Input: 

  • 100-120vac, 50/60Hz, 4.0A

Output:

  • 24vdc @5A total continuous output

  • Filtered and electronically regulated output

  • 12 PTC protected outputs @0.500A current limited

  • Class 2

  • 24vdc adjustable output

  • 24vdc S1 on/off switch

  • Input and output status LED indicators

Protection:

  • Short Circuit/Overload/Over Voltage

Supervision:

  • DC power failure supervision (form C contacts)

Environmental:

  • For indoor use ONLY

  • Operating temperature 32° F to 120° F (0° C to 49° C) ambient

Power Distribution Module:

Page 5

Terminal Identification:

Under normal conditions, the 2500-PWR24U should be checked for proper operation annually. It is recommended to 

check the output voltage and verify that 24vdc is present under normal load conditions. It is also recommended to  

check the current draw to ensure that the current is within specifications.

Conforms to UL STD 2017

Specifications

Maintenance

Troubleshooting

Terminal Legend

Function/Description

L, G, N

Connections for VAC terminals: L to Hot, N to Neutral, Ground to Chassis

+ DC -

24vdc @5A cotinuous power limited output

DC Power Failure

Indicates loss of DC power, e.g. connect to annunciator/alarm panel

NC, C, NO

Relay normally energized when DC power is present. Contract rating at 1A @ 28vdc.

    Earth Ground Stud

Used for making connection from enclosure to earth ground

1+ to 12+

Positive DC power outputs

1- to 12-

Negative DC power outputs

Problem

Possible Cause & Solutions

Green power LEDs are 

not illuminated:

• Verify the power switch S1 on the Distribution Board is set to “ON” (Fig. 3, pg. 4).

• Verify the 2500-PWR24U is connected to a good 120vac power source.

Device does not have 

power:

• Verify the green LEDs are illumninated on the 2500-PWR24U (Fig. 2 and 6, pg. 4).

• Verify that each output on the 2500-PWR24U is producing 24vdc.