Terminating the RAK-LINK
The final step in the installation process is to terminate the RAK-LINK. The termination that
is required depends on the nature of the installation and the position of the RAK-LINK within
the system.
Termination Jumper settings:
No Term - Both Jumpers removed
Used when the RAK-LINK is not at the end of line. This is usually identifiable by two cables
being punched down to the RAK-LINK.
Term - Jumper fitted across 1+2 & 4+5
Used when the RAK-LINK is end of line in a daisy chain configuration (such as the
RAK-LINK shown in “Typical Wired Installation layout” on page one).
Star Term - Jumper fitted across 2+3 & 5+6
Used when the RAK-LINK is end of line in a STAR wire configuration.
Programming the RAK-LINK
The RAK-LINK is programmed using the Rasoft pro programming software. A
WA/WTC-Bridge is required for any programming of a wired system.
For more information on how to programme a RAK-LINK please refer to “Wired System
Setup Guide”