5.19
INSTALLATION INSTRUCTIONS FOR CONCENTRIC 80/125 FLUE SYSTEM
L + L = 23.5m Max
Straight Flue Straight Flue 90° Offset Flue 135° Offset Flue
L = 25 m Max L = 20 m Max L = 20 m Max L = 22.5m Max
plus Terminal plus Terminal plus Terminal plus Terminal
The vertical 80/125 flue kit is intended for use
where a horizontal 60/100 flue outlet is not
possible or desired.
The vertical flue can be installed on either a flat
installed on either a flat
roof or a pitched roof (maximum pitch 60°).
roof or a pitched roof (maximum pitch 60°).
Where a straight vertical flue is not possible or
Where a straight vertical flue is not possible or
desired, an offset vertical flue can be used in
desired, an offset vertical flue can be used in
conjunction with a side horizontal flue extension
conjunction with a side horizontal flue extension
piece and an inline 135°/90° flue bend (fig. 27).
piece and an inline 135°/90° flue bend (fig. 27).
Part No Description
COL160050 Straight fl ue header / sample point
60/100
PRO110300 Flue Extension 80/125 L1000
RID110050 125/80 to 100/60 Flue reducer
CUR110250 45° fl ue bend 80/125
CUR110300 90° elbow fl ue bend 80/125
TER010050 Horizontal Flue Terminal 80/125
TER110200 Vertical Flue Terminal 80/125
TEG060051 Flashing sleeve/slate
IMPORTANT:
- See fi g. 6 for terminal clearances.
See fi g. 6 for terminal clearances.
Fig. 27
IMPORTANT NOTICE:
When using our vertical fl ue kit the 125 mm x 100 reducer is supplied
complete with the vertical terminal simply remove this and fi x it into
the straight fl ue header (which must be fi tted) on the top of the boiler.
Fig
NOTE :
If using Flue arrangement in fi g. 27 then the 125x100 Flue reducer
must be purchased separately.
IMPORTANT: Please lubricate the
internal part of the seals before
fitting.
TABLE 8