Timer
schedule
Graphically programme the Timer in
1
hour time blocks.
You can set a block to OFF, Economy temp,
Maintain temp, or HEAT-UP*
OFF
MAINTAIN
HEAT-UP
ECONOMY
(*HEAT-UP=
100
% power, only when using the HWAT-R
cable. This is the legionella prevention mode and it is not
pre-programmed.
Activate this preferably during night
hours to avoid scalding.
Use the modes button to overwrite the timer schedule.
Select a temperature mode to assign to the time bock
of choice.
5. PARAMETER SETTINGS (DEFAULT)
Language
English
Country
Not pre-defined; to be selected
Date
01
/
01
/
2017
or last saved date
Time
00
:
00
; or last saved time
Building programme
Not pre-defined; to be selected
Heating cable type
Not pre-defined/ to be selected
Pipe diameter
DN
25
Insulation thickness
30
mm
Ambient temperature
20
°C
Maintain temperature
55
°C
Economy temperature
50
°C
Low temperature limit
40
°C
High temperature limit
65
°C
Low temperature alarm
OFF
High temperature alarm
ON
Alarm sound
ON
Key lock
OFF
6. TECHNICAL SPECIFICATIONS
6.1
Building programme schedule
Apartments
HEAT-UP
TIME IN HOUR
APARTMENT WEEKDAY
MON
09:31
00
01
02
03
04
21
22
23
12
13
14
15
16
18
19
05
07
09
11
20
17
06
08
10
16
|
Содержание nVent HWAT-ECO V5 (EU)
Страница 4: ...EN HWAT ECO V5 150 mm 1A 1B 5 2 3 2 INSTALLATION INSTRUCTIONS 4 nVent com RAYCHEM...
Страница 5: ...EN 1 2 A B C 4 5 6 nVent com RAYCHEM 5...
Страница 6: ...EN 7 8 9 6 nVent com RAYCHEM...
Страница 7: ...EN CLICK 10 11 12 nVent com RAYCHEM 7...
Страница 8: ...EN 30mA RCD C20A ON 15 HWAT E CO V5 13 14 8 nVent com RAYCHEM...