No user maintenance is required! There are no user 

adjustments or calibrations that can be performed in the field.

Each TTA-SIM is tested and calibrated at the factory. An 

operating TTA-SIM runs a continuous self check routine and 

reports any discrepancies to the TTDM-128 or host computer. 

If the TTA-SIM or the network wiring fails in such a way that 

the TTA-SIM cannot communicate with the host, then the host 

reports the failure as a communications failure.

Status Indicators

There are 5 LED’s on the TTA-SIM-1A circuit board to indicate: 

power, communications (inbound and outbound), sensor status 

(leak detected and trouble). See Figure 9.
The green Power LED will be ON and will blink once every 

5 seconds when the TTA-SIM is powered and fuctioning 

correctly. Table 1 lists various sensor status conditions and 

possible corrective actions. Table 2 lists communication status 

conditions (applicable when the TTA-SIM is used in a  

network system).

Figure 9. TTA-SIM-1A LED positions (all LEDs are located on the 

TTSIM unit)

Table 1.  TTA-SIM-1A LED operational status indications

Table 2.  TTA-SIM communication status indications 

(only active if connected to a network)

Leak

Service

Indication

TX

RX

Indication

FLASH

Leak detected. Check sensor for leak or spill.

FLASH

FLASH

Unit is communicating normally with TTDM-128 

or host.

ON

Leak alarm has been reset by operator but the 

leak condition still exists

OFF

FLASH

Unit is receiving communication from TTDM-128 

or host, but is not responding. 

FLASH

The sensor needs servicing. Check sensor 

and leadwires/jumpers for continuity or 

contamination. 

OFF

ON

RS-485 communication wires are reversed

OFF

OFF

Unit is not communicating with TTDM-128 or host. 

TX (Yellow)

RX (Yellow)

TRACETEK

Power (Green)

Service (Yellow)

Leak (Red)

INPUT: 92- 132 Vac

50/60 Hz 3VA

RS–

RS–

Operating Instructions: TTA-SIM-1A

No user maintenance is required! There are no user adjustments or 

calibrations that can be performed in the field.

Each TTA-SIM is tested and calibrated at the factory. An operating 

TTA-SIM runs a continuous self check routine and reports any 

discrepancies to the TTDM-128 or host computer. If the TTA-SIM 

or the network wiring fails in such a way that the TTA-SIM cannot 

communicate with the host, then the host reports the failure as a 

communications failure.

Status Indicators

There are 5 LEDs on the TTA-SIM-2 to indicate: power, 

communications (RX=inbound and TX=outbound), sensor status  

(leak detected and trouble). There is also a Reset pushbutton  

which is used to acknowledge or reset alarms or for updating the 

location display. See Figure 10 for the location of the LEDs and  

RESET pushbutton.
The green Power LED will be ON and will blink once every 5 seconds 

when the TTA-SIM-2 is powered and fuctioning correctly. Table 3 

lists various sensor status conditions and possible corrective 

actions. Table 4 lists communication status conditions  

(applicable when the TTA-SIM is used in a network system).

Figure 10. TTA-SIM-2 LED positions (all LEDs are located on the TTSIM unit)

TX (Yellow)

RX (Yellow)

Power (Green)

Service (Yellow)

Leak (Red)

Reset pushbutton

TRACETEK

Operating Instructions: TTA-SIM-2