Electrical Wiring
WARNING
To reduce risk of SEVERE INJURY or DEATH to persons:
•
All electrical wiring should be permanent and should be done by a qualified professional
and in accordance to local electrical codes.
•
Always shut OFF the main power before performing any electrical intervention.
•
Use proper wire gauge for incoming power line. Use copper conductors only.
•
Use cable type CL2, CL2P, CL2R, or CL2X complying with the Standard “UL13 - Power-
Limited Circuit Cables” for accessory connections.
•
Install operator main circuit breaker next to operator for easy access for power shut-off.
•
Use separate knockouts on operator control box for accessories and main power cables.
•
Always separate low and high voltage wires.
•
Operator should be properly grounded to the building ground and to the main power
supply ground lug.
•
Always use suitable and appropriate rating circuit breakers for operator protection.
•
Compare available power supply voltage to voltage on operator name plate prior to
electrical connection. Failure to connect appropriate power supply voltage may cause
serious damage to the operator.
NOTICE
•
THE OPERATOR MUST BE ADEQUATELY PROTECTED AGAINST OVERCURRENT AND SHORT-
CIRCUIT.
•
PLEASE REFER TO LOCAL ELECTRICAL CODE.
•
PLEASE REFER TO NATIONAL ELECTRIC CODE (NFPA 70) ARTICLE 430 SECTION IV (430.51 /
430.52 / 430.53).
•
PLEASE REFER TO CANADIAN ELECTRIC CODE (CSA 22.1) SECTIONS 28-200 / 28-206.
Guideline to determine the branch-circuit rating of the protective device [A]:
Time Delay Fuse: 1.75 x
FLA
Non-Time Delay Fuse: 3.0 x
FLA
A fuse, which does not exceed the next standard amperage value, shall be permitted.
Example: If
FLA = 5.0A
•
Time Delay Fuse: 1.75 x
5.0A
= 8.75A → Standard fuse to use: 10A
•
Non-Time Delay Fuse: 3.0 x
5.0A
= 15.0A → Standard fuse to use: 15A
For technical support, please call
1-800-4-Raynor (1-800-472-9667)
or visit
www.raynor.com
FLA = Full Load Amp
Содержание ControlHoist CMT
Страница 39: ...39 Notes For technical support please call 1 800 4 Raynor 1 800 472 9667 or visit www raynor com ...
Страница 40: ...40 Notes For technical support please call 1 800 4 Raynor 1 800 472 9667 or visit www raynor com ...
Страница 41: ...41 Notes For technical support please call 1 800 4 Raynor 1 800 472 9667 or visit www raynor com ...
Страница 42: ...42 Notes For technical support please call 1 800 4 Raynor 1 800 472 9667 or visit www raynor com ...