Chapter 7: Trouble Shooting
Indication
Root Cause
Remedy
There is no
indication on
the panel
No power to the
Panel
Check AC power and
Standby power.
If there is any
false alarm
from the
detector
May be the
detector is faulty
or check EOL
resistor
Ensure the AC supply
within range 185 -
245v (or) Change the
faulty detector
Detector OPEN
is not detected
by the panel
Total zone loop
current exceed
the rated value
Check number of
detectors connected
in the loop. Total
detectors current
should not go above
3mA
Hooter fault
indication
There is no proper
connection in the
hooter
Or loop Fault.
Connection Details for Non
Polarized Hooter
Diode
IN4007
+ +
- -
If there is no hooter
connected to the
output, check if EOL
resistor connected
there or not.
Check loop wiring for
short / open using a
meter.
If hooter is non-
polarized, then ensure
each hooter’s +ve
loop is connected to
1N 4007 diode’s
cathode and the
hooter –ve loop
connected to the
anode of 1N 4007.
Hooter
(NAC)