Fig. 24
IMPORTANT: Please, lubricate the
internal part of the seals before
fitting.
37
52 - Self-cutting joint securing screw
IMPORTANT:
These instructions must be read in
conjunction with the main installation and
servicing instructions.
As with all fl ues the kits must be installed
taking due account of the current issue of BS
5440 parts 1 & 2 and timber frame housing
DM2 is referenced to the Institute of Gas
Engineers Document IGE/UP/7.
Also note that the requirements will vary
depending upon the kit being installed.
Guidance is provided but unless otherwise
stated, always comply with the
recommendations of the relevant codes of
practice.
5.14
INSTALLATION INSTRUCTIONS FOR TWIN FLUE PIPE (ECCENTRIC FLUE DUCT SYSTEM)
5.15
TWIN FLUE INSTRUCTIONS
This part of the installation manual covers the
installation and fi xing instructions of the twin
fl ue eccentric fl ue duct systems only.
When ordering twin fl ue it must be stated for
HE 25/30/35/40 C range.
Typical installation procedures are illustrated
by the drawing (fi g.24).
Remove the front panel of the case (sect.8.1).
Unscrew the screws on the fl ue adapter.
Make sure that the heat exchanger rubber
Make sure that the heat exchanger rubber
seal is located, and lubricate the internal part
seal is located, and lubricate the internal part
of the seal before assembly.
of the seal before assembly.
Locate the header gasket on the twin fl ue
Locate the header gasket on the twin fl ue
header and push into the fl ue adaptor making
header and push into the fl ue adaptor making
sure that the inner plastic exhaust
sure that the inner plastic exhaust locates fi r-
mly in the outlet spigot of the heat exchanger,
and screw the securing screws that secure
the twin fl ue header on to the boiler.
Locate the 2 x 80 mm O-rings in the twin
flue header and lubricate the internal part of
the seal before assembly to ensure an easy
snug fi t.
Measurements and bends must be calculated
correctly to ensure the maximum flue length
is not exceeded.
All located O-rings must be lubricated with a
silicone grease to ensure a snug fit.
NOTE: Exhaust flue must slope 1.5° down
towards the boiler 25 mm/m fall per metre of
flue length.
Spacing Clips
Spacing Clips are available on request should
they be required.
NOTE: for eccentric vertical flue a 125 mm
(5 in) diameter flashing plate will be required.
Part. No Description
SDO160050 Twin fl ue header F80/F80
PRO110200 Straight pipe L.1000 80
CUR110150 90° elbow bend 80
CUR110200 45° bend 80
GRI110050 Air inlet terminal 80
GRI110100 Exhaust terminal 80
TER060110 Vertical eccentric fl ue Terminal
/