3.  INSTALLATION NOTES

The installation and, if necessary, the maintenance and the 

disassembling must be carried out by a qualified electrical installer. 

The installation must be compatible with local regulations. Check the 

maximum circuit length for your circuit breaker in the next table:

Maximum circuit length at 

230

 VAC and for 

20

°C start-up temperature 

C-characteristic circuit breaker

Multiple units on multiple power points can be used if longer heating 

cables are required. We recommend to use nVent RAYCHEM HWAT-SBS 

panels to operate 

3

6

9

 or 

12

 heating circuit

Fig. 

1

HWAT-L

HWAT-M

HWAT-R

Circuit breaker

(Yellow)

(Orange)

(Red)

10

 A

80

 m 

50

 m 

50

 m

13

 A

110

 m

65

 m

65

 m

16

 A

140

 m

80

 m

80

 m

20

 A

180

 m

100

 m

100

 m

The nVent RAYCHEM HWAT-ECO has a removable top lid. Both top and 

bottom of the box have electronic parts and are connected to each other 

by an Ethernet connector cable. The unit is delivered with top lid and 

back part dismantled.

Warning: 

For over voltage protection (e.g. in case of thunderstorm) we 

recommend the use of an external over voltage protection device.

Care and maintenance

Clean the HWAT-ECO with a soft damp cloth only, do not use any 

solvents. Do not pour water directly on the device. Do not use a water 

hose or a high pressure cleaner.

3.1 

Description

The HWAT-ECO control unit has been developed for operation with the 

self-regulating heating cables: nVent RAYCHEM HWAT-R, HWAT-M and 

HWAT-L. The hot water temperature maintenance system is a comfort 

system providing instant hot water at the tap. A self-regulatinga heating 

cable is positioned on the pipe and compensates for any temperature 

loss of the warm water. 
The HWAT-ECO control unit combines the following features:
•  The operating temperature of the heating cable can be limited to a 

desired temperature. Combined with the integrated “power off” timer 

function, this offers important energy savings.

•  Energy can be saved upon activation of the “trace boiler” function 

and installation of the boiler sensor. The maintain temperature of 

the heating cable will automatically be lowered in case the boiler 

temperature is reduced, preventing the heating cable from using too 

much energy for heating the water in the pipes.

•  On big warm water systems it is sufficient to programme one 

HWAT-ECO unit in a nVent RAYCHEM SBS panel to manage multiple 

heating circuits. The HWAT-ECO controller can be delivered in 

different prefabricated panels, depending on the quantity of heating 

circuits (

3

6

9

).

•  An alarm terminal makes remote reading of errors possible.
•  A pipe sensor (to be ordered separately) can be installed as reference 

point to track and monitor pipe temperature in a large hot water 

distribution network.

•  The unit can be pre-programmed in power-off mode by external 

power bank (to be ordered separately) connected via A-A-USB cable 

and USB connection.

nVent.com/RAYCHEM 

|

 9

Содержание nVent HWAT-ECO V5 (EU)

Страница 1: ...HWAT ECO V5 EU Firmware version 1 1 3 or higher Installation operation and maintenance manual HWAT ECO V5...

Страница 2: ...Product overview 3 2 Installation instructions 4 3 Installation notes 9 4 Operation 11 5 Parameter settings default 16 6 Technical specifications 16 Appendix 21 2 nVent com RAYCHEM Electrical schemes...

Страница 3: ...EN HWAT ECO V5 HWAT ECO V5 HWAT ECO V5 HWAT ECO V5 1x 1x 2x M25 2x M20 PCN 1244 020365 PCN 1244 015847 2x 2x 1x 1x 1x 1x 1x A B C 1 PRODUCT OVERVIEW nVent com RAYCHEM 3...

Страница 4: ...EN HWAT ECO V5 150 mm 1A 1B 5 2 3 2 INSTALLATION INSTRUCTIONS 4 nVent com RAYCHEM...

Страница 5: ...EN 1 2 A B C 4 5 6 nVent com RAYCHEM 5...

Страница 6: ...EN 7 8 9 6 nVent com RAYCHEM...

Страница 7: ...EN CLICK 10 11 12 nVent com RAYCHEM 7...

Страница 8: ...EN 30mA RCD C20A ON 15 HWAT E CO V5 13 14 8 nVent com RAYCHEM...

Страница 9: ...eveloped for operation with the self regulating heating cables nVent RAYCHEM HWAT R HWAT M and HWAT L The hot water temperature maintenance system is a comfort system providing instant hot water at th...

Страница 10: ...ckup 10 days Clock accuracy A variation of 10 minutes per year is possible Settings All settings are stored in non volatile memory Operating temperature 0 C to 40 C ambient Selectable temperature 37 C...

Страница 11: ...unit is automatically executing a connection check It will check the heating cable connection boiler sensor and pipe sensor connection A connection of the unit to an external relay needs to be confir...

Страница 12: ...ture is the selected maintain temperature Test programme start The test programme runs for 30 minutes during which all parameters will be ignored to check heating cable and connection on site You can...

Страница 13: ...ER SELECT PROGR PROGRAM TIM SELECT CABLE TYPE SELECT PIPE DIAMETER SELECT INSULATION THICKNESS SELECT AMBIENT TEMPERATURE SELECT BOILER SENSOR SELECT BOILER CUT OFF TEMPS HWAT M DN 25 40 MM 20 C ON 35...

Страница 14: ...mperature is too low the maximum temperature is lowered to the boiler temperature minus the trace temperature In this case the green trace boiler LED will be on Boiler low temperature limit You can de...

Страница 15: ...ER TEMP PROGRAMMING ER EMP 0 SELECT LANGUAGE SELECT COUNTRY SELECT DATE SELECT TIME SELECT ALARM GENERAL SETTING SELECT SAVING TIME ENGLISH GERMANY 01 10 2017 14 17 OFF ON 14 17 14 17 14 17 14 17 14 1...

Страница 16: ...Language English Country Not pre defined to be selected Date 01 01 2017 or last saved date Time 00 00 or last saved time Building programme Not pre defined to be selected Heating cable type Not pre d...

Страница 17: ...HOTEL WEEKDAY 10 29 00 01 02 03 04 21 22 23 12 13 14 15 16 18 19 05 07 09 11 20 17 06 08 10 Nursing home Weekday Weekend HEAT UP TIME IN HOUR HOSPITAL WEEKDAY 10 30 00 01 02 03 04 21 22 23 12 13 14 1...

Страница 18: ...0 30 00 01 02 03 04 21 22 23 12 13 14 15 18 19 05 07 09 11 20 17 06 08 10 16 Sport center Weekday Weekend HEAT UP TIME IN HOUR SPORT CENTER WEEKDAY 10 29 00 01 02 03 04 21 22 23 12 13 14 15 16 18 19 0...

Страница 19: ...sor failure Sensor has not been installed Sensor or sensor cable defect only when water heater sensor On is selected Check Sensor and Boiler temperature E 3 2 BOILER TEMP HIGH Water heater temperature...

Страница 20: ...error provide the exact error number cable type cable length and the setpoint temperature E 6 5 INTERNAL ERROR Internal error Disconnect HWAT ECO controller and replace unit When reporting this error...

Страница 21: ...er your 4 digit password If you forgot your password enter the backup password 3000 to unlock the controller See key lock Seeing 3 dots one by one on the screen Pushing the screen for 30 seconds cause...

Страница 22: ...AC 30 mA MAX C 20 A HWAT ECO S1 Pipe Sensor Rohrleitungsf hler R rsensor Potrubn idlo Sonde du tuyau Sensore tubazione Leidingsensor Czujnik temperatury rury S2 Boiler Sensor Boilerf hler Kedelsensor...

Страница 23: ...EN ELECTRICAL SCHEME K1 L3 N L1 L2 30 mA T L L N N PE PE COM NO NC S1 S1 GND S2 S2 GND Temperature sensors NTC Alarm 1 A 30 VDC 0 5 A 125 VAC HWAT HWAT L M R ECO MAX C 20 A nVent com RAYCHEM 23...

Страница 24: ...l 39 02 577 61 51 Fax 39 02 577 61 55 28 salesit nVent com Lietuva Latvija Eesti Tel 370 5 2136633 Fax 370 5 2330084 info baltic nVent com Magyarorsz g Tel 36 1 253 7617 Fax 36 1 253 7618 saleshu nVen...

Отзывы: