1.5 Routine Testing

 

In order to ensure that the system is fully operational, and to comply 
with the requirements of IS 2189: 1999, the following routine attention is 
recommended: 
 
Daily - Check the panel to ascertain that it indicates normal 
operation. If any fault is indicated check that it has been recorded 
and that the appropriate actions have been taken, e.g. informing the 
maintaining company. 
Weekly - Test at least one detector or call point to confirm the 
operation of the panel and the audible alarms. Test a different zone 
each week and, if possible, a different device. Keep a record of the 
device and zone tested each week. Record and report any 
malfunction. 
Quarterly - The responsible person should ensure that every three 
months the system is checked by a competent person.  Check the 
standby batteries and the charger voltage Test at least one device in 
each zone to check the panel functions. Check the operation of the 
audible alarms and any link to a remote manned centre, Central 
Station, etc. Carry out a visual inspection of the installation to check 
for alterations or obstructions and issue a certificate of testing. 
Annually - The responsible person should ensure that, in addition to 
the quarterly checks, each device on the system is tested and that a 
visual inspection is made of the cable fittings and equipment. 
Note:  The control panel case should be cleaned periodically by 
wiping with a soft, damp cloth. Do not use any solvents. 

 
 

 
 
 
 
 
 
 
 
 
 

Содержание RE -102

Страница 1: ...RE 102 RE 104 Fire Alarm Control Panel Installation Commissioning Operating Manual...

Страница 2: ...P N RE 102 104 Rev No 0 1...

Страница 3: ...P N RE 102 104 Rev No 0 2...

Страница 4: ...P N RE 102 104 Rev No 0 3 NOTES...

Страница 5: ...R 3 Installation 11 3 1 Installation Precaution 11 3 2 Mounting Details 13 3 3 Input Circuits 14 3 4 Output Circuits 15 CHAPTER 4 Operating Instructions 16 4 1 Switch Functions 16 4 2 Status LED 17 4...

Страница 6: ...itions of the field devices and the control equipment 1 2 General The panel is self contained with integral power supply and space provision for two sealed lead acid standby batteries and comply with...

Страница 7: ...the audible alarms and resetting the system as described later Fault Indication If the control panel indicates a Fault condition make a note of all illuminated indicators refer to the chart on Page 23...

Страница 8: ...ne tested each week Record and report any malfunction Quarterly The responsible person should ensure that every three months the system is checked by a competent person Check the standby batteries and...

Страница 9: ...voltage and Battery level 2 1 Product Features Rugged CRCA sheet with powder coated finish Operates on 220v 50Hz AC supply Standby battery back up with built in charging Error free Fire Fault status...

Страница 10: ...s B wiring Normal Operating Voltage Nominal 24 VDC Alarm Current 15 35mA threshold Short Circuit Current 42mA Maximum Loop resistance 50 ohms Maximum End Of Line Resistor 4 7K 1 4watt Standby Current...

Страница 11: ...Yellow Zone Fire Red Zone Fault Yellow Zone Isolate Walktest Yellow Local Buzzer A piezo buzzer provides separate and distinct sounds for alarm and trouble conditions Alarm steady Fault pulse 0 5sec O...

Страница 12: ...cept the changes of edited menu This key also used for lamp test in system normal condition MENU Key This key is used to enter into the Main menu in the LCD 2 4 Mechanical Construction The enclosure o...

Страница 13: ...any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits system operations or software functions known...

Страница 14: ...age circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications...

Страница 15: ...the inner parts of the panel are given sufficient protection during installation All external cables are to be entered via the 19mm preformed knockouts located at the top of the panel When the instal...

Страница 16: ...zone is supervised for opens and ground faults Both conditions are visually and audibly toggle tone annunciated Each zone is a Class B Initiating Device Circuit IDC Zones designed to accept any normal...

Страница 17: ...otal load capacity of this circuit is capacity of this O P is 1Amps Sounder Circuit Class B Note If the non polarized devices are used connect the device as mentioned in page 23 Standard Relay The con...

Страница 18: ...Fire Condition The panel is reset by pressing this key followed by password if enabled During reset condition all the detector input voltages are cut off up to 3 seconds for Detectors and MCP s Then...

Страница 19: ...blown the AC Power on LED will OFF and it also indicated by fault Buzzer tone BATTERY ON This LED indicates the presence of standby power supply Whenever the Main Supply 220v A C fails the panel supp...

Страница 20: ...corresponding ZONE FIRE red LED will be illuminated At the same time hooter potential free contact Fire Relay and local buzzer continuous tone will be activated The External hooter NAC Sounder and buz...

Страница 21: ...ease the time delay 1 Zone 1 1 Zone 1 Enabled 1 Zone 1 Disabled 1 Zone 1 Zone Test 1 Zone 1 Walk Test Default 2 Zone 2 3 Zone 3 4 Zone 4 5 Auto KeyLock Ena bled 5 Auto KeyLock Disabled 7 Auto Silence...

Страница 22: ...one is Tested for Fire Open Short and Isolate automatically without disturbing the normal operations Walk test Mode In this mode the selected zone is used to check all the loop devices manually one by...

Страница 23: ...t the panel comes out of the walk test mode automatically d During test condition that the other zones that are not in test mode fire will consider as actual fire 4 3 5 2 Zone 2 From this menu the zon...

Страница 24: ...atically and after the set time delay key pad will be locked 4 3 5 6 Auto Lock Time The Auto key lock time will be enabled only when the Auto Key lock is Enabled If the Auto Key Lock is in Enabled con...

Страница 25: ...ime is 60 Seconds 4 3 5 9 Change Password From this menu the password used for key panel enable can be changed The default factory setting password is 123 The password should be three digits 4 3 5 10...

Страница 26: ...esting of devices by a single person In this mode if the panel detects any fire then after 3 seconds the panel will get automatically silenced After 6 seconds of silence the panel will go to reset Thi...

Страница 27: ...the menu key zone1 selects first 2 Press cursor key consequently until select the zone which is to be test 3 After selecting the zone press the ENTER KEY 4 After the ENTER KEY is pressed Select the Z...

Страница 28: ...fer specification Page 10 for Quiescent standby alarm currents System current S Quiescent Current Standby current X No of zone Fire current F Alarm Current x no of zones Hooter Current x No of Hooter...

Страница 29: ...Total zone loop current exceed the rated value Check number of detectors connected in the loop Total detectors current should not go above 3mA Hooter fault indication There is no proper connection in...

Страница 30: ...P N RE 102 104 Rev No 0 29 Chapter 8 Terminal Details...

Страница 31: ...044 4204 9599 Email marketing ravelfirepanels com Web www ravelfirepanels com DATE TEST CERTIFICATE This is to certify that the following items are tested and checked Microprocessor Based Conventional...

Страница 32: ...warranty period returned to the company under a written intimation and which to the company s satisfaction to be found defective The company reserves the right to decide the workplace for the repair w...

Страница 33: ...P N RE 102 104 Rev No 0 32 Ravel Electronics Pvt Ltd 150A Electronic Industrial Estate Perungudi Chennai 600096 India Web www ravelfirepanels com Email marketing ravelfirepanels com...

Отзывы: