Technical specification

NUMBER OF CHANNELS

One, Two, Three or Four channels

OUTPUTS

Common Relays - user selectable

High alarm RL2 - D.P.C.O. normally energised or de-energised - factory set de-energised
Latched or unlatched - factory set latched
Low alarm RL1 - D.P.C.O. normally energised or de-energised - factory set de-energised
Latched or unlatched - factory set latched
Fault alarm RL3 - S.P.C.O. normally energised or de-energised - factory set de-energised
Latched or unlatched - factory set latched
General Alarm Relay RL4 - S.P.C.O. changes on all alarms and is resettable at all times.

Channel Relay - user selectable

Selectable high or low alarm S.P.C.O. normally energised or de-energised
- factory set low de-energised
Latched or unlatched - factory set latched
All contacts rated 5A/230v AC
Analogue output 4~20mA into 200 ohms max load

SENSOR CABLE

Flammable (catalytic) - 3 core, 1.5mm screened cable, mineral insulated copper sheathed or
steel wire armoured – maximum cable loop resistance 20 ohms.
Transmitter – 3 core 0.5 mm minimum screened cable, mineral insulated copper sheathed or
steel wire armoured – maximum cable loop resistance 200 ohms.

POWER SUPPLY

230, 110v, AC 50/60Hz. or 24v DC (21-30 volts tolerance)

POWER CONSUMPTION

Per channel
Normal operating condition

3w

Full alarm condition

4.5w

OVERLOAD PROTECTION

1A fuse - AC
1 amp anti-surge fuse - DC
2 amp anti-surge fuse - Batteries.

ACCURACY

±5% F.S.D

REPEATABILITY

±2% F.S.D

ENVIRONMENTAL

Ambient operation temp.

0 to 50 degrees centigrade

Storage temperature

-20 degrees to +60 degrees centigrade

Humidity range

0 to 90% RH

Case Ingress Protection

IP52 - Option IP65

MISCELLANEOUS

CE Cert No.

C511

Dimensions

310mm wide x 265mm high x 75mm deep

Weight

3.5kg

ADD ON OPTIONS: 

Standby battery 1 hour - Field installation - position the batteries so that they are supported by
the plastic base block and then retained using the tywrap, connect the battery connectors to
terminal blocks JP11 and JP12.

Содержание FMC-40

Страница 1: ...FMC 40 OPERATING HANDBOOK Manual No AWK043 4 C922...

Страница 2: ...il and Field Terminals 15 3 Alarm Board Component Layout 16 4 Sensor Termination 17 SYSTEM DATA Manufacture date Works Order No Sensor type life life life life Gas Range Low alarm trip High alarm trip...

Страница 3: ...is indicated by the amber L E D press again to continue the auto step sequence RANGE INDICATORS Three range indicators are positioned directly above the panel meter L E L Lower Explosive Level PPM Par...

Страница 4: ...ER used to adjust the meter indication to read correctly when the sensor is subject to a test gas of known concentration ALARM SET SWITCH alarm trip points setting SENSOR CURRENT POTENTIOMETER sensor...

Страница 5: ...core 1 5mm screened cable mineral insulated copper sheathed or steel wire armoured maximum cable loop resistance 20 ohms Transmitter 3 core 0 5 mm minimum screened cable mineral insulated copper shea...

Страница 6: ...f the power supply to which the instrument will be connected SITING THE SENSING HEADS A key feature of the installation is the correct siting of the sensing head Several considerations must be taken i...

Страница 7: ...vent gas reaching the sensor When monitoring gases outside those lighter than air will be quickly dispersed but gases heavier than air will tend to form in layers and again cause a dangerous hazard Wh...

Страница 8: ...minutes for the sensors to stabilise Select channel 1 and for flammable or toxic sensors adjust meter to read zero by means of appropriate ZERO POTENTIOMETER marked Z on the alarm module or for oxyge...

Страница 9: ...isplay toxic flammable or 20 8 for oxygen and press alarm set switch alarm indicators will turn off and the green power indicator will turn on SENSOR SUPPLY ADJUSTMENT CATALYTIC SENSOR Factory set no...

Страница 10: ...servicing and instructed not to attempt to exceed the scope of such training Liaison should be established with those responsible for maintenance of the building fabric or redecoration etc to ensure t...

Страница 11: ...switch on or off any electrical lights or appliances D Turn off the gas supply at the gas emergency control and or with L P G supply the storage tank E Open doors and windows to increase ventilation I...

Страница 12: ...er Million vol Volume Hi High Alarm Lo Low Alarm C1 C4 Channel Selection Sensor F Fault Indicator P Power On Green Mains Fail Red Hold Channel Selection Reset Sounder Alarms Test Electronic System Tes...

Страница 13: ...ly energised Normally de energised J3 Common Low Relay Normally energised Normally de energised J1 Common Fault Relay Normally energised Normally de energised J5 Sounder Permanent Mute JP10 remove Sta...

Страница 14: ...secs T2 30 secs When used with GDS300 Flow sample systems FS Sensor Selection 24v 4 20mA input P Pellistor mV input 4 20mA Output TP3 TP4 Calibration TP1 TP2 Adjustments Potentiometer RV1 Sensor Zero...

Страница 15: ...l Unit Detector Head mV pellistors or 3 wire CV W Y P W Y SIG P E Gas Detector Control Unit CV Transmitter Gas Detector Control Unit Transmitter W Y P 24V OV SIG Sensor Sensor Sensor RED ident R flamm...

Страница 16: ...16...

Отзывы: