               When starting, the fan will always start at the 

set-point  speed.

  

The boiler is fi tted with an anti-cycling device 
on the control board. This delays the boiler 
from re-fi ring within 10 minutes.

                If the heating temperature goes 20 °C below
                the set point, the burner restarts immediately. 
                The domestic hot water will always take 

priority and is unaff ected by the anti-cycling 
device.

2.6 

GENERAL FUNCTION

  

The instrument panel  permits regulation of the 
boiler to partial heating requirements, between 
maximum and minimum settings.

                 

Air and gas are drawn by the fan for 

                 combustion.

                 

The fan also forces exhaust gas through 

the fl ue to the outside, this creates a lesser 
pressure in the sealed combustion chamber, 
thus sucking in combustion air, through the 
inlet duct.

            

The boiler water temperature is automatically 

controlled by a built in thermostat.

                 

Interior space temperature is set by the room 

thermostat to be installed in the heating 
system. The boiler already carries connection 
terminals for this thermostat, as well as for 
a external timer if required.  The

external timer if required.  The burner 

continues to operate until it is stopped by the 
digital clock or one of the thermostats.

                 

When the internal CH temperature sensor 

                 or the room thermostat intervenes the  burner 

shuts down. The fan stops but the pump 
continues to operate for 3 minutes.

 

 

The boiler also incorporates an anti-block 
system which powers the pump every 24 
hours, allowing it to operate for 2 minutes if 
the boiler has not been in use. This operation 
may in some cases be heard for a short 
period when the pump has been activated.

                 The heat exchanger in the DHW circuit is 
                 a stainless steel plate heat exchanger water 

to water, and domestic water is heated by 
converting the water in the central heating 
circuit. The transfer of heat is very high 
because the two fl uids move in a counter 
direction.

                Select the winter position by summer/winter 

button (item 1 fi g. 1).

                When a hot water tap isturned on the 

When a hot water tap isturned on the 

                diverter valve motor  moves  to 

                diverter valve motor  moves  to 

exclude the central 

exclude the central 
heating  circuit,  the  boiler  automatically 

heating  circuit,  the  boiler  automatically 
modulates to maintain the domestic hot 

modulates to maintain the domestic hot 
water at a constant temperature. 

water at a constant temperature. 

 

The water temperature can be regulated by 

 

The water temperature can be regulated by 
the digital display.

the digital display.

2.2

               

INTRODUCTION

               

This boiler is designed for the production of 

                central heating and domestic hot water 
                combined in one unit.
 

It  is  fi tted  with  an  automatic  domestic  hot 
water priority valve.

 

It is possible to select either a summer or 

It is possible to select either a summer or 
winter function.

winter function.

                With the summer position only being for 

                With the summer position only being for 
                domestic hot water. 

                domestic hot water. 
 

The winter position being for central heating 

 

The winter position being for central heating 
with domestic hot water priority. 

with domestic hot water priority. 

2.3

2.3

  

DESCRIPTION OF CONTROL SYSTEM

DESCRIPTION OF CONTROL SYSTEM

 

AND SEQUENCE OF OPERATION

 

AND SEQUENCE OF OPERATION

2.4 

 Domestic hot water mode

2.4 

 Domestic hot water mode

  

When the appliance is in rest mode, select 
the summer position by pressing the ON/OFF 
button (item 1 fi g. 1) please ensure that the 
heating circuit is charged with water (above 1 
bar).

                If the domestic hot water tap is turned on, the 

boiler will function in the following sequence:

                 

The pump starts.

 

The fan starts and sends a 

                 signal back to the ignition board that the fan is 
                 running.

 
              

The spark ignition system is powered which in 

turn  commences  the  spark  igniter  to  operate 
and light the burner. 

 

At this point the ignition board opens the gas 
valve to light the burner.

  

When the electrode sensor senses the signal  
that the burner is alight, the spark igniter 
stops.

                

The fan speed settings on the boiler increases 

The fan speed settings on the boiler increases 

to  the  maximum  permissible  speed  over 

to  the  maximum  permissible  speed  over 
a  period  of  5  seconds  and  will  remain  at  its 

a  period  of  5  seconds  and  will  remain  at  its 
maximum  required  power  until  its  maximum 

maximum  required  power  until  its  maximum 
regulated  temperature  is  achieved  and  then 

regulated  temperature  is  achieved  and  then 
will modulate to maintain this.

will modulate to maintain this.

  

When the domestic hot water tap is closed the 

  

When the domestic hot water tap is closed the 
diverter  valve  goes  back  into  rest  mode,  the  

diverter  valve  goes  back  into  rest  mode,  the  
burner is shut down along with the fan which is 

burner is shut down along with the fan which is 
also switched off .

also switched off .

2.5 

Central heating mode

2.5 

Central heating mode

              

              

If the appliance is in winter mode with a 

If the appliance is in winter mode with a 

demand for heat to supply radiators, etc. , 

demand for heat to supply radiators, etc. , 
with  the heating circuit fully cha

with  the heating circuit fully charged  above 
1 bar, so as to operate the low water sensor 
device the boiler will start in the same way 
as domestic hot water mode. 

            
               As the heating sensor reaches temperature 

the fan speed modulates to maintain the 
temperature set  on the display panel.

    

  

12

Содержание HE 80 T

Страница 1: ...VENHEAT MANUFACTURING LTD CHARTISTS WAY MORLEY LEEDS U K LS27 9ET TEL 0113 252 7007 FAX 0113 238 0229 Website www ravenheat co uk E mail sales ravenheat co uk Instructions for Use Installation and Ser...

Страница 2: ...2...

Страница 3: ...ger for super high heat transfer to domestic hot water supply Stainless steel plate heat exchanger for super high heat transfer to domestic hot water supply Built in frost protection Built in frost pr...

Страница 4: ...SLQJ URRI VXFWLRQ 7HFKQLFDO GDWD 7 U3 1DW JDV IURP YHUWLFDO ZDOO 7HFKQLFDO GDWD 7 U3 3 KDXVW VXFWLRQ V VWHP ZLWK WZR 7HFKQLFDO GDWD 7 U3 1DW JDV VHSDUDWH SLSHV WKURXJK D VLQJOH 7HFKQLFDO GDWD 7 U3 3 Y...

Страница 5: ...H FKDQJHU 7R UHPRYH UHSODFH H SDQVLRQ YHVVHO 7R UHPRYH UHSODFH JDV YDOYH 7R UHPRYH UHSODFH SODWH KHDW H FKDQJHU 7R UHPRYH UHSODFH WKH ZDWHU SUHVVXUH WUDQVGXFHU 7R UHPRYH UHSODFH GLYHUWHU YDOYH PRWRU 7...

Страница 6: ...APPLIANCE CHECKING THE SYSTEM YOUR APPLIANCE CHECKING THE SYSTEM PRESSURE PRESSURE Before lighting the appliance check that the Central Before lighting the appliance check that the Central Heating sy...

Страница 7: ...domestic hot water temperature DHW 5 power of modulation 6 fan speed FAN the display show 2 digits e g 20 2000 rpm 7 external temperature if the external probe is present OTC 8 error history 9 error h...

Страница 8: ...g 1 to esc time function KEY 1 Day indicator time clock version only 1 Monday 1 Monday 2 Tuesday 2 Tuesday 3 Wednesday 3 Wednesday 4 Thursday 4 Thursday 5 Friday 5 Friday 6 Saturday 6 Saturday 7 Sunda...

Страница 9: ...these days but Sunday will remain the same as table one unless changed individually If you wish to override these times press the timer mode button to select MAN this puts the boiler in manual mode w...

Страница 10: ...sure relief valve 12 Water pressure transducer 13 CHreturn 14 Controlboard 15 Circulation pump 16 Automaticairvent 17 Condensatedrain 18 Expansionvessel 19 Mainheatexchanger 20 Sparkelectrode 21 Sensi...

Страница 11: ...ctrode 12 Sensor electrode 13 Fan 14 Flue temperature temperature sensor 15 Expansion vessel 16 Automatic air vent 17 Circulation pump 18 Water pressure transducer 19 Safetypressurereliefvalve 20 Dive...

Страница 12: ...f central heating and domestic hot water combined in one unit It is tted with an automatic domestic hot water priority valve It is possible to select either a summer or It is possible to select either...

Страница 13: ...r When DHW is no longer required the burner When DHW is no longer required the burner and pump and fan will immediately turn o and pump and fan will immediately turn o This also takes place when in wi...

Страница 14: ...1066 I h 20 C rise Minimum ow rate C H 350 l h D H W ow rate 30 C rise 11 9 l min D H W ow rate 35 C rise 10 2 l min D H W ow rate 40 C rise 8 9 l min 10 C Inlet temperature D H W temperature Max 60...

Страница 15: ...ing operating temperature Max 80 C min 35 C Design ow rate 1066 I h 20 C rise Minimum ow rate C H 350 l h D H W ow rate 30 C rise 11 9 l min D H W ow rate 35 C rise 10 2 l min D H W ow rate 40 C rise...

Страница 16: ...eating operating temperature Max 80 C min 35 C Design ow rate 1811 I h 20 C rise Minimum ow rate C H 350 l h D H W ow rate 30 C rise 14 0 l min D H W ow rate 35 C rise 12 0 l min D H W ow rate 40 C ri...

Страница 17: ...ing operating temperature Max 80 C min 35 C Design ow rate 1811 I h 20 C rise Minimum ow rate C H 350 l h D H W ow rate 30 C rise 14 0 l min D H W ow rate 35 C rise 12 0 l min D H W ow rate 40 C rise...

Страница 18: ...ler on the Gas Safe register www gassaferegister co uk Failure to install appliances correctly could lead to prosecution It is in your own interest and that of your safety to ensure the law is complie...

Страница 19: ...m containing a bath or shower any electrical switch or appliance control utilising mains electricity should be situated so that it cannot be touched by a person using a bath or shower A compartment wh...

Страница 20: ...s of BS 5440 Part 1 IMPORTANT NOTES For greater ue lengths see alternative ue instructions Flue must be positioned in a place not likely to cause a nuisance from pluming IMPORTANT NOTICE If the ue ter...

Страница 21: ...21 4 10 FLUE TERMINAL POSITION...

Страница 22: ...have a gradient to ensure air is carried naturally to air release to ensure air is carried naturally to air release points and water flows naturally to drain points and water flows naturally to drain...

Страница 23: ...sion see table 4 and add additional sealed expansion capacity as additional sealed expansion capacity as appropriate Fig 7 In general modern appropriate Fig 7 In general modern systems below 7 L shoul...

Страница 24: ...and invalidate the appliance guarantee and contravene the Building Regulations contravene the Building Regulations It is recommended that you fit a primary It is recommended that you fit a primary wat...

Страница 25: ...appliance except where the appliance is installed in a bathroom The current electrical IEE Wiring regulations must be followed in UK 5 INSTALLATION 5 1 WARNING It is MOST IMPORTANT that this appliance...

Страница 26: ...0 52 Self cutting joint securing 52 Self cutting joint securing screw screw 57 Elbow header 59 Rubber seal 60 56 Rubber seal 100 60 Fumes sample point 61 Flue exhaust duct 62 Air intake duct 69 Air sa...

Страница 27: ...ng Fig 12a FLUE EXHAUST DEFLECTION BEND Fig 12a Flue exhaust de ection bend are also available These come in both 45 and 90 degree versions These bends t directly onto the ue exhaust terminal to de ec...

Страница 28: ...en the a good seal is made with O rings Tighten the two screws on the flue flange to secure the two screws on the flue flange to secure the elbow header in place and fix securing screws elbow header i...

Страница 29: ...tion 5 5 Extensions must instructions in section 5 5 Extensions must be installed with the widened end of the air be installed with the widened end of the air intake pipe and the tapered end of the fl...

Страница 30: ...osite the extension s straight end NOTE A suitable support bracket flue bracket is available from Ravenheat and should be used to support the flue length at least every one metre preferably at each jo...

Страница 31: ...int 61 STD ue exhaust duct 62 Terminal 63 Flue extension 64 Flue exhaust duct extension 65 Flue manifold rubber seal 66 Securing screw 67 Flue temperature sensor 69 Air sample point 127 Terminal Rubbe...

Страница 32: ...re line is vertical and that the flue centre line is virtually below the point at which the flue will exit the roof Ensure that the maximum permissible flue permissible flue length is not exceeded fig...

Страница 33: ...om the outside Lift the boiler on the wall locating onto the top two fixing bolts Tighten the two bolts using a spanner to secure to the wall Measure the vertical distance between the top of the flue...

Страница 34: ...located into the ue manifold and lubricate the internal part of the seal before assembly the internal part of the seal before assembly Locate the header gasket on the twin ue Locate the header gasket...

Страница 35: ...Exhaust ue must slope 1 5 down towards the boiler 25 mm fall per metre Exhaust suction system with two separate pipes through a single vertical wall g 26 Maximum distance D L L1 37 metres Minimum dist...

Страница 36: ...fig 27 Part No Description PR5094110A Straight ue header sample point 60 100 PRO110300 Flue Extension 80 125 L1000 RID110050 125 80 to 100 60 Flue reducer CUR110250 45 ue bend 80 125 CUR110300 90 elb...

Страница 37: ...TING CONNECTION Fig 29 Before any central heating connections are made to the boiler all system valves should be opened and the system thoroughly flushed out with cold water Connect the central heatin...

Страница 38: ...if possible be discharged into the household internal drainage system If this is not practicable discharge can be allowed into the external household drains or a purpose designed soak away It is recom...

Страница 39: ...ock which is a 3 core cable which is a 3 core cable of 0 75 mm2 24x0 2 mm to BS 6500 Make sure all wires to the appliance are routed away from sharp edges and hot surfaces The cable must be fastened w...

Страница 40: ...hat they clock and thermostat make sure that they are calling for heat are calling for heat Select winter function the winter icon in Select winter function the winter icon in digital display will be...

Страница 41: ...with the valve inlet pressure test point fig 35 with the boiler operating at full rate boiler operating at full rate Check with the Local Gas supplier if the Check with the Local Gas supplier if the...

Страница 42: ...le pressure flow regulator should be fitted on the cold water supply to the appliance Slowly close the draw off tap to reduce the flow rate to the min approx 2 8 L min Select a different temperature f...

Страница 43: ...1 for 5 seconds to enter in item 6 and 4 fig 1 for 5 seconds to enter in USER PARAMETERS mode USER PARAMETERS mode Use arrow up and arrow down buttons Use arrow up and arrow down buttons item 3 and 4...

Страница 44: ...librated in accordance with the analyser manufacturers requirements Competence can be demonstrated by satisfactory completion of th satisfactory completion of the CPA1 ACS assessment which covers the...

Страница 45: ...ter at any remaining debris by spraying water at any remaining debris through the condensate trap through the condensate trap Ensure the water is kept away from Ensure the water is kept away from elec...

Страница 46: ...s must be carried out by a competent person Before replacing any parts the boiler should be isolated from the mains electric supply and the gas should be turned off at the service cock on the boiler A...

Страница 47: ...om the fan the fan U Unscrew the screws to the burner cover and remove the cover with the fan To remove the burner unscrew the screws in the lower cover side Replace in reverse order always fitting a...

Страница 48: ...ed check combustion CO2 and adjust if necessary see section 6 9 8 10 TO REMOVE REPLACE PLATE HEAT EXCHANGER Fig 44 Remove the front and bottom panels fig 39 40 Remove the panel control box sect 8 23 C...

Страница 49: ...rew the nut that fastens the pump to Unscrew the nut that fastens the pump to the CH pipe and remove the pump and the CH pipe and remove the pump and remove the securing clip at the pump remove the se...

Страница 50: ...connecting ensure the correct wires go to the relevant sensor the polarity on each one is unimportant 8 20 TO REMOVE REPLACE FLUE SENSOR Fig 3 item 22 Remove the f the front panel fig 39 Detach the wi...

Страница 51: ...ew the four screws and lift up Replace in reverse order Replace in reverse order 8 25 TO REMOVE REPLACE DIGITAL 8 25 TO REMOVE REPLACE DIGITAL DISPLAY BOARD DISPLAY BOARD Remove the front panel fig 39...

Страница 52: ...supply has been purged of air The heating system pressure is at least 1 bar min to 1 5 bar max select winter position on the digital display and set the central heating temperature to maximum sect 1 5...

Страница 53: ...osition on the digital display and setting see section 9 and after selecting the summer position on the digital display and setting the domestic hot water temperature to maximum the domestic hot water...

Страница 54: ...10 ELECTRICAL SYSTEM DIAGRAM 54 Fig 55...

Страница 55: ...55 11 SPARE PARTS Fig 56...

Страница 56: ...N150050 D H W sensor 20 OTT150050 Diverter valve by pass 21 FOR150150 Diverter valve motor clip 22 MOT150050 Diverter valve motor 23 5018030 3 4 gasket GUA010250 24 RAC150100 Gas valve inlet pipe 25 T...

Страница 57: ...r gasket 49 1 GUA150120 HE 80 T burner gasket 50 BRU150050 HE 80 T burner 50 1 BRU150100 HE 98 T burner 51 FLA110050 Flue ange FLA110052 52 GUA110350 Flue ange gasket 53 GUA110250 Flue manifold washer...

Страница 58: ...oncentric flue 80 125 see sect 5 18 Part No Description PR5094110A Straight ue header sample point 60 10 PRO110300 Flue Extension 80 125 L1000 RID110050 125 80 to 100 60 Flue reducer CUR110250 45 bend...

Страница 59: ...LS27 9ET Telephone 0113 252 7007 Fax 0113 238 0229 Website www ravenheat co uk E mail sales ravenheat co uk Ravenheat reserves the right to make changes and improvements in our products which may a ec...

Страница 60: ...l heating return temp measure and record Temperature control to heating 12 For combination boilers only Temperature control to hot water 12 Scale reducer 25 Heating zone valves n a Hot water mode Auto...

Страница 61: ...61...

Страница 62: ...62...

Страница 63: ...commissioning checNlist completed in full 7o instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation 7o maintain the boiler guarante...

Страница 64: ...64 FLOWCHART FOR CO LEVEL AND COMBUSTION RATIO CHECK ON COMMISSIONING A CONDENSING BOILER...

Страница 65: ...65 12 1 ANALYSER CHECK LIST...

Страница 66: ...iler interlocN 3roYided ALL SYSTEMS 7Ke s stem Kas Eeen usKed and cleaned in accordance ZitK 6 and Eoiler manuIacturer s instructions Yes Kat s stem cleaner Zas used Kat inKiEitor Zas used 4uantit lit...

Страница 67: ...SKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDWH 2 SSP AND 2 W PLQ UDWH KHUH 3RVVLEOH 2 SSP AND 2 RPPHQWV 6LJQDWXUH SERVICE 04 DWH QJLQHHU QDPH RPSDQ QDPH 7HOHSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDW...

Отзывы: