Advanced Setup
Relay Outputs: Relay Mode
Use this menu to change the mode of one or both relay outputs� The mode
defines the behavior of the output�
1� Navigate to
SETUP > ADVANCED SETUP > RELAY OUTPUTS.
2� Press UP/DOWN to scroll to an output mode, then press ENTER�
3� Scroll through the available modes, then press ENTER to select and save
the setting�
Option
Description
NO RELAY/DISABLED
Disables output
TOTALIZER
Totalizer output
ALARM: HIGH
On/Off function, energized at the high set point
ALARM: LOW
On/Off function, energized at the low set point
ALARM: RANGE
On/Off function, energized beyond high and low set points
MANUAL
On/Off function of manual operation
Table 17: Relay mode options
Relay Outputs: Relay Settings
Use this menu to change the relay settings for the respective relay mode�
1� Navigate to
SETUP > ADVANCED SETUP > RELAY OUTPUTS
�
2� Press UP/DOWN to scroll to the applicable relay setting, then press ENTER�
3� Scroll to and edit each option, as necessary�
OTE:
N
Alarm icons "R1" and "R2" will appear in the upper right section of the Home Screen
to provide a local indication when a relay condition has been met and when the
relay has be energized�
Output Mode Option
Description
TOTALIZER
OUTPUT SOURCE Parameter assignment (e�g� Flow Total or Energy Total)
SCALING FACTOR Pulse(s) transmitted per unit of measure
UNITS
Converts output unit of measure
PULSE WIDTH
Time between the rising and falling edges of a single pulse
ALARM: HIGH
OUTPUT SOURCE Parameter assignment (such as Flow Rate or Temperature)
HIGH SETPOINT
Instructs the device to energize the relay if this value reached/
exceeded� This value is linked to the
OUTPUT SOURCE
and its unit
of measure (for example, Flow Rate in GPM)
HYSTERESIS HI
Creates a window/zone below the
HIGH SETPOINT
value where
the relay remains in an energized state
SET DELAY
Time in seconds that will elapse before the relay energizes, if the
HIGH SETPOINT
value is reached/exceeded
RELEASE DELAY
Time in seconds that the relay will remain energized, if the
HYSTERESIS HI
value is reached/exceeded
LATCHING
Leaves the relay in an energized state until it is manually cleared
on the device, either through the keypad interface or through
the Digital I/O channels
Page 31
June 2020