P/N RE - 102 / 104 Rev. No. 0
20
2.
By silencing, sounders are switched off and Fire relay
output for actuators will remains in ON Condition until
reset.
4.3.5
Programming Menu Flow Chart:
MENU KEY - FLOW DIAGRAM
Menu
Key
5. Auto KeyLo ck
6. KeyLock
Time
7.
Auto Silence
8. Sile nce Time
9.
Chg e Passw o rd
6. KeyL ock Time
060 (secs)
Use Cursor Key to
Increa se / D ecrea se
the ti me del a y
8. S ilence Tim e
060 (secs
)
Use Cursor Key to
Incr ea se / Decre a se
the t i me del a y
1. Zone 1
1. Zone 1
Enabled
1. Zone 1
Disabled
1. Zone 1
Zo ne Test
1. Zone 1
W alk Test
De fa ul t
2. Zone 2
3. Zone 3
4. Zone 4
5. Auto KeyLock
Ena bled
5. Auto Ke yLock
Disabled
7.
Auto Silence
Enabl ed
7.
Auto Silence
Disabled
Enter Old
P assw ord?X XX
Ente r New
Pa ssw ord?X XX
Passw ord
Changed
Note:
1. Use Cursor key ( ) to move the menu list previous or next
and to interchange the status of the menu.
2. Use Enter Key ( ) to select the menu list and conform the change of the status.
3. Menu 2,3,4 are same as 1.
4. default Password is '123'.
10. Net Address
10. Net Address
<01>
Use Cursor Key to
Increa se / D ecrea se
the Network Address