Power Meter Quick Setup Guide 
QSG-PMM-0

B

-E 

 255-64-0004-00 

Product Specification 

Voltage Measurement 
Inputs: 

Input Range* 

90-277VLN, 156-480VLL

Phase to Ground* 

277V 

Measurement Category  CAT III, Pollution Level 2 

Frequency 

47-63 Hz 

Input Impedance 

10MΩ 

*Ratings for models with field wiring terminals. For models with factory
installed line-cords, rating is limited by plug and ratings are labeled on
back on unit.

Current Measurement 
Inputs: 

Input Range 

0-400mV

Input Impedance 

10k 

CT Type 

Voltage Output = 333mV at rated current 

CT Rated Current 

1-1200A

Meter Measurement 
Accuracy: 

Active Power & Energy 

0.5%: IEC 62053 Class .5, EN 50470-3 
Class C 

Reactive Power & 
Energy 

2% 

RMS Voltage & Current  0.2% 

Frequency 

0.1% 

Sample Rate 

64x AC frequency (phase locked) 

Measurement Update 
Rate 

3 seconds: IEC 61000-4-30 Class S 

Power Requirements: 

Voltage 

90-240V

Current 

0.2A 

Overvoltage Category 

CAT III, Pollution Level 2 

Frequency 

47-63 Hz

Содержание PM Series

Страница 1: ...d only for use with 0 33V output current transducers CTs DO NOT USE CURRENT OUTPUT e g 5A CTs ON THIS PRODUCT Failure to follow these instructions can result in overheating and permanent equipment dam...

Страница 2: ...wer meter with neutral and earth current monitoring PMB a 96 channel branch circuit monitor that plugs into PMM A PMM PMB monitors a panel board mains and branch circuit PMC power meter controller One...

Страница 3: ...ited by plug and ratings are labeled on back on unit Current Measurement Inputs Input Range 0 400mV Input Impedance 10k CT Type Voltage Output 333mV at rated current CT Rated Current 1 1200A Meter Mea...

Страница 4: ...Temperature 0 60 C Operating Humidity 5 85 RH Operating Elevation 0 3000m Conformance Safety UL EN 61010 1 EMC EMI EN61326 1 FCC Part 15 Class A Power Meter PMM Connectors and Controls A Voltage measu...

Страница 5: ...ctor cable CT 5 connector 6 Multi conductor cable CT 6 connector 7 Multi conductor cable CT 7 connector 8 Multi conductor cable CT 8 connector Power Meter Controller PMC A MODBUS RDU isolated RS 485 B...

Страница 6: ...ail Pull white tab here to remove Voltage and Current Measurement Wiring A Protect phase lines with fused disconnects rated for available short circuit current at connection point B All wiring 14 22 A...

Страница 7: ...anels White labels for sequentially numbered panels C Multi conductor CT cable Available lengths 3m 10m D Connect labeled end into matching labeled connector All CTs 333mV output DO NOT current output...

Страница 8: ...auxiliary AC power source Powering from the voltage measurement inputs minimizes circuitry but the meter may stop functioning if the voltage turns off Powering from an auxiliary single phase circuit i...

Страница 9: ...ain wired to a single controller PMC using shielded cat 5 Ethernet cable The wiring order of the modules and controller is not important A All cables shielded Cat 5 each cable 100m max length B Switch...

Страница 10: ...ect a cat 5 cable between the PC and PMM network ports 3 Open a browser Enter the URL https pdu local The login page appears If the URL does not resolve use the IP address of the PMC Retrieve the dire...

Страница 11: ...from the BCM2 Support page Follow the instructions in the spreadsheet To configure with the product web interface Make a network connection to the product See Login and Configuration on page 10 Follow...

Страница 12: ...Ratings are marked on the CT 5 Click OK The configured power meter displays in the dashboard If there are more unconfigured power meters the scan results stay open Configure Panel Mains Circuit 1 In t...

Страница 13: ...Ratings are marked on the CT 7 Click OK The configured branch circuit monitor displays in the dashboard Configure Panel Branch Circuits 1 In the dashboard click the BCM to open the pop up menu 2 Click...

Страница 14: ...LL One Phase LLN or Three Phase Circuit type cannot be changed later 7 Enter the current rating of the circuit in Amps 8 Enter the rating of the CT connected at this circuit position in Amps 9 Click t...

Страница 15: ...ialog opens 3 Double click the reading you want to set thresholds for A new dialog opens on top 4 Select the checkbox for the level and enter the threshold current in amps Click OK This example shows...

Страница 16: ...h automatic and manual modes In automatic mode the display scrolls through readings Manual Mode In manual mode you can select readings and settings to view Press or to view the Main Menu To return to...

Отзывы: