Wiring a Power Vent Assembly

to an Appliance with IID

Ignition

Venting

The vent pipe must be the same size or one size larg-

er than what is indicated. The D-2 Power Vent is

capable of 360-degree discharge rotation and oper-

ates with a positive vent static pressure and with a

vent gas temperature less than 400°F.

The total

length of horizontal run shall not exceed an equiv-

alent of 40 feet including termination cap.

For all

cases, each 90-degree elbow reduces the maximum

horizontal vent run by 10 feet and each 45-degree

elbow in the vent run reduces the maximum vent run

by 5 feet. See the table below for maximum vent

lengths using 90-degree and 45-degree elbows.

The D-2 Power Vent uses positive pressure to push

flue gases through the vent pipe to the outside. The

vent must be installed to prevent flue gas leakage.

Care must be taken during assembly to ensure that all

joints are sealed properly and are airtight.

The vent must be installed to prevent the potential

accumulation of condensate in the vent pipes. It is rec-

ommended that:

a) The vent be installed with a slight downward slope

of not more than 1/4” per foot of horizontal run to the

vent terminal.

b) The vent be insulated through the length of horizon-

tal run.

For appliances installed in extreme cold climate, it is

recommended that:

a) The vent be installed with a slight upward slope of

not more than 1/4” per foot of horizontal run to the vent

terminal. In this case, an approved condensate trap

must be installed per applicable codes.

b) The vent be insulated through the length of the hor-

izontal run.

Fig. 4: Draft Assembly

The Raypak Power Vent operates with a positive vent

static pressure and with a vent gas temperature that

avoids excessive condensate production in the vent

and as such it is listed as a

CATEGORY III

appliance.

Exception: When a Power Vent is connected to a ver-

tical vent of sufficient height to generate a negative

draft in the system. Consult sizing guide or factory.

The D-2 Power Vent assembly is suitable for through

the wall venting, and for connection to smaller size

vent pipes and breeching other than the standard

atmospheric heater.

WARNING:

Disconnect all electrical power to the

unit before servicing to avoid potential shock injury

or damage to the unit. To change voltages, follow

wiring diagram for correct voltage connections.

Improper wiring connections can burnout the relay

and blower motor.

90 Degree Elbows

45 Degree Elbows

Quantity

Maximum

Length (ft)

Quantity

Maximum

Length (ft)

1

30

1

35

2

20

2

30

3

10

3

25

Table C: Reduced Maximum Equivalent Vent Run

LEFT SIDE

4"

DIAMETER

Содержание 181/182

Страница 1: ...n an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a...

Страница 2: ...8 reflects the following Changes to Fig 2 on page 5 Fig 4 on page 7 Fig 5 on page 8 Dimensional Drawing on page 13 Illustrated Parts List on page 15 Additions Note on page 4 Wiring Diagrams on pages...

Страница 3: ...presence of hazards or unsafe practices which could cause severe personal injury death or substantial property damage if ignored CAUTION Indicates the presence of hazards or unsafe practices which co...

Страница 4: ...blower with a 120 240 volt 60 Hz 1 0 1 95A 3200 RPM motor a plenum complete with a draft proving switch and a motor relay When provided for field mounting the assembly is equipped with a wire harness...

Страница 5: ...t down to the appli ance 10 If the appliance is a 181 182 330 or 331 remove the tabs underneath the power vent using a 5 16 nut driver and relocate them closer to the center of the Power Vent as shown...

Страница 6: ...e 4 ft 1 2m below or to side of opening 1 ft 30 cm above opening 3 ft 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above pav...

Страница 7: ...d through the length of horizon tal run For appliances installed in extreme cold climate it is recommended that a The vent be installed with a slight upward slope of not more than 1 4 per foot of hori...

Страница 8: ...ctive controls in the heater control box The harness is of sufficient length to fit the appliance for which it is sized Reference the wiring diagram supplied with each appliance for actual connections...

Страница 9: ...9 Wiring Diagrams 182 260 H4 WH1 Atmospheric...

Страница 10: ...10 181 261 H4 WH1 Low NOx...

Страница 11: ...11 Wiring Diagrams 330 400 H4 WH1 Atmospheric...

Страница 12: ...12 331 401 H4 WH1 Low NOx...

Страница 13: ...TA Model No A B C D 181 18 13 12 38 7 88 4 25 182 18 13 12 38 7 88 4 25 260 18 13 12 38 7 88 4 25 261 18 13 12 38 7 88 4 25 330 17 50 15 75 7 63 6 00 331 17 50 15 75 7 63 6 00 400 17 50 15 75 7 63 6 0...

Страница 14: ...power switch 4 Set operating control to call for heat a Fan motor starts draft proving switch clos es b Heater pump starts flow switch closes c Ignition module energized d Check for spark at gas pilo...

Страница 15: ...8 6 8 0 0 x o B e u l F 5 6 Base Assembly 008684F 008685F F 6 8 6 8 0 0 F 6 8 6 8 0 0 r a l l o C e u l F 7 F 8 8 6 8 0 0 F 7 8 6 8 0 0 r o t p a d A e u l F 8 F 9 8 6 8 0 0 F 9 8 6 8 0 0 e g n a l F...

Страница 16: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: