Redundant Configuration
The procedure outlined below must be followed to ensure this configuration functions properly:
−
After installation, all UMT Matrix Switches should undergo a
FUNC
reset to clear the switch
database. This procedure should be performed starting from the third tier device down to the base
unit.
−
Execute the
FUNC
reset in the following order: UMT-3A
→
UMT-3B
→
UMT-2A
→
UMT-2B
→
UMT-Base 1
→
UMT-Base 2.
−
Whenever a third tier UMT Matrix Switch is replaced, all of the second tier and base UMT Matrix
Switches should undergo a
FUNC
reset.
−
Whenever a second tier UMT Matrix Switch is replaced, all of the base UMT Matrix Switches
should undergo a
FUNC
reset.
−
Whenever a base UMT Matrix Switch is replaced, only the new UMT Matrix Switch should
undergo a
FUNC
reset.
Figure 56 Redundant Configuration
UST
UST
UMT-3A
UMT-3B
UMT-2A
UMT-2B
UMT-Base1
UMT-Base2
UST
UST