DESCRIPTION

The FMC-40 is a multi channel combustible and toxic gas monitor, which can accommodate
up to 4 sensor channels housed in wall mounting enclosure. Sensors may be added or
removed as required, but should be carried out with the power to the unit switched off. Each
sensor continuously monitors for gas, with the digital display sequentially sampling each
sensor reading. Where a particular sensor reading requires to be viewed, the hold button
should be pressed when the channel indicator is on the appropriate sensor, pressing the
hold button again will restart the sampling sequence.

The gas alarms are activated at preset levels and will remain on until the gas clears, these
in turn activate the appropriate alarm relays. The fault indicator is initiated should the
sensor connecting lines become open/short circuit, or an electronic fault be detected.

The control unit requires an a.c. mains power supply and/or a low voltage d.c. power
supply. When both are provided the low voltage d.c. acts as a standby supply in the event
of an a.c. mains power failure.

HOLD

(Fig.1) Pressing and releasing the button will hold the meter display on a particular

sensor channel which is indicated by the amber L.E.D., press again to continue the auto
step sequence.

RANGE INDICATORS

Three range indicators are positioned directly above the panel

meter % L.E.L. (Lower Explosive Level), PPM (Parts Per Million) and % Volume, each
sensor is addressed to indicate its appropriate range.

MAINS ON LAMP

(P) GREEN indicates that power is being supplied to the control unit.

When the optional standby battery is fitted loss of mains supply will result in the GREEN
Mains ON Lamp changing to RED.

ALARM LAMPS

C1, C2, C3, C4 - Lo and Hi RED illuminated when the gas concentration

increases beyond the alarm trip points.

FAULT LAMP

(F) AMBER illuminated in the event of a sensor cable fault or sensor supply

circuit /electronic fault.

SOUNDER

initiated in the presence of a fault or gas alarm condition.

TEST

When pressed for 15 seconds alarm L.E.DʼS are activated. If pressed for a further

15 seconds alarm relays will change state.

RESET

used to mute the sounder and reset alarms, gas alarms cannot be reset until the

gas concentration has decreased below the set alarm level.

ALARM RELAY INHIBIT

Pressing the reset pad for 15 seconds will inhibit the alarm relays

which is indicated by the fault light coming on. To remove the inhibit press the reset pad for
15 seconds, the fault light will turn off.

ZERO POTENTIOMETER

meter zero adjust when the sensor is monitoring a gas free

atmosphere.

3

Содержание FMC-40

Страница 1: ...FMC 40 OPERATING HANDBOOK Manual No AWK043 4 C922...

Страница 2: ...il and Field Terminals 15 3 Alarm Board Component Layout 16 4 Sensor Termination 17 SYSTEM DATA Manufacture date Works Order No Sensor type life life life life Gas Range Low alarm trip High alarm trip...

Страница 3: ...is indicated by the amber L E D press again to continue the auto step sequence RANGE INDICATORS Three range indicators are positioned directly above the panel meter L E L Lower Explosive Level PPM Par...

Страница 4: ...ER used to adjust the meter indication to read correctly when the sensor is subject to a test gas of known concentration ALARM SET SWITCH alarm trip points setting SENSOR CURRENT POTENTIOMETER sensor...

Страница 5: ...core 1 5mm screened cable mineral insulated copper sheathed or steel wire armoured maximum cable loop resistance 20 ohms Transmitter 3 core 0 5 mm minimum screened cable mineral insulated copper shea...

Страница 6: ...f the power supply to which the instrument will be connected SITING THE SENSING HEADS A key feature of the installation is the correct siting of the sensing head Several considerations must be taken i...

Страница 7: ...vent gas reaching the sensor When monitoring gases outside those lighter than air will be quickly dispersed but gases heavier than air will tend to form in layers and again cause a dangerous hazard Wh...

Страница 8: ...minutes for the sensors to stabilise Select channel 1 and for flammable or toxic sensors adjust meter to read zero by means of appropriate ZERO POTENTIOMETER marked Z on the alarm module or for oxyge...

Страница 9: ...isplay toxic flammable or 20 8 for oxygen and press alarm set switch alarm indicators will turn off and the green power indicator will turn on SENSOR SUPPLY ADJUSTMENT CATALYTIC SENSOR Factory set no...

Страница 10: ...servicing and instructed not to attempt to exceed the scope of such training Liaison should be established with those responsible for maintenance of the building fabric or redecoration etc to ensure t...

Страница 11: ...switch on or off any electrical lights or appliances D Turn off the gas supply at the gas emergency control and or with L P G supply the storage tank E Open doors and windows to increase ventilation I...

Страница 12: ...er Million vol Volume Hi High Alarm Lo Low Alarm C1 C4 Channel Selection Sensor F Fault Indicator P Power On Green Mains Fail Red Hold Channel Selection Reset Sounder Alarms Test Electronic System Tes...

Страница 13: ...ly energised Normally de energised J3 Common Low Relay Normally energised Normally de energised J1 Common Fault Relay Normally energised Normally de energised J5 Sounder Permanent Mute JP10 remove Sta...

Страница 14: ...secs T2 30 secs When used with GDS300 Flow sample systems FS Sensor Selection 24v 4 20mA input P Pellistor mV input 4 20mA Output TP3 TP4 Calibration TP1 TP2 Adjustments Potentiometer RV1 Sensor Zero...

Страница 15: ...l Unit Detector Head mV pellistors or 3 wire CV W Y P W Y SIG P E Gas Detector Control Unit CV Transmitter Gas Detector Control Unit Transmitter W Y P 24V OV SIG Sensor Sensor Sensor RED ident R flamm...

Страница 16: ...16...

Отзывы: