battery will not be damaged. When the battery charge is higher than the 

over-discharge voltage returns, the controller exits over-discharge protection, 

restore power to the load. 

 

over-voltage protection:

 

When  the  battery  voltage  is  increased  to  over-voltage  point,  the 

controller  enters  the  state  of  overcharge  protection;  turn  off  the  load 

output,  in  order  to  protect  the  load  is  not  damaged.  When  the  battery 

voltage  is  lower  than  over-voltage,  the  controller  exits  over-voltage 

protection, restoration load output. 

● 

Overload protection 

When the load current exceeds the rated current, will enter the overload 

time limited protection mode, to avoid damage to the controller. When the 

load current is less than 1.25 times the rated current, the controller may 

overload long run, but by the controller temperature protection control. 

{

Overload time limited protection

}: 

The  load  current  is  equal  to  1.25  times  the  rated  current  with  working 

for  120s,  load  disconnect  output;  1.5  times  for  10S,  2  times  overload 

protect immediately. 

 

Load Fault protection:

 

If load short circuit, the controller automatically protection, the Controller 

will detect whether the load fault exclusion. If the fault persists more than 5 

times, the controller will off the load output. 

 

Over-temperature protection:

 

When  the  controller  itself  temperature  is  too  high  (>  85  °),  in  order  to 

avoid  damage,  the  controller  will  cut  off  the  load  output  or  charging,  stop 

working,  and  so  on  after  the  temperature  dropped  to  65  °,  and  then 

restarting the load or charge. 

 

Temperature sensor damage fault protection:

 

When the temperature sensor short circuit or damage, the controller will 

default to work at 25 

, in order to avoid erroneous temperature 

compensation for damage to the battery. 

 

Battery polarity protection:

 

Содержание SUNSHIELD PRO

Страница 1: ...8V Max PV Voltage 150V Rated Current 50A 80A Date of Purchase S N Ramsond Corporation World headquarters 4051 Haggerty Rd West Bloomfield MI 48323 Ramsond North America Service Warranty Center 14850 L...

Страница 2: ...g term safe and reliable operation within the definition PV and Battery both with against reverse protection All products are equipped with soft start and overload time limit protection adaptation cap...

Страница 3: ...or custom Variety parameters can be modified support panel keypad or infrared remote control Support PV Battery Load key parameters display and check Manual Light Control or automatic dual period loa...

Страница 4: ...RS485 terminal Connected with computer or other controllers to realize the remote communication 5 The terminal of the temperature sensor Connected with the controller temperature sensor that offered...

Страница 5: ...06 mm Distance of installation hole 177 5x60 mm Installation hole 6 5x3 5 mm Install Step a Type Selection Please strictly follow the system application range choose the most appropriate products spec...

Страница 6: ...state to adjust it Typically as long as the battery voltage is in the range shown in the following table the controller can correctly recognize the system voltage without manually setting 12V system...

Страница 7: ...hich built in SDI P series controller can be soft start and provides a larger starting current to the load especially for the capacitive load equipment such as inverters switching power supplies etc g...

Страница 8: ...button to on off the load Note When Controller fails the error icon flashes and an error code display on the LCD screen User can press up or down button to view details Table of Error Code E101 load...

Страница 9: ...to mode PV 3 Light control voltage PV 4 Light control delay time minute BAT 5 Battery type BAT 6 System Voltage Note following parameter only for battery type at DIY BAT 7 Over voltage BAT 8 Over disc...

Страница 10: ...late the battery voltage to maintain it at the setting value to prevent battery overcharge c Float Charging At this stage the battery nearly full no need more power But the controller will remain very...

Страница 11: ...monitor status of the controller Others Additional interfaces optional SDI P series controller configuration USB interface is optional interface which Supports load output capability of USB 5V1A Batt...

Страница 12: ...by the controller temperature protection control Overload time limited protection The load current is equal to 1 25 times the rated current with working for 120s load disconnect output 1 5 times for 1...

Страница 13: ...12V 24V 36V 48V PV max open circuit voltage 150V Rated load current 50A 60A 70A 80A Direct charge voltage GEL 14 4V LEAD ACID 14 2V Custom 9 17V x12V Boost charge voltage GEL 14 8V LEAD ACID 14 6V Cus...

Страница 14: ...essness or negligence if the problem was preventable by proper usage then the warranty is not applicable and Ramsond Corporation must charge a fee for repair services For complete information on warra...

Страница 15: ...15 Fax 248 363 7834 Sales Service Email sales ramsond com Technical Support Email tech ramsond com Web www ramsond com Note Dates Time Weather Solar Voltage Solar Amperage Battery Voltage...

Отзывы: