background image

2  |  nVent.com/RAYCHEM

Note: 

To avoid damage to the TTA-SIM, store the unit in its packaging until ready to install.

SELECTING THE MOUNTING POSITION

Choose a location where the module will be protected from  

the elements, temperature extremes or heavy vibration.  

The TTA-SIM is designed to be wall mounted at any location  

as long as it does not create a tripping hazard or expose the 

TTA-SIM to impact damage.

MOUNTING THE TTA-SIM

• Plan cable/conduit alignment and drill holes as necessary. 

Cable entries should all be located in the open space at the 

right hand of the TTA-SIM (see Figure 2). A typical installation 

will require holes to accommodate the following cabling:

- Incoming power supply
- TraceTek sensor leadwire
- [optional] telemetry cable (for RS-485 communication)
- [optional] cable for relay contacts to remote alarm

• Secure the TTA-SIM enclosure to any convenient vertical 

surface using the four corner mounting holes and hardware 

suitable for the selected surface.

• Rough-in conduit as required and pull the cables for power and 

telemetry. Leave approximately 20 cm (8 in) for connection to 

TTSIM terminals. Pull in the sensor circuit leader cable.

Note

: Rough-in and final connections do not have to be 

completed at the same time, however, make sure to replace the 

cover and tighten the cover screws if the enclosure will be left in 

a partially installed condition overnight or longer.

Figure 2. Cable entry locations

POWER SUPPLY OPTIONS

The TTA-SIM has two power supply options available. Depending 

on the version being installed and local regulations, the wiring 

requirements may vary. In all cases, be sure that each TTA-SIM 

receives supply voltage from one and only one source.

Important

: Power supply voltage must be within range specified 

on TTA-SIM label (located on inside of enclosure cover;  

the information is also located on TTSIM top label).

CONNECTIONS FOR POWER

Power and ground (earth) connections to the TTA-SIM are made 

using the large cage-clamp power terminal blocks at the right 

end of the DIN rail as shown in Figure 3. Cut back the power 

wires to fit and strip to expose approximately 6 mm (1/4 in) of 

conductor. Push the tip of a small flat-blade screwdriver into 

the cage clamp actuator to open the terminal, then insert the 

wire into the terminal and release the clamp by removing the 

screwdriver.

Note

: In order to provide maximum electrostatic discharge 

protection, and to be CE compliant, the TTA-SIM must  

be grounded.

Figure 3. Power connections

Important:

 The TTA-SIM is an electronic unit. Take the following 

precautions to avoid damage to electronic components:

•  Handle with care and avoid mechanical shock and impact

•  Keep dry

•  Avoid exposure to static electricity

•  Avoid contact with metal filings, grease, pipe dope and 

other contaminants

Space 

available for 

cable entries

Relay unit

Power

terminals

TTSIM-1A (or 

TTSIM-2) unit

Phase

Ground (earth)

Neutral

Installing the TTA-SIM

Отзывы: