Chapter 5: Using the Web Interface
130
"below lower non-critical" State
Only a numeric sensor shows this state.
This state means the sensor reading is below the lower non-critical
threshold as indicated below:
Lower Critical Threshold <= Reading < Lower Non-Critical Threshold
Note: The symbol <= means smaller than (<) or equal to (=).
"above upper non-critical" State
Only a numeric sensor shows this state.
This state means the sensor reading is above the upper non-critical
threshold as indicated below:
Upper Non-Critical Threshold <= Reading < Upper Critical Threshold
Note: The symbol <= means smaller than (<) or equal to (=).
"above upper critical" State
This state means a numeric sensor's reading is above the upper critical
threshold as indicated below:
Upper Critical Threshold <= Reading
Note: The symbol <= means smaller than (<) or equal to (=).
Unmanaging Environmental Sensors
When it is unnecessary to monitor a particular environmental factor, you
can unmanage or release the corresponding environmental sensor so that
the Dominion PX device stops retrieving the sensor's reading and/or state.
To release a managed sensor:
1. Choose External Sensors > External Sensors Details. The External
Sensor Details page opens.
2. Click Remove for the sensor that you want to release.
After a sensor is removed from management, the ID number assigned to
that sensor is released and can be automatically assigned to any
newly-detected sensor.