Wuhan Raycus Fiber Laser Technologies Co., Ltd.
User Guide of RFL-C4000S-CE
16
c) Cooling water requirements:
1
)
It is recommended to use purified water.
2
)
In order to prevent mould growing that may lead to pipe blockage, we recommend to
add alcohol about 10% of the total volume.
3
)
If the product is used in an environment that ambient temperature is between -10
℃
and 0
℃
, we recommend to use 30% alcohol, and replace it every two months.
4
)
If the product is used in an environment that ambient temperature is below -10
℃
,
please to use dual-system chillers (with heating function) and ensure uninterrupted
operation of the cooling system.
d)
Requirements for output cable cooling system:
1
)
Rate of liquid flow: 1.7-2.0 L/min;
2
)
Pressure of liquid flow: < 0.6 MPa at the inflow;
3
)
Type of liquid exchange junction: SMC MS-5H-6:
4
)
Type of tube: outer diameter6; inner diameter4;
5
)
Direction of cooling liquid: unidirectional; connect the tube with the water-pipe
strictly according to direction shown on the layer of the tube;
6
)
Type of liquid: de-ionized water, condensed water, pure water;
7
)
PH value of liquid: 5.5-9;
8
)
Filter is needed for the cooling system, and the size of the solid residual practical
should be within 100um;
9
)
Maximum temperature of liquid: 45
℃
:
10
)
Minimum temperature of liquid: greater than the saturated dew-point 5
℃
;
11
)
Additive to the liquid: satisfies the requirements of PH value and size of solid
residual practical as above;