Ravelli Circular 7 Скачать руководство пользователя страница 38

Use and maintenance manual Circular

Pag.38 

Rev.1  02/11/2021

EN

Chronothermostat

With the Chrono-thermostat function you can program the automatic switch ON/OFF of the stove for each day of the week for each 

day of the week in 4 independent time intervals (SET CHRONO 1-2-3-4). Below are given the steps for accessing the relative menu 

starting from “Home” mode.

            To exit the page and return to “Home” page, press the button repeatedly.

The exit key shows the CHRONO menu to set other variables related to the menu functions.

Set air - pellet 

The setting of the PELLET-FLOW mixture allows to adjust the combustion by varying the quantity of pellets loaded in the brazier 

and/or the quantity of air. In fact, by its nature, pellets vary in grain size and composition: even bags of pellets of the same brand 

can have different characteristics.

 

If combustion is not optimal, vary the flow parameter to adjust the combustion air. If air regulation alone is not sufficient, it may also 

be necessary to modify the pellet parameter.

 

Combustion regulation is an operation that requires a lot of experience. We recommend that you contact an Authorised 

Service Centre to calibrate the stove appropriately.

To exit the screen and return to the home screen, press the key repeatedly.

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.32 

Pag.33 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

VERSION FW.

Press the key

“confirm”

to access the function

To access the next setting, follow the steps given above or simply remove and replace the batteries.

The device resets and prompts you again to select the language you want to set.

Settings > Language

Settings > Adjust

Use the UP/DOWN keys to change the value read by the 

room temperature probe installed inside the handheld 

set, with respect to a reference value.

  The value can vary from -10°C to 10°C.

The standard value is 0°C.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu

The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and

the room temperature fan installed inside them.

Below are the messages shown on display when the stove is equipped with ventilation system.

            To exit the page and return to Stand-by page, press the button repeatedly.

VENTILATION menu (function only for models in which the same is specified in the dedicate user’s manual)

Control: v

entilation can be set from 0 to AUTO where 0 indicates that the same is disabled, setting from MIN to MAX enables selecting 

the heat distribution speed. If set to AUTO, the ventilation follows the power set on the stove.

Press the increase/decrease keys

“increase/decrease”

to change the ventilation.

            To exit the page and return to Stand-by page, press the button repeatedly.

The exit key shows the CHRONO menu to set other variables related to the menu functions.

Press the key

“enter” at the end of the

setting, from the following

CHRONO page

The temperature read by the handheld unit controls the modulation of the stove. If you want to adjust the ventilation by 

adjusting the stove, set the fan to A mode as shown in the relative chapter.

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“confirm”

to quickly switch to

VENTILATION.

Press the increase/decrease keys

“increase/decrease”

to change the ventilation.

Pages displayed upon the activation of advanced layouts

By activating a layout different from the standard (layout 0), even if maintaining the same functions of the menu, the “Stand-by” page will 

display all connected utilities such as the temperature of the boiler of the puffer.  

Below is shown the new display mode and the function of every icon for every layout, to change the various settings.

Layout 1 (DHW heating control)

The following layout can be used when you have a boiler that is not equipped with plate heat exchanger and you intend to buy a puffer

that should be connected to the circuit to produce hot domestic water.

In this type of circuit, room temperature is controlled however by the handheld unit which, being a radio device, acts as a remote

chronothermostat. The boiler is managed by the thermostove through a contact or immersion probe (not supplied) connected directly 

to the back of the stove. Below is shown the new “Stand-by” mode.

By setting the SUMMER function, the 3-way valve remains fixed in a single position, enabling the release of heat output 

by the stove exclusively inside the boiler. As soon as this condition is reached, the boiler switches to ECO STOP mode.

The operation is the same as for the basic layout except for the fact that in this layout, the boiler exchanges heat directly in the

boiler (priority); when the temperature set is reached, the 3-way valve changes its position and the boiler starts exchanging heat within

the heating circuit. From this moment, the stove is controlled by the radio handheld unit for contolling the room

temperature or via H2 setting (see the operation with layout 0 to find the data on modulation, eco stop etc.).

The 3-way valve is directed again into the boiler when:

- there is a request from the Boiler;

- there is a requested from the flow switch (optional, if connected).

The stove restarts from Eco-stop or Stand by mode according to heating requests or boiler requests.

T°C Boiler

From STAND BY mode, press

the ARROW key UP

to set the

room T°C

and DHW boiler T°C that you

desire.

Boiler water T°C

From STAND BY mode, press

the ARROW key DOWN

to set

the boiler water T°C

that you desire.

Press the key

“V” from STAND BY page

to display the actuale states and

the room temperature

Chrono function

By enabling the chrono function, it is possible to control the ventilation speed for each program as shown in the logic above.

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

CRONO-THERMOSTAT.

If the type of system designed requires controlling the 3-way valve (diagram 1 and 3), it is necessary to purchase the

optional kit from the retailer or the authorized Ravelli dealer.

DATE-TIME

DATE-TIME

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

CONTRAST

CONTRAST

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

MENU

USER

TECHNICIAN

VENTILATION POW.

USER

POWER SETTING

CHRONOTHERMOSTAT

SCREW LOADING

SET AIR-PELLET

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

POWER SETTING

SET AIR-PELLET

SET AIR-PELLET

CHRONOTHERMOSTAT

CHRONOTHERMOSTAT

SCREW LOADING

SCREW LOADING

CHRONO

CHRONO

ENABLE CHRONO

ENABLE CHRONO

ENABLE CHRONO

ENABLE CHRONO

VENTILATION POW.

SET CHRONO 1

SET CHRONO 1

SET CHRONO 2

SET CHRONO 2

SET CHRONO 3

SET CHRONO 3

SET CHRONO 4

SET CHRONO 4

POWER                    MOD

PUMP
3-WAY VALVE         HEAT
PRESSURE  1.1 BAR
HH T .     

21°C

MANUFACTURER’S

MANUFACTURER’S

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.32 

Pag.33 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

VERSION FW.

Press the key

“confirm”

to access the function

To access the next setting, follow the steps given above or simply remove and replace the batteries.

The device resets and prompts you again to select the language you want to set.

Settings > Language

Settings > Adjust

Use the UP/DOWN keys to change the value read by the 

room temperature probe installed inside the handheld 

set, with respect to a reference value.

  The value can vary from -10°C to 10°C.

The standard value is 0°C.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu

The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and

the room temperature fan installed inside them.

Below are the messages shown on display when the stove is equipped with ventilation system.

            To exit the page and return to Stand-by page, press the button repeatedly.

VENTILATION menu (function only for models in which the same is specified in the dedicate user’s manual)

Control: v

entilation can be set from 0 to AUTO where 0 indicates that the same is disabled, setting from MIN to MAX enables selecting 

the heat distribution speed. If set to AUTO, the ventilation follows the power set on the stove.

Press the increase/decrease keys

“increase/decrease”

to change the ventilation.

            To exit the page and return to Stand-by page, press the button repeatedly.

The exit key shows the CHRONO menu to set other variables related to the menu functions.

Press the key

“enter” at the end of the

setting, from the following

CHRONO page

The temperature read by the handheld unit controls the modulation of the stove. If you want to adjust the ventilation by 

adjusting the stove, set the fan to A mode as shown in the relative chapter.

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“confirm”

to quickly switch to

VENTILATION.

Press the increase/decrease keys

“increase/decrease”

to change the ventilation.

Pages displayed upon the activation of advanced layouts

By activating a layout different from the standard (layout 0), even if maintaining the same functions of the menu, the “Stand-by” page will 

display all connected utilities such as the temperature of the boiler of the puffer.  

Below is shown the new display mode and the function of every icon for every layout, to change the various settings.

Layout 1 (DHW heating control)

The following layout can be used when you have a boiler that is not equipped with plate heat exchanger and you intend to buy a puffer

that should be connected to the circuit to produce hot domestic water.

In this type of circuit, room temperature is controlled however by the handheld unit which, being a radio device, acts as a remote

chronothermostat. The boiler is managed by the thermostove through a contact or immersion probe (not supplied) connected directly 

to the back of the stove. Below is shown the new “Stand-by” mode.

By setting the SUMMER function, the 3-way valve remains fixed in a single position, enabling the release of heat output 

by the stove exclusively inside the boiler. As soon as this condition is reached, the boiler switches to ECO STOP mode.

The operation is the same as for the basic layout except for the fact that in this layout, the boiler exchanges heat directly in the

boiler (priority); when the temperature set is reached, the 3-way valve changes its position and the boiler starts exchanging heat within

the heating circuit. From this moment, the stove is controlled by the radio handheld unit for contolling the room

temperature or via H2 setting (see the operation with layout 0 to find the data on modulation, eco stop etc.).

The 3-way valve is directed again into the boiler when:

- there is a request from the Boiler;

- there is a requested from the flow switch (optional, if connected).

The stove restarts from Eco-stop or Stand by mode according to heating requests or boiler requests.

T°C Boiler

From STAND BY mode, press

the ARROW key UP

to set the

room T°C

and DHW boiler T°C that you

desire.

Boiler water T°C

From STAND BY mode, press

the ARROW key DOWN

to set

the boiler water T°C

that you desire.

Press the key

“V” from STAND BY page

to display the actuale states and

the room temperature

Chrono function

By enabling the chrono function, it is possible to control the ventilation speed for each program as shown in the logic above.

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

CRONO-THERMOSTAT.

If the type of system designed requires controlling the 3-way valve (diagram 1 and 3), it is necessary to purchase the

optional kit from the retailer or the authorized Ravelli dealer.

DATE-TIME

DATE-TIME

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

CONTRAST

CONTRAST

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

MENU

USER

TECHNICIAN

VENTILATION POW.

USER

POWER SETTING

CHRONOTHERMOSTAT

SCREW LOADING

SET AIR-PELLET

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

POWER SETTING

SET AIR-PELLET

SET AIR-PELLET

CHRONOTHERMOSTAT

CHRONOTHERMOSTAT

SCREW LOADING

SCREW LOADING

CHRONO

CHRONO

ENABLE CHRONO

ENABLE CHRONO

ENABLE CHRONO

ENABLE CHRONO

VENTILATION POW.

SET CHRONO 1

SET CHRONO 1

SET CHRONO 2

SET CHRONO 2

SET CHRONO 3

SET CHRONO 3

SET CHRONO 4

SET CHRONO 4

POWER                    MOD

PUMP
3-WAY VALVE         HEAT
PRESSURE  1.1 BAR
HH T .     

21°C

MANUFACTURER’S

MANUFACTURER’S

1

Ignition time

2

Shutdown time

3

Day of the week when the 

program is active

4

Program number “chrono” 

5

Power setting

6

Setting the room temperatures

1

2

3

4

5

6

Select SET AIR-PELLET 

and press the CONFIRM 

button.

Use the UP and DOWN 

keys to change the % pellet 

value.

Press the CONFIRM button 

to confirm the value and

go to the item % change 

flow.

Use the UP and DOWN buttons to change the 

pellet % value. Press the CONFIRM button to 

confirm the value and

change to the item % flow.

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.30 

Pag.31 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Stove State

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

Stove STATUS.

            To exit the STOVE STATE page and return to Stand-by page, press the button repeatedly.

In this mode you can check the proper operation of the most important parameters of the appliance. Here is a list of real data of the 

stove useful for service during inspection.

- Circulator state (ON running)

- Position of 3-way valve DHW (domestic hot water) or HEAT (heating);

- System pressure;

- Stove state;

- Current boiler power;

- Flow read by the flow meter;

- Fume extractor speed;

- Actual flow set;

Settings > Enable thermostat

Press the “enter” key

to access the

SETTINGS

Press the key

“selection” to switch to

ENABLE THERMOSTAT.

Press the key

“confirm”

to access the function

Press the key

“confirm”

to enable the function.

In Stand-By mode, instead of room temperature measured

and settable, appears the line T ON if the room in which 

the thermostat is installed has not reached the temperature 

requested  or  the  writing  T  OFF  if  the  temperature  in  the 

room is reached.

Press the key for several 

times

to return to 

“STAND BY” page

- Temperature read by the handheld unit;

- External thermostat (request ON);

- Flame temperature (combustion chamber);

- Combustion fume exhaust temperature;

- Inlet flow meter temperature;

- Heated flow meter temp.;

- Electronic board temperature;

- Boiler water temperature (SUPPLY);

- Boiler water temperature (optional) - RETURN from the system;

- Boiler DHW temperature;

- Puffer  temperature - average warm point;

- Puffer  temperature second reading (low temp.).

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Settings

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“selection” to switch to

second menu page

to the function

SETTINGS.

After following the procedure above step by step, you can set the following functions:

Settings > Contrast

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use the UP/DOWN keys to change contrast setting and obtain 

a better visualisation of the information shown on the handheld 

set.

The  value  can  vary  from  0  to  100.  50  with  respect  to  the 

standard value.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Settings > Season

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use  the  UP/DOWN  keys  to  change  the  WINTER/

SUMMER season. Function that can be set when 

working with DHW puffer (Boiler).

See chap. Evolved hydraulic diagrams

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Press the “enter” key to

access the

SETTINGS

Press the key

“selection” to switch to

CONTRAST.

Press the key

“confirm”

to access the function

Settings > Firmware version

By pressing the button you will confirm the data and switch to the page within the SETTINGS menu.

MENU

STOVE STATE

STOVE STATE

STOVE STATE

STOVE STATE

USER

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTUAL STATES

PUMP

PRESSURE   1.1 BAR

SHUTDOWN

POWER MOD

HH T …

EXT.T …

FLAME T 340°C

FUME T   120°C

F. EX. T   30°C

C. EX. T    55°C

EL B. T---25°C

T. CALDERA
T.PUFFER H
T.PUFFER L

3-WAY VALVE   HEAT

ACTUAL STATES

ACTUAL STATES

ACTUAL STATES

H20 TEMPERATURE

H20 TEMPERATURE

v

H20 TEMPERATURE

TECHNICIAN

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

WINTER

CONTRAST

FIRMWARE

SUMMER

DATE-TIME

ENABLE THERMOSTAT

ENABLE THERMOSTAT

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

SEASON

SEASON

SEASON

SEASON

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

MANUFACTURER’S

MANUFACTURER’S

Press the selection 

keys to navigate the 

menu screens.

USER.

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.30 

Pag.31 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Stove State

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

Stove STATUS.

            To exit the STOVE STATE page and return to Stand-by page, press the button repeatedly.

In this mode you can check the proper operation of the most important parameters of the appliance. Here is a list of real data of the 

stove useful for service during inspection.

- Circulator state (ON running)

- Position of 3-way valve DHW (domestic hot water) or HEAT (heating);

- System pressure;

- Stove state;

- Current boiler power;

- Flow read by the flow meter;

- Fume extractor speed;

- Actual flow set;

Settings > Enable thermostat

Press the “enter” key

to access the

SETTINGS

Press the key

“selection” to switch to

ENABLE THERMOSTAT.

Press the key

“confirm”

to access the function

Press the key

“confirm”

to enable the function.

In Stand-By mode, instead of room temperature measured

and settable, appears the line T ON if the room in which 

the thermostat is installed has not reached the temperature 

requested  or  the  writing  T  OFF  if  the  temperature  in  the 

room is reached.

Press the key for several 

times

to return to 

“STAND BY” page

- Temperature read by the handheld unit;

- External thermostat (request ON);

- Flame temperature (combustion chamber);

- Combustion fume exhaust temperature;

- Inlet flow meter temperature;

- Heated flow meter temp.;

- Electronic board temperature;

- Boiler water temperature (SUPPLY);

- Boiler water temperature (optional) - RETURN from the system;

- Boiler DHW temperature;

- Puffer  temperature - average warm point;

- Puffer  temperature second reading (low temp.).

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Settings

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“selection” to switch to

second menu page

to the function

SETTINGS.

After following the procedure above step by step, you can set the following functions:

Settings > Contrast

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use the UP/DOWN keys to change contrast setting and obtain 

a better visualisation of the information shown on the handheld 

set.

The  value  can  vary  from  0  to  100.  50  with  respect  to  the 

standard value.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Settings > Season

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use  the  UP/DOWN  keys  to  change  the  WINTER/

SUMMER season. Function that can be set when 

working with DHW puffer (Boiler).

See chap. Evolved hydraulic diagrams

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Press the “enter” key to

access the

SETTINGS

Press the key

“selection” to switch to

CONTRAST.

Press the key

“confirm”

to access the function

Settings > Firmware version

By pressing the button you will confirm the data and switch to the page within the SETTINGS menu.

MENU

STOVE STATE

STOVE STATE

STOVE STATE

STOVE STATE

USER

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTUAL STATES

PUMP

PRESSURE   1.1 BAR

SHUTDOWN

POWER MOD

HH T …

EXT.T …

FLAME T 340°C

FUME T   120°C

F. EX. T   30°C

C. EX. T    55°C

EL B. T---25°C

T. CALDERA
T.PUFFER H
T.PUFFER L

3-WAY VALVE   HEAT

ACTUAL STATES

ACTUAL STATES

ACTUAL STATES

H20 TEMPERATURE

H20 TEMPERATURE

v

H20 TEMPERATURE

TECHNICIAN

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

WINTER

CONTRAST

FIRMWARE

SUMMER

DATE-TIME

ENABLE THERMOSTAT

ENABLE THERMOSTAT

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

SEASON

SEASON

SEASON

SEASON

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

MANUFACTURER’S

MANUFACTURER’S

% Flow

% Flow

MENU

USER

TECHNICIAN

PRODUCER

USER

LOADING AUGER

CHRONOTHERMOSTAT

SET AIR-PELLET

STOVE STATUS

USER

LOADING AUGER

CHRONOTHERMOSTAT

SET AIR-PELLET

STOVE STATUS

CHRONOTHERMOSTAT

ENABLE CHRONO

SET CHRONO 1

SET CHRONO 2

SET CHRONO 3

SET CHRONO 4

CHRONOTHERMOSTAT

ENABLE CHRONO

SET CHRONO 1
SET CHRONO 2

SET CHRONO 3

SET CHRONO 4

MENU

USER

TECHNICIAN

PRODUCER

USER

LOADING AUGER

CHRONOTHERMOSTAT

SET AIR-PELLET

STOVE STATUS

USER

LOADING AUGER

CHRONOTHERMOSTAT

SET AIR-PELLET

STOVE STATUS

Содержание Circular 7

Страница 1: ...USE AND MAINTENANCE MANUAL Circular 7 Circular 9...

Страница 2: ......

Страница 3: ...que Ravelli Modello Model Mod le Circular 7 L oggetto della dichiarazione di cui sopra conforme alla pertinente normativa di armonizzazione dell Unione The object of the declaration described above is...

Страница 4: ...nwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y mantenimient...

Страница 5: ...nwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y mantenimient...

Страница 6: ......

Страница 7: ...n do not discard it without reading it Incorrect installation maintenance and improper use of the product relieve the Manufacturer of all liability deriving from use of the stove For further informati...

Страница 8: ...ircular 9 19 Main parts 20 Description of operation 20 Automatic cleaning system 21 Recharge the fuel 21 Doors opening 21 User training 21 Safety devices 22 SHIPPING AND INSTALLATION 23 Safety warning...

Страница 9: ...3 Warning Pop Up 44 Alarms table with reference codes 44 INSTALLATION QUICK GUIDE RAVELLI SMART WI FI 47 Connect the WiFi module cable 47 App 47 Connection to the WiFi module 47 Account registration 4...

Страница 10: ...nised standards and or technical specifications have been applied EN 14785 EN 55014 1 EN 55014 2 EN 61000 3 2 EN 61000 3 3 EN 60335 1 EN 60335 2 102 EN 62233 EN 50581 ETSI EN 300220 1 All local regula...

Страница 11: ...e die Montage und Nutzungsanweisungen Distanza minima da materiali infiammabili Minimum distance from flammable materials Distance moindre de mat riels inflammables Distancia minima de materiales infl...

Страница 12: ...s the gaskets the paint job the stainless steel or cast iron combustion grille the resistance the Majolica cladding the aesthetic parts any damages caused by unsuitable installation and or use of the...

Страница 13: ...if any inconsistency arises it will be necessary to follow the text in the original language or contact our Technical Documentation Office Symbols used in the manual symbol definition This symbol is u...

Страница 14: ...nly use original spare parts Any tampering and or replacements that have not been authorised by Ravelli can pose a danger to the user s safety In the event of particularly adverse weather conditions t...

Страница 15: ...e contract and herein the operating manual procedures are followed routine maintenance is carried out according to the times and methods set forth extraordinary maintenance is promptly carried out whe...

Страница 16: ...regulation chimney provide a suitable system for the supply of combustion air air intake or intake duct for watertight appliances always perform maintenance with the appliance off and cold perform cle...

Страница 17: ...e Ravelli recommends using wood pellet classified A1 and A2 according to the EN ISO 17225 2 2014 standard or certified DIN PLUS more restrictive than the A1 class or ONORM M 7135 Pellet may be light o...

Страница 18: ...0 0 1 10 0 1 Electrical connection Hz V 50 230 50 230 Electrical power consumption max W 245 245 Electrical power consumption reduced nominal W 10 11 10 13 Stand by electrical consumption W 2 5 2 5 sm...

Страница 19: ...Pag 19 Rev 1 02 11 2021 EN Measurements Unit of measurement Circular 7 Circular 9 Height mm 1208 Width mm 520 Depth mm 540 Weight kg 150 Technical diagram Circular 7 Circular 9 80 upper smoke outlet 5...

Страница 20: ...ng and safety The user can choose the operating power from 5 levels or set the temperature to be maintained in the room In this case the stove will manage the power to ensure maximum comfort Among the...

Страница 21: ...amber door the pellet hopper lid and the ash drawer can only be opened when the stove is in the OFF state If one of them is not closed the pellet supply is interrupted the control unit emits an acoust...

Страница 22: ...o standard equipped with a grounding circuit and all the safety systems required by the standards It should be noted that the stove s operating program has been designed to stop stove operation in the...

Страница 23: ...led that the safety distances from flammable materials are observed Verification of system compatibility has a priority over any other assembly or installation operation Local administrative regulatio...

Страница 24: ...Manufacturer Do not connect the appliance to a collective chimney The chimney must be built applying the following regulations it must observe product standard EN 1856 1 it must be made of materials...

Страница 25: ...in the presence of other combustion appliances or VMC system it is necessary to check the appliance for correct operation The appliance must be placed inside living quarters It must never be installed...

Страница 26: ...s another one installed so that the outside section can be inspected It is prohibited to install two 90 bend since the ashes would quickly obstruct smoke passage causing draught problems in the applia...

Страница 27: ...quickly obstruct smoke passage causing draught problems in the appliance See Fig 2 INTERNAL CHIMNEY Fig 5 Protection from rain Covering sheet Air tight steel sheet metal T fitting with collection cham...

Страница 28: ...r intake proceed as follows step action 1 Connect a 50 mm diameter pipe to the combustion air inlet pipe at the back of the stove Note the pipe must be no more than 2 m in length The air vent must be...

Страница 29: ...nance manual Circular Pag 29 Rev 1 02 11 2021 EN Concentric installation Follow the regulations in force in your region for installation Not provided 1 2 3 4 5 6 7 8 9 x2 x3 x4 x6 x4 x2 Not provided 6...

Страница 30: ...Use and maintenance manual Circular Pag 30 Rev 1 02 11 2021 EN Rear smoke outlet x6 x7 10 11 12 1 2 3 4 6 x2 x2 x2 5 x2 Break the pre cut Optional kit x2 Optional...

Страница 31: ...power cord and any other cables outside the equipment do not come into contact with hot surfaces Ensure that the electrical system is grounded For direct connection to the mains it is necessary to pro...

Страница 32: ...Touch LEGEND Safety devices T1 Pressure switch T2 Resettable thermal breaker T3 Pellet tank contact Motors M1 Infeed screw gear motor M2 Automatic cleaning system M3 Fume exhaust system M4 Room fan R...

Страница 33: ...reason on display appears the following message If the handheld set is used for the first time select YES using the selection keys and confirm with the dedicated key On the display of the handheld se...

Страница 34: ...er of the battery on the back of the remote control as shown in Figure A and insert the 3 batteries mini pen style battery AAA 1 5V in the housing of the remote control and observe the poles Install t...

Страница 35: ...ION ADJUST LANGUAGE SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE The display is subdivided into three parts 1 It shows the current room temperature measured by the handheld set Moreover i...

Страница 36: ...TA COMFORT CLIMA DELTA RESTART DELTA SHUTDOWN DELAY SETTINGS SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CONTACT THEREFORE NOT POWERED MO...

Страница 37: ...tact therefore not powered moreover we recommend you use a thermostat with a minimum offset of 3 C if you ntend to use the comfort clima function Description of menu functions Press the key to access...

Страница 38: ...ature If the type of system designed requires controlling the 3 way valve diagram 1 and 3 it is necessary to purchase the optional kit from the retailer or the authorized Ravelli dealer CHRONO CHRONO...

Страница 39: ...WE RECOMMEND YOU USE A THERMOSTAT WITH A MINIMUM OFFSET OF 3 C IF YOU INTEND TO USE THE COMFORT CLIMA FUNCTION Operating phases of the appliance Modulation During the work phase the appliance should r...

Страница 40: ...N FW VERSION LANGUAGE LANGUAGE LANGUAGE LANGUAGE ADJUST ADJUST ADJUST ADJUST In Home mode instead of room temperature measured and settable appears the line T ON if the room in which the thermostat is...

Страница 41: ...ill confirm of data and switch to the page within SETTINGS menu The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and the ro...

Страница 42: ...to MAX enables selecting the heat distribution speed If set to AUTO the ventilation follows the power set on the stove The temperature read by the handheld unit controls the modulation of the stove If...

Страница 43: ...e set is reached see the dedicated section WAITING START RESTART Switch on is requested but with the stove in cooling phase once this condition is met it restarts automatically IGNITION RESTART The HO...

Страница 44: ...e Support Service If the problem persists contact the Support Service AL 04 FAN BROKEN Fume exhaust encoder is not working or is connected incorrectly Contact the Support Service No power to fume extr...

Страница 45: ...e AL 15 AUGER TRIAC An internal part of the electronic board that controls the pellet auger is faulty Check the flue is free and clean Possible voltage drops or incorrect input voltage Check the mains...

Страница 46: ...6 Rev 1 02 11 2021 EN EXTERNAL POWER SUPPLY WITH MICRO USB CONNECTOR WIFI MODULE BOARD WITH CONNECTORS FOR EXTERNAL POWER SUPPLY CONNECTION Wifi kit Wifi external power supply kit if applicable MOTHER...

Страница 47: ...tphone tablet entrare nel menu Android Impostazioni Connessioni Wi Fi iOS Impostazioni Wi Fi Selezionare la rete WINET XXXXXXXX ed inserire la chiave WPA indicata nell etichetta del dispositivo wi fi...

Страница 48: ...l name e g KTR AIR and then click Yes The screen offers a list of firmware once you have identified your model click on Select Yes Close the App and go to step 6 to register the account 4 CONNECTION T...

Страница 49: ...n where you can register the WiFi device WiFi device registration When you click the link in the confirmation E mail the window to register the new device will open click Register your wifi device now...

Страница 50: ...umber and give the module a name e g living room stove STEP 3 complete with your information click Next and then Complete registration STEP 2 enter the product serial number and give the module a name...

Страница 51: ...ke sure that the ashes are completely cold Always operate with equipment that is appropriate for maintenance When maintenance is finished re install all of the dis assembled parts before restarting op...

Страница 52: ...Extraction duct cleaning Periodically check that the extraction duct is free from obstructions dust animal hair and remove them if necessary Extraordinary maintenance Maintenance operations must be c...

Страница 53: ...y a Ravelli Assistance Centre Schedule this type of cleaning with the Ravelli Assistance Centre To clean the combustion chamber proceed as described below After cleaning the combustion chamber it is a...

Страница 54: ...pe of cleaning with the Ravelli Assistance Centre The stove is equipped with some hatches for cleaning the internal smoke ducts To clean the smoke ducts proceed as described below step action 1 Remove...

Страница 55: ...Replace the electronic board contact the Technical Assistance Service AL 15 The flame does not ignite Check that the igniter warms up Check and if necessary replace the igniter AL 05 Air inlet duct b...

Страница 56: ...moke duct AL 08 The door is not closed perfectly or the gasket are worn Close the door and have the gaskets replaced with original ones AL 05 AL 06 The stove stops automatically Alarm presence Check t...

Страница 57: ...not work Remote control battery low Replace battery or connection to the stove via cable Faulty remote control Replace remote control The stove always works at maximum power Temperature not set corre...

Страница 58: ...e room is clear of any obstructions and that there are no other combustion appliances or extraction hoods that create a vacuum in the room Difficult lighting Closely follow the directions in the dedic...

Страница 59: ...r s parer cet appareil et ou les piles ou les accumulateurs des autres types de d chets et de le confier au service municipal de collecte On peut demander au distributeur de pr lever le d chet d appar...

Страница 60: ...r at forebygge ventuelle skader for milj et eller sundheden bedes brugeren om at behandle dette udstyr og eller de medf lgende batterier eller akkumulatorerne separat fra andre affaldstyper og at leve...

Страница 61: ......

Страница 62: ......

Страница 63: ......

Страница 64: ...f free to make any variations to the features of its products without notice Aico S p A Headquarter Via Consorzio Agrario 3 25032 Chiari BS Italy Research and Development Centre Viale del commercio 12...

Отзывы: