35
GB
INSTALLATION
DIMENSIONS TERMINAL POSITION
DISTANCE (mm)
A*
Directly below an opening, ventilation, opening window, etc.
600
B
Above an opening, ventilation, opening window, etc.
300
C
Adjacent to an opening, ventilation, opening window, etc.
400
D
Below gutters, soil pipes or drainpipes
300
E
Below eaves
300
F
Below balconies of car port roof
600
G
From a vertical drainpipe or soil pipe
300
H
From an internal or external corner
600
I
Above ground roof or balcony level
300
J
From a surface facing the terminal
600
K
From a terminal facing the terminal
600
L
From an opening in the car port (e.g. door, window into the dwelling)
1200
M
Vertically from a terminal on the same wall
1500
N
Horizontally from a terminal on the same wall
300
P
From a vertical structure on the roof
600
Q
Above an intersection with the roof
150
POSITIONING FLUE TERMINALS
The table below shows how different flue terminals can
be positioned in the house and how large the safety
distances must be.
* In addition, the terminal should not be nearer than 300 mm to an opening in the building fabric
formed for the purpose of accommodating a built in element such as a window frame.
NOTE!
Be aware that the safety distances
below are English national guides.
Please follow national regulatory
requirements.