background image

Page 1 of 8                                                                                                                                                   IN014 Rev I 

 

 
 

 

 
 
 

 

 

 

 

 

 

 

 

Please Read And Save These Instructions 

DO NOT CONNECT POWER SUPPLY UNTIL FAN IS COMPLETELY 
INSTALLED. MAKE SURE ELECTRICAL SERVICE TO FAN IS LOCKED IN 
"OFF" POSITION. DISCONNECT POWER BEFORE SERVICING FAN. 

 

1.  

WARNING!

  Do not use fan in hazardous environments where fan electrical system could provide ignition to    

     combustible of flammable materials. 
2.  

WARNING!

  Do not use fan to pump explosive or corrosive gases. 

3. 

 WARNING! 

 Check voltage at the fan to insure it corresponds with nameplate. 

4.  

WARNING!

  Normal operation of this device may affect the combustion airflow needed for safe operation of     

     fuel burning equipment. Check for possible backdraft conditions on all combustion devices after installation. 
5.  

NOTICE!

  There are no user serviceable parts located inside the fan unit. 

     

Do NOT attempt to open.

 Return unit to the factory for service. 

6.  All wiring must be performed in accordance with the National Fire Protection Association’s (NFPA)”National    
     Electrical Code, Standard #70”-current edition for all commercial and industrial work, and state and local     
     building codes. All wiring must be performed by a qualified and licensed electrician. 
7. 

WARNING! 

 Do not leave fan unit installed on system piping without electrical power for more than 48 hours.  

    Fan failure could result from this non-operational storage.  
8. 

WARNING  - TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS,  

    OBSERVE THE FOLLOWING: 

    

a) Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.

 

    b) Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to      
    prevent power from being switched on accidentally. When the service disconnecting means cannot be locked,     
    securely fasten a prominent warning device, such as a tag, to the service panel

 

 

 

Содержание XP101

Страница 1: ...o open Return unit to the factory for service 6 All wiring must be performed in accordance with the National Fire Protection Association s NFPA National Electrical Code Standard 70 current edition for all commercial and industrial work and state and local building codes All wiring must be performed by a qualified and licensed electrician 7 WARNING Do not leave fan unit installed on system piping w...

Страница 2: ... considered in the overall system design In some cases the rushing sound of the outlet air may be disturbing In these instances the use of a RadonAway Exhaust Muffler is recommended 1 4 GROUND WATER In the event that a temporary high water table results in water at or above slab level water may be drawn into the riser pipes thus blocking air flow to the GP XP XR Series Fan The lack of cooling air ...

Страница 3: ... 90 CFM For more precision determine flow rate by using the chart in the addendum Under some circumstances in an outdoor installation a condensate bypass should be installed in the outlet ducting as shown This may be particularly true in cold climate installations which require long lengths of outlet ducting or where the outlet ducting is likely to produce large amounts of condensation because of ...

Страница 4: ...or electrical boxes are outdoor rated and properly sealed to prevent water penetration into the box A means such as a weep hole is recommended to drain the box 1 9 SPEED CONTROLS The GP XP XR Series Fans are rated for use with electronic speed controls however they are generally not recommended If used the speed control recommended is Pass Seymour Solid State Speed Control Cat No 94601 I 2 0 INSTA...

Страница 5: ...solation 2 4 ELECTRICAL CONNECTION Connect wiring with wire nuts provided observing proper connections See Section 1 8 2 5 VENT MUFFLER optional Install the muffler assembly in the selected location in the outlet ducting Solvent weld all connections The muffler is normally installed at the end of the vent pipe 2 6 OPERATION CHECKS _____ Verify all connections are tight and leak free _____ Insure t...

Страница 6: ...peration Reduce by 10 for High Temperature Operation Reduce by 4 per 1000 feet of altitude Power Consumption 120 VAC XP101 40 49 watts XP151 45 60 watts XP201 45 66 watts XR261 65 105 watts XP Series Inlet Outlet 4 5 OD 4 0 PVC Sched 40 size compatible XR Series Inlet Outlet 5 875 OD Mounting Mount on the duct pipe or with optional mounting bracket Recommended ducting 3 or 4 Schedule 20 40 PVC Pip...

Страница 7: ...ation Reduce by 10 for High Temperature Operation Reduce by 4 per 1000 feet of altitude Power Consumption 120 VAC GP501 70 140 watts GP401 60 110 watts GP301 55 90 watts GP201 40 60 watts Inlet Outlet 3 5 OD 3 0 PVC Sched 40 size compatible Mounting Fan may be mounted on the duct pipe or with integral flanges Weight 12 lbs Size 13H x 12 5 x 12 5 Recommended ducting 3 or 4 Schedule 20 40 PVC Pipe S...

Страница 8: ...donAway 5 YEAR EXTENDEDWARRANTY WITH PROFESSIONAL INSTALLATION RadonAway will extend the Warranty Term of the fan to 5 years from date of manufacture if the Fan is installed in a professionally designed and professionally installed radon system or installed as a replacement fan in a professionally designed and professionally installed radon system Proof of purchase and or proof of professional ins...

Отзывы: