52 

 
 
 

Appendix 6 LBS port definition 

Definition of port

 

 

 

Connection between the UPS LBS port.   

UPS(RJ45) 

UPS(RJ45) 

Description 

Pin 1/2/3 

Pin 1/2/3 

LBS 

Pin 5/7/8 

Pin 5/7/8 

GND 

Available function of LBS 

The output power of two or more UPS in non-parallel system should be synchronized with each 

other. 

The output phase of two or more UPS in non-parallel system should be synchronized with each 

other. 

 

CAUTION!

 

Two or more LBS cables must be used to form a ring when two or more LBS in   

non-parallel system. And the cables must use horizontal line. 

 

 

 

 

 

Содержание UPS Series

Страница 1: ...t high frequency online UPS designed by our R D team who is with years of designing experiences on UPS With excellent electrical performance perfect intelligent monitoring and network functions smart...

Страница 2: ...le installation 26 3 12 LBS installation optional 27 3 12 1 LCD setting 27 3 12 2 LBS cable installation 27 3 12 3 UPS installation 28 4 Operation 28 4 1 Operation Modes 28 4 2 Turn on off UPS 31 4 2...

Страница 3: ...led from the battery is strongly poisonous and do harmful to body 4 Please avoid short circuit between anode and cathode of battery otherwise it will cause spark or fire 5 Don t disassemble the UPS co...

Страница 4: ...redundancy This series UPS adopts N X parallel redundancy design user can set different redundancy according to the importance of the load While the redundancy modules are set more than two the avail...

Страница 5: ...50 kVA 200 kVA 250 kVA 300 kVA 350 kVA 400 kVA 450 kVA and 400 kVA 600kVA The models provide 12 configurations 50 kVA 100 kVA 150 kVA 200 kVA 250 kVA 300 kVA 350 kVA 400 kVA 450 kVA 500 kVA 550 kVA an...

Страница 6: ...S is damaged or not during the transportation do not switch on the UPS if any damage found Please contact the dealer right away 3 Check the accessories according to the packing list and contact the de...

Страница 7: ...6 Front View internal 250kVA Full configuration Front View Side View Rear View Front View internal Front View Copper bar 200 300 400kVA Standard and Full configuration...

Страница 8: ...7 Front View Side View Rear View 200kVA Standard and Full configuration...

Страница 9: ...8 standard configuration full configuration Connect copper bar...

Страница 10: ...9 300kVA Standard and Full configuration standard configuration full configuration Connect copper bar...

Страница 11: ...10 400kVA Standard configuration Standard configuration Full configuration 400 500 600kVA Standard and Full configuration Front View Side View Rear View...

Страница 12: ...11 400kVA Full configuration Full configuration Connect coppper bar Mains bypass common copper bar...

Страница 13: ...12 500kVA Standard and Full configuration Standard configuration Full configuration Connect coppper bar Mains bypass common copper bar...

Страница 14: ...kVA Standard and Full configuration Standard configuration Connect copper bar Connect coppper bar Mains bypass common copper bar 1 LCD panel Display UPS data and status 2 power cabinet Assembly power...

Страница 15: ...er bar 18 Output A input copper bar 19 Output B input copper bar 20 Output C input copper bar 21 Output neutral copper bar 22 Bypass A input copper bar Wiring must be used when mains bypass separation...

Страница 16: ...tor unit 4 Intelligent slot ECU unit 1 PARALLEL port 2 LBS port 3 LED Dry contact unit 1 EPO port 2 SWITCH STATUS 3 the other port 4 BP_FEEDBACK PIN1_NC PIN2_NO PIN4_common 5 Optional dry contacts Mon...

Страница 17: ...6 1 Input dry contacts 2 LCD port 3 CAN port BMS port and remote LCD port 4 COM battery monitor port 5 BAT_T battery temperature detect port 6 PE 7 RS 485 3 3 UPS module appearance Front View Side Vie...

Страница 18: ...keep in a range of 0 40 If the environment temperature exceeds 40 the rated load capacity should be reduced by 12 per 5 The max temperature can t be higher than 50 If the UPS is dismantled under low...

Страница 19: ...t and rear so they should not be blocked by any exotic obstacles 3 5 External Protective Devices For safety reasons it is necessary to install external circuit breaker at the input A C supply and the...

Страница 20: ...is 400 V multiply the currents by 0 95 If the rated voltage is 415 V multiply the currents by 0 92 If primary loads are non linear loads increase the cross sectional areas of neutral wires1 5 1 7 time...

Страница 21: ...rimped OT terminals M10 10 5mm 26N m 250k Mains input connector Crimped OT terminals M10 10 5mm 26N m Bypass input connector Crimped OT terminals M10 10 5mm 26N m Battery input connector Crimped OT te...

Страница 22: ...utput connector Crimped OT terminals M16 18mm 120N m Grounding connector Crimped OT terminals M12 14mm 470N m 3 6 3 Recommended input front end and output back end circuit breakers UPS capacity Compon...

Страница 23: ...Connect each cabinet to the main ground system For Grounding connection follow the shortest route possible WARNING FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES MAY RESULT IN ELECTROMAGNETIC INTERFE...

Страница 24: ...neutral bonding arrangement must be in accordance with local and national codes of practice 3 9 Battery connection The UPS adopts positive and negative double battery framework total 30 optional 32 3...

Страница 25: ...i e inter tier and inter block connections are from to terminals Don t mix batteries with different capacity or different brands or even mix up new and old batteries either WARNING Ensure correct pol...

Страница 26: ...will light and green indicator flash Remove the screws 1 of the module and remove the module from the cabinet WARNING 1 Before start the module the module_ON switch must on the ON status and the red i...

Страница 27: ...UPS must be the same rated and connected to the same way bypass power supply Bypass and the mains input power must be received with the same neutral The output of all UPS machines must be connected t...

Страница 28: ...setting Set every UPS of the systems to be LBS Master or LBS Slave For instance if the UPS belongs to LBS master system its LBS setting must be set to Master 3 12 2 LBS cable installation The two por...

Страница 29: ...28 3 12 3 UPS installation The whole systems are showed below 4 Operation 4 1 Operation Modes...

Страница 30: ...o AC and supplies to the load Battery mode Stored Energy Mode If the AC mains input power fails the inverter which obtains power from the battery supplies the critical AC load There is no power interr...

Страница 31: ...z or less than 13 33ms 60Hz ECO Mode When the UPS is at AC Mode and the requirement to the load is not critical the UPS can be set at ECO mode in order to increase the efficiency of the power supplied...

Страница 32: ...is safely isolated from the UPS output terminals Turn ON the bypass and input switches of the UPS make sure that Bypass module insert the cabinet and fix with screws and the module_in switch at the o...

Страница 33: ...ng The UPS can be loaded up to its maximum capacity during load test 4 2 3 Cold start procedure CAUTION Follow these procedures when the input AC Utility Failure but battery is normal Switch on the ba...

Страница 34: ...no internal UPS faults Open the front and rear doors of the UPS to be easily access to the main power switches Switch ON the output switch Switch ON the input switch Switch ON the battery switch The...

Страница 35: ...parallel number for each UPS up to 4 units can be parallel set the ID of each cabinet the ID of each unit must be different Switch ON the input switch Close the external input switch and start from m...

Страница 36: ...click on the back icon return to last window and click on the homepage icon jumpe to main page 3 Click on the Load icon to enter the output data window click on the back icon return to last window and...

Страница 37: ...e battery icon to enter the battery data window click on the back icon return to last window and click on the homepage icon jumpe to main page 4 3 2 Click on Runn info icon to enter the information pa...

Страница 38: ...tione time click on the back icon return to last window and click on the homepage icon jumpe to main page 2 Click on the ENV data icon to enter the environment data window can see the temperature and...

Страница 39: ...page 3 Click on the module data icon to enter the module data window can see the module data click on the back icon return to last window and click on the homepage icon jumpe to main page 4 3 3 Click...

Страница 40: ...module data window can see the alarm data click on the back icon return to last window and click on the homepage icon jumpe to main page 2 Click on the module data icon to enter the module data windo...

Страница 41: ...n to last window and click on the homepage icon jumpe to main page 4 3 4 Click on setting icon to enter setting page click on the back icon return to last window and click on the homepage icon jumpe t...

Страница 42: ...click on the back icon return to last window and click on the homepage icon jumpe to main page 4 3 6 Click on Function icon to enter setting page click on the back icon return to last window and clic...

Страница 43: ...Fan Fault Beep continuously Fault LED lit 9 17 Fan Power fault Beep continuously Fault LED lit 10 18 Charger Over Temp Beep continuously Fault LED lit 11 19 Soft Start Failed Beep continuously Fault...

Страница 44: ...ult LED lit 46 155 Dry contact Power Fault Beep continuously Fault LED lit 47 156 Dry contact Comm Fault Beep continuously Fault LED lit 48 157 Bypass Feedback Fault Beep continuously Fault LED lit 49...

Страница 45: ...BPS Par cable abnormal Once per 2 seconds Alarm LED lit 36 357 Bypass Comm Error Once per 2 seconds Alarm LED lit 37 358 Bypass module take over Once per 2 seconds Alarm LED lit 4 5 Options Network M...

Страница 46: ...323 138Vac At 30 C The UPS works at full load when the voltage is 305 485Vac and is derated load when the voltage is 305 138Vac Frequency Range 40Hz 70Hz Power Factor 0 99 Current THDi 3 100 nonlinear...

Страница 47: ...Mode Switch to Bypass Backup Mode Shut down UPS immediately Battery Low Alarm and Switch off Self diagnostics Upon Power On and Software Control EPO Shut down UPS immediately Battery Advanced Battery...

Страница 48: ...0 20 30 Frequency protection range 10 Output Phase 3 Phase 4 Wires and Ground Rated Voltage 380 400 415Vac Power Factor 1 Voltage Regulation 1 Frequency Utility Mode 1 2 4 5 10 of the rated frequency...

Страница 49: ...tery Voltage parameter set history record Other Standard cabinet Dimensions W D H 600 850 2000 600 850 2000 1200 850 2000 Full cabinet Dimensions W D H mm 1200 850 200 0 Module Dimensions W D H mm 440...

Страница 50: ...already damaged Take out this module replace with a new module 8 Utility LED is flashing Utility voltage exceeds UPS input range If the UPS operates at battery mode please pay attention to the remaini...

Страница 51: ...PIN 1 PIN 1 CAN_H PIN 2 PIN 2 CAN_L PIN 3 7 PIN 3 7 CAN_GND Available function of CAN Communicate to BMS Communicate to remote LCD Appendix 4 RS485 communication port definition Definition of port Co...

Страница 52: ...Definition of port Connection between the Device s RS485 port and UPS COM port device RJ45 UPS RJ45 Description Pin 1 5 Pin 1 5 485 A Pin 2 4 Pin 2 4 485 B Available function of RS485 communicate to...

Страница 53: ...Available function of LBS The output power of two or more UPS in non parallel system should be synchronized with each other The output phase of two or more UPS in non parallel system should be synchr...

Страница 54: ...UPS REPO Description Pin 1 Pin 1 GND Pin 2 Pin 2 EPO In addition to the local EPO push button on the front panel of the UPS that stops operation of that module when pressed for more than 3 second the...

Страница 55: ...connector The remote switch can be connected to several UPS s in a parallel architecture allowing the user to stops all units at once Additionally a second system not provided can be connected to the...

Отзывы: