

Страница 10: ...ate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers d Place in operation the appliance being inspected Follow the lighting instructions Adjust tankstat so appliance will...

Страница 11: ...as pressure upstream of the gas valve and downstream which is the same as the manifold pressure The gas pressure regulator is preset and sealed at 4 W C for natural gas and 11 W C for propane gas Betw...

Страница 12: ...at the time of installation No valve is to be placed between the relief valve and the storage tank The pressure rating of the relief valve must not exceed the 160 maximum working pressure indicated o...

Страница 13: ...a disconnecting means within sight of the heater Remove the control box cover and make the power supply connections in the field wiring compartment The pump is supplied and factory wired to operate wi...

Страница 14: ...PILOT MODELS 260 400 NOTES USE GROUND CLIP PROVIDED PUMP DELAY ADJUSTABLE BETWEEN 3 AND 10 MINUTES VENT TEMP SWITCH PROVIDED ONLY ON INDOOR HEATERS ROLL OUT AND VENT SWITCHES NOT REQUIRED ON MODELS 33...

Страница 15: ...TIGNITIONDEVICE IID MODEL 260 15 NOTES USE GROUND CLIP PROVIDED FAILURE TO PROVIDE PROPER GROUND MAY RESULT IN LOCK OUT PUMP DELAY ADJUSTABLE BETWEEN 3 AND 10 MINUTES VENT TEMP SWITCH PROVIDED ONLY ON...

Страница 16: ...ENTIGNITIONDEVICE IID MODELS 330 400 16 NOTES USE GROUND CLIP PROVIDED FAILURE TO PROVICE PROPER GROUND MAY RESULT IN LOCK OUT PUMP USED MUST BE RATED 10 AMPS MAX OR 3 4 HP MAX PUMP DELAY ADJUSTABLE B...

Страница 17: ...17 WIRING DIAGRAM INTERMITTENT IGNITION DEVICE IID MODEL 261 LOW NOx...

Страница 18: ...18 WIRING DIAGRAM INTERMITTENT IGNITION DEVICE IID MODEL 401 LOW NOx...

Страница 19: ...ircuitiscompletedbetweenthesensorand burner ground The flame sensing circuit in the module detects the flame current shuts off the spark generator and energizes the second main valve operator which op...

Страница 20: ...GASCONTROL KNOBSHOWN IN OFF POSITION GASINLET NOTE Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force 6 Wait five 5 minutes to clear out any gas Then smell for gas...

Страница 21: ...ry to light the pilot by hand B BEFORE OPERATINGsmell all around the heater area for gas Be sure to smell next to the floor because some gases are heavier than air and will settle on the floor WHAT TO...

Страница 22: ...ade c Gas valve will shut off main burners after about three 3 minutes End of test If the gas valve 22 will not shut off follow the instructions To Turn Off Gas To Heater and call service technician o...

Страница 23: ...er with gas supply off 2 Check ignition module as follows a Set the thermostat or controller to call for heat b Watch for continuous spark at the pilot burner c Check the ignition spark operation Time...

Страница 24: ...ews from control box Open the control box 3 Remove the pilot wire from the ignition wire 4 Remove 2 screws that mount the pilot bracket to the air manifold assembly 5 Pull the pilot bracket downwards...

Страница 25: ...up recheck all air vents and expansion tank levels COMBUSTIONCHAMBERREMOVAL Toremovecombustionchamberyoumustfirsthave removed the heat exchanger Unbolt metal combustion chamberretainerfromtopandremov...

Страница 26: ...e power is on 2 Check continuity on thermostat and wiring circuit Replace thermostat or repair wiring connections 3 Check secondary voltage If no 24V replace transformer 1 Light pilot burner Follow li...

Страница 27: ...er to installation instructions regarding combustion air requirements 2 Refer to installations instructions 3 See yellow flame section above 3 Pilot Outage Standing pilot models 4 Yellow lazy flame 5...

Страница 28: ...s off pilot gas if pilot fails to light To reset interrupt power to heater NOTE Before troubleshooting familiarize yourself with the start up and checkout procedure Check line voltage power low voltag...

Страница 29: ...NOTLIGHT CHECK FOR 24 V CHECKTHERMOCOUPLE AT GAS VALVE IF NOT 24 V IF 24 V IF O K IFDEFECTIVE CHECKTRANSFORMEROUPUT REPLACE FOR 24 V GAS VALVE REPLACE REPLACE GAS VALVE THERMOCOUPLE IF NO IF 24 V 24V...

Страница 30: ...ce use a socket wrench and remove the manifold DONOTovertightenwhenreinstall ing 30 HIGHLIMITORTANKSTATREMOVAL 1 Turnoffelectricalpower 2 Removefrontinspectionpanel 3 Remove wires to high limit and lo...

Страница 31: ...lling operation and avoid thinning any wall of the tube beyond 0 015 10 Use same procedure on opposite end 11 Apply line pressure test Re roll if necessary 12 ReinstallasoutlinedunderHEATEXCHANGER REA...

Страница 32: ...32 FOR UNITS WITH A LOW NOx TRAY...

Страница 33: ...33...

Страница 34: ...34...

Страница 35: ...ver on parts not manufactured by it but Raypak will apply any such warranty as may be provided to it by the parts manufacturer TO MAKE WARRANTY CLAIM Promptly notify the original installer supplying t...

Страница 36: ...ak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 FAX 800 872 9725 Raypak Canada LTD 2805 Slough Street Mississauga Ontario Canada L4T 1G2 905 677 7999 FAX 905 677 8036 Litho in U S A www raypak...

Отзывы: