Voltage Monitor – Instruction Manual 
Model 520603-2V150

 

 

P/N 520603-
2V150 

REV. B  9/11 

© 2011 RAILWAY EQUIPMENT CO. 

 

4

 
                                

HIGH AMP 

                                SET ___    - 

Parameter for amp setting above which channel two will change relay 

                                State.  Amp range is -120 to +120 amps.  Factory default is +120 amps. 
 
                                

LOW AMP 

                                SET ___   - 

Amp setting below which channel two will trip.  Amp range is -120 

                                to +120 amps.  Factory default is -120 amps. 
 
                                There is also an optional temperature probe that can control the channel two 
                                output.  If the probe is used, the temperature can be displayed as Fahrenheit 
                                or Celsius.  To select either Fahrenheit or Celsius, enter 10 on the 

PASSWORD 

                                screen.  With 10 as your password, two additional screens will show up as the 
                                parameter screens are toggled through.  One screen  is: 

 F OR C _____.

 The 

                                

INCREASE

 or 

DECREASE

 buttons can be used to select which temperature scale  

                                will be displayed.  The next screen  will be 

REV. LEV ______.

  This screen will 

                                display the software revision level installed on the monitor.  The addition of the 
                                temp probe adds the following screens: 
 
                                

HIGH TEMP  

                                SET ___       - 

Temperature setting above which channel two relay will change 

                                state.    Available temperature range is -40 to +300 degrees F (-40 to 148.9  
                                degrees C).  Factory default is +300 F (148.9 C). 
 
                                

LOW TEMP 

                                SET ___      - 

Temperature setting below which channel two relay will change 

                                state.  Available temperature range is -40 to +300 degrees F (-40 to 148.9 
                                degrees C).  Factory default is -40 F (-40 C). 
 
                                The following 

Fault Counter Screens 

will appear only if the fault count in each is  

                                Greater than 0: 
                                 
                                

CH 1 HI V 

                                COUNT ___ - 

Number of high voltage incidents on Channel 1.  Press 

DECREASE

   

                                to clear. 
 
                                

CH 1 LO V 

                                

COUNT ___ -

Low voltage incidents on Channel 1.  Press 

DECREASE

 to clear. 

                                 
                                

CH 2 HI V 

                                COUNT ___ - 

High voltage incidents on Channel 2.  Press 

DECREASE 

to clear. 

 
                                

CH 2 LO V 

                                COUNT ___ - 

Low voltage incidents on Channel 2.  Press 

DECREASE 

to clear. 

 
                                

HI TEMP 

                                COUNT ___ - 

High temperature incidents on Channel 2.  Press 

DECREASE 

to  

                                clear. 
 
                                

LOW TEMP 

                                COUNT ___ - 

Low temperature incidents on Channel 2.  Press 

DECREASE 

to  

Содержание 520603-2V150

Страница 1: ...ree standing unit that features the ability to monitor two DC voltage sources and has optional temperature and current monitoring ability CRAGG RAILCHARGER Instruction Manual for Digital Voltage Monit...

Страница 2: ...ii Contents 1 0 WARNINGS CAUTIONS AND NOTES 1 2 0 OPERATION 2 2 1 Front Panel Features and Components 2 2 1 1 Figure 1 Front Panel of Voltage Monitor 3 2 1 2 Digital Display 3 2 1 3 Push Buttons 5 2...

Страница 3: ...fore proceeding Table 1 Warnings Cautions and Notes Symbol Description WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION indicate...

Страница 4: ...e fuse Channel two has a voltage range of 1 to 150 VDC but is only available for use if channel one is powered There is 2 500 volts isolation between channels The monitor has easy front panel access f...

Страница 5: ...y will change state and the channel one CHANNEL OK LED will go out Factory default is 50 0 VDC LOW VCH1 SET __ _ Low voltage setpoint for channel one adjustable from 0 to 50 0 VDC If the input voltage...

Страница 6: ...screen will display the software revision level installed on the monitor The addition of the temp probe adds the following screens HIGH TEMP SET ___ Temperature setting above which channel two relay w...

Страница 7: ...if enabled MODE This control is used to increment through the available screens 2 1 4 LED Status Indicators Two LEDs are used to indicate Channel OK one for each input channel 2 1 5 External Wiring C...

Страница 8: ...current level can be used to trigger a fault condition on channel two either independently or in conjunction with channel two voltage and or with the temperature sensor described in 2 1 7 2 1 7 TEMPE...

Страница 9: ...attery Voltage Monitor with Relay Outputs For Lead Acid and NiCad Batteries Programmable Voltage Parameters LED Status Indicators Digital Amperage Meter when optional Amp Probe is used Digital Voltage...

Страница 10: ...DC Channel 1 and 2 sensitivity is 100 MV per step The inputs are protected against reverse polarity The input power is protected by an internal resettable fuse The monitor outputs are form C relay wit...

Отзывы: