Supplied By www.heating spares.co Tel. 0161 620 6677
Once the process of commissioning the boiler is
complete, the commissioning engineer MUST complete
his section in the Benchmark log book.
29
6.13
CHECKING THE FLUE SYSTEM
6.13.1
The flue system should be visually checked for
soundness Check all connections and fixings
are secure and tight
6.14
CHECKING THE HEATING THERMOSTAT
6.14.1
Allow the system to warm up and then turn
the C.H thermostat to ensure the main burner
modulates from “high” to “low” and “low” to
“off” and vice versa (scale range
covers approx. 45° C - 85° C).
6.15 TESTING AND REGULATING THE
DOMESTIC HOT WATER SYSTEM FLOW
6.15.1
Put the appliance in operation with the
(summer/winter) switch in summer position
- Open a domestic hot water tap (preferably
the bath tap). Ensure cold water inlet
stopcock is open and the D.H.W. thermostat
16 is set at maximum.
- If the burner does not light check that the
water flow rate is above the min. required
to operate the differential pressure 2 8 Lts./
min. (0.61 gals/min).
- The temperature of the water will depend on
the rate at which it flows. If, due to high water
pressure, the flow rate is too high (and thus
the temperature too low for practical use)
the flow rate may be adjusted. It is better to
set for the lowest acceptable temperature,
preferably at the bath tap since the user
can gain higher temperatures at other
restricted flow taps (Table 1)
- To adjust the flow rate refer to (Fig 53)
side view and locate the adjustment screw
(Fig. 53). Turn the screw clockwise until the
required temperature is reached.
N.B.: If the cold supply is subject to large
fluctuations or is above the permitted max.
water pressure, a suitable pressure/flow
regulator should be fitted in the cold water
supply to the appliance.
- Turn the appliance mode selector switch
(Fig. 50) (1) to the summer position Slowly
close the draw off tap to reduce the flow
rate to above the min (approx. 2.8 litre/min
- 0 61 gals/min.). Rotate the D.H.W. control
thermostat to ensure it operates at its
various setting.
- Close the draw-off tap still further. The
burner should stop when the rate falls
below about 2.8 litres/min (0.61 gals/min ).
Содержание HE 85 A
Страница 1: ...Supplied By www heating spares co Tel 0161 620 6677 HE 85 A T...
Страница 16: ...Supplied By www heating spares co Tel 0161 620 6677 17...
Страница 42: ...Supplied By www heating spares co Tel 0161 620 6677 43...
Страница 43: ...Supplied By www heating spares co Tel 0161 620 6677 Is fan Running at Maximum speed 44...
Страница 44: ...Supplied By www heating spares co Tel 0161 620 6677 45...
Страница 45: ...Supplied By www heating spares co Tel 0161 620 6677 46...
Страница 49: ...Supplied By www heating spares co Tel 0161 620 6677 15 50...
Страница 52: ...Supplied By www heating spares co Tel 0161 620 6677 COD 0017LIB06007 1 10 2006...