D9412G/D7412G Operation & Installation Guide

43488D

Page 22

©  2002 Radionics

D9412G/D7412G

3.4

Installing the Assembly

1.

Place the assembly over the inside back of the enclosure, aligning the large rectangular openings of the
mounting skirt with the mounting hooks of the enclosure. Slide the assembly down so it hangs on the hooks.
See 

Figure 2.

2.

Remove the tape from the #6x1/4-inch screw in the mounting tab on the assembly. The screw passes through
the mounting tab and into the skirt mounting hole in the enclosure. Tighten the screw to secure the assembly
in the enclosure.

3.

Connect earth ground to the panel before making any other connections. See section

 3.5 Connecting Earth

Ground.

3.5

Connecting Earth Ground

3.5.1

Terminal  

To help prevent damage from electrostatic charges or other transient electrical surges, connect the system to earth
ground at Terminal 10 before making any other connections. A grounding rod or cold water pipe are recommended
earth ground references.

Do not use telephone or electrical ground for the earth ground connection. Use 14-16 AWG wire when making
the connection. Do not connect any other panel terminals to earth ground.

3.5.2

Ground Fault Detect Enable

Ground fault detect capability is available only on firmware
versions 6.10 or higher.

GROUND FAULT is defined as “a circuit impedance to Earth Ground
of approximately 95 kilohms or less.” The panel will detect a ground
fault on Terminals 1-9 and Terminals 11-32 if the Ground Fault
Detect Enable jumper (S4) (see 

Figure 3) is locked (closed) and a

non-zero value is entered in Area 5 Silent Alarm Relay (see the
D9412G/D7412G Program Entry Guide). When the jumper is in the
unlocked (open) position, the panel will not detect ground fault
conditions. If a ground fault condition occurs, the command centers
will display 

SERVC GND FAULT

 and the panel will transmit a 

TROUBLE

REPORT GROUND FAULT AREA

 

 

 

 

 

(Modem IIIa

 format only). In order

for the panel to detect a ground fault condition, the panel must see
the ground fault for at least 30 consecutive seconds. When the panel
recognizes that ground fault condition is corrected, a 

RESTORAL

report is sent. For the restoral condition to be met, the
ground fault must have been corrected for between 5
and 45 consecutive seconds.

The 9000 Series Control/Communicators log and
print a Ground Fault event as a Trouble Point 256.

3.5.3

Locking the Reset Pin

Locking the Reset Pin disables the panel. See 

Figure 4.

The system ignores the command centers and points
while disabled. 

CALL FOR SERVICE

 appears in

command center displays while the pin is locked down.

On-board relays (Terminals 6, 7, and 8) and off-board
relays deactivate when the panel is reset. There is power
at Terminal 8 when the relay is deactivated. Activation
interrupts power at that terminal. The relays remain
deactivated while the Reset Pin is locked in the disable
position.

Installation

Figure 4: Reset Pin

Reset Pin

Disable All Except Battery

Charging And Programming

PERIPHERAL DEVICE CONNECTIONS

RED

POWER +

YELLOW

DATA BUS A

GREEN

DATA BUS B

BLACK

COMMON

32

31

30

29

RESET PIN

LOCKED (CLOSED)

RESET PIN

NORMAL (OPEN)

Figure 3: Ground Fault Detect

GROUND FAULT DETECT

Enabled
Disabled

PHONE
LED

RED

ON WHEN
COMMUNICATING
OFF WHEN IDLE

LOOP START

PHONE MONITOR SELECT

GROUND START

Requires

Relay # D136 in

Ground

Start Socket

GND START

GROUND FAULT
DETECT ENABLE

S4

With S4 closed, panel detects
ground faults.

With S4 open, panel does not
detect ground faults.

Содержание D9412G

Страница 1: ...D9412G D7412G Control Communicators Operation and Installation Guide...

Страница 2: ...D9412G D7412G Operation Installation Guide 43488D Page 2 2002 Radionics D9412G D7412G Notes...

Страница 3: ...Communicator 16 2 4 4 Command Centers 17 2 4 5 Keyswitch 17 2 4 6 Access Control 17 2 4 7 Event Memory 17 2 4 8 Event Log 17 2 4 9 EMI Lightning Transient Protection 18 2 4 10 Programming 18 2 4 11 O...

Страница 4: ...rcuit Protection 29 5 2 Total Available Power 29 5 3 Continuous Power Outputs Terminals 29 5 3 1 Continuous Current Draw 29 5 4 Programmable Power Outputs Terminals 29 5 4 1 Programming 29 5 4 2 Optio...

Страница 5: ...Expansion Loops to POPEX Modules 43 8 3 5 POPIT Sensor Loops 43 8 3 6 POPIT Module Point Assignments 43 8 3 7 Program Record Sheet 43 8 4 D8128D OctoPOPIT Module 44 8 4 1 Description 44 8 4 2 Listing...

Страница 6: ...le 59 11 6 1 1 Connecting the D9133DC 59 11 6 1 2 Used as an External Modem 59 11 6 2 D9133TTL E Network Interface Module 59 11 6 3 Address Settings 59 11 6 4 Supervision 59 12 0 Programmer and Access...

Страница 7: ...el 40 Figure 14b Connecting the D8125 POPEX to the D7412G Panel 41 Figure 15 Program Record Sheet 44 Figure 16a Connecting D8128D OctoPOPITs to the D9412G 47 Figure 16b Connecting D8128D OctoPOPITs to...

Страница 8: ...7 Charging Status and Low Battery LEDs 28 Table 8 Data Expansion Loop Wire Specifications 42 Table 9 D8128D OctoPOPIT Switch Settings for D9412G D7412G 46 Table 10 D8129 OctoRelay Switch Settings 49...

Страница 9: ...s plus the status and battery LEDs 4 Power Supply provides information on the primary and secondary modules and instructions on connecting and programming them 5 Power Outputs provides information on...

Страница 10: ...ourier Text Text that appears like this indicates what may appear on the D5200 Programmer display command center keypad or internal printer CAPITALIZED TEXT Text like this is used to indicate to the u...

Страница 11: ...jack The ringer equivalence number REN is used to determine the number of devices that may be connected to the telephone line Excessive RENs on the telephone line may result in the devices not ringin...

Страница 12: ...D9412G D7412G Operation Installation Guide 43488D Page 12 2002 Radionics D9412G D7412G Introduction Notes...

Страница 13: ...rm the panel by area Each panel can have up to eight areas Each area can have its own account number or areas can be grouped together with a common account number Points of protection are assigned to...

Страница 14: ...put 2 0 A maximum at 10 2 VDC to 13 9 VDC output Output may be steady or one of three pulsed patterns depending on programming See Relays in the D9412G D7412G Program Entry Guide Switched Aux Power 1...

Страница 15: ...2C D192D D268 D269 D279A D442 D448 D449 D720 D720R D720W D928 D1218 D1255 D1255R D1255W Dual Battery Harness Powered Loop Interface Module 12 V 7 Ah Rechargeable Battery Reversing Relay Dual Class A I...

Страница 16: ...control panels can be monitored on the network for their status 2 4 Standard Features 2 4 1 Points The Radionics D9412G Control Communicator panel provides up to 246 points of protection and the D7412...

Страница 17: ...o access doors with up to 396 uniquely identified cards tokens Access can be granted from a Wiegand style access control device card reader connected to the D9210B Access Control Interface Module Acce...

Страница 18: ...nt Manager RAMIV Fire Alarm Verification Programmable Alarm Output Programmable Relay Output using the D8129 OctoRelay Module Opening and Closing Windows Skeds scheduled events 2 4 12 Control Communic...

Страница 19: ...ntrol Communicators for Central Station Local Police Connect Bank Safe and Vault Mercantile Safe and Vault and Grade A Household systems Access Control and Proprietary Department of Defense DOD The D9...

Страница 20: ...D9412G D7412G Operation Installation Guide 43488D Page 20 2002 Radionics D9412G D7412G Overview Notes...

Страница 21: ...tion of the D5200 Programmer or the Remote Account Manager RAM IV 3 2 Enclosure Options Mount the control communicator assembly in any of the Radionics enclosures listed below Refer to the D9412G D741...

Страница 22: ...Entry Guide When the jumper is in the unlocked open position the panel will not detect ground fault conditions If a ground fault condition occurs the command centers will display SERVC GND FAULT and t...

Страница 23: ...iption of these events Always touch Terminal 10 the panel s earth ground connection before beginning work on the panel 3 6 2 Install and Wire Detection Devices Install and wire detection devices and c...

Страница 24: ...must be installed for fire or combined fire burglary systems using verification points Use the D9412G D7412G Program Record Sheet to gather the information needed to fill out the point chart Install...

Страница 25: ...ctors including the transformer wire Route data wiring away from AC and phone wiring Connect the battery and then plug in the transformer Radionics recommends that the battery always be connected firs...

Страница 26: ...START GND START GROUND START 12 11 13 Point 1 Point 2 GROUND START Requires Relay D136 in Ground Start Socket Battery Wires To Batteries To ensure proper spacing secure wires using Tie Wraps or simil...

Страница 27: ...he discharge continues the panel becomes inoperative when the battery voltage drops below 10 2 VDC 4 2 5 Battery Charging Circuit Float Charge The float voltage for the battery charging circuit is 13...

Страница 28: ...ttery is missing shorted or reversed The Charging Status LED is off but the red Low Battery LED is flashing Yellow On Battery float charge is below 13 8 VDC If AC is present the battery is charging Wh...

Страница 29: ...al 32 Power Use this terminal to power SDI Serial Device Interface devices such as command centers the D9131A Parallel Printer Interface Module and the D9210B WiegandTM Control Interface Module Access...

Страница 30: ...ls 6 and 7 to power bells siren drivers piezo fire sounders electronic horns or other devices Programming determines the format of the output and the conditions that activate it One PTC protects Termi...

Страница 31: ...r One self resetting circuit breaker protects Terminals 6 7 and 8 against shorts Verification Reset Relay The default program sets Relay C Terminal 8 as a verification reset relay See Relay Parameters...

Страница 32: ...D9412G D7412G Operation Installation Guide 43488D Page 32 2002 Radionics D9412G D7412G Power Outputs Notes...

Страница 33: ...ure See Figure 8 Install the jack on the street side of the phone switch wired ahead of any PBX equipment Line seizure provides for a temporary interruption of normal phone usage while the communicato...

Страница 34: ...o test the status of the phone line In some instances a given telephone line may be out of service without affecting the voltage on the line The phone line monitor can not recognize this trouble condi...

Страница 35: ...ines The panel monitors both lines If a signal is generated and the panel senses that a line is bad then it will attempt to use the other phone line to send the message If trouble is detected the pane...

Страница 36: ...6 12 5 D928 Status LEDs Four LEDs mounted on the front edge of the D928 Module show the status of AC power for the panel the status of the two phones lines and communication failure See Figure 11 When...

Страница 37: ...across the point input terminal and one of the common terminals The sensor loops must be connected and the 1 k end of line resistor in place Open Loop Greater than 3 7 VDC but less than 5 0 VDC Norma...

Страница 38: ...y Positive Are Inherently Power Limited Requirements For Battery Standby Time May Reduce Allowable Output CAUTION See Manual For Power Requirements Relating to Terminals 6 7 WARNING Multi Battery Inst...

Страница 39: ...BLE report The panel sees all points on the shorted expansion loop as shorted and responds according to point programming except for fire points The fire points will respond locally as a trouble condi...

Страница 40: ...D9412G D7412G Operation Installation Guide 43488D Page 40 2002 Radionics D9412G D7412G Off board Points Figure 14a Connecting the D8125 POPEX to the D9412G Panel...

Страница 41: ...D9412G D7412G Operation Installation Guide 2002 Radionics Page 41 43488D D9412G D7412G Figure 14b Connecting the D8125 POPEX to the D7412G Panel Off board Points...

Страница 42: ...of the D8125 POPEX Module to ZONEX OUT 1 Terminal 28 4 Connect the AUX terminal of the D8125 to Terminal 24 on the D9412G or to Terminal 3 on the D7412G For Point numbers from 129 to 247 D9412G only 1...

Страница 43: ...grounded circuit conditions on their sensor loops They transmit the condition of their loops to the panel A ground on the sensor loop reports as a general system ground fault condition see Ground Fau...

Страница 44: ...r Outputs to be sure to provide enough power for the OctoPOPITs and other powered devices that will be connected to the system 8 4 2 Listing The D8128D OctoPOPIT Module is UL listed for Local or Polic...

Страница 45: ...ules to the D9412G D7412G Both OctoPOPIT and POPEX Modules can be connected to the same Point Bus terminals The modules wire in parallel Remember never assign the same point number to more than one po...

Страница 46: ...PIT two OctoPOPIT sensor loops or two POPITs do not function properly 8 4 7 Address Assignment Switches Switches 1 2 3 and 4 assign the OctoPOPIT sensor loops to point numbers on the panel Table 9 sho...

Страница 47: ...10 12 13 14 15 16 P1 COMP2 P3 COMP4 P5 COMP6 P7 COMP8 AUX OUT GND IN TO CONTROL 1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 P1 COMP2 P3 COMP4 P5 COMP6 P7 COM P8 AUX OUT GND IN TO CONTROL 1 2 3 4 5 6 7 8 9 10...

Страница 48: ...lation Guide 43488D Page 48 2002 Radionics D9412G D7412G Off board Points Figure 16b Connecting D8128D OctoPOPITs to the D7412G TO CONTROL 1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 P1 COMP2 P3 COMP4 P5 COMP...

Страница 49: ...e normally closed and common terminals 9 1 3 Installation Set the switches on the OctoRelay before installing it in the enclosure See section 9 1 1 Configuring the D8129 OctoRelay Install the OctoRela...

Страница 50: ...N F P A Sty le 3 5 Si gna l ing Li ne Circuits 32 31 30 29 28 27 PROG CONN Point 8 G ND FA ULT D e te c t E N A B L E D I S A B L E ZONEX OUT2 26 25 ZONEX IN2 ZONEX POWE R 24 ZONEX COMM ON 23 21 22 On...

Страница 51: ...pen and common terminals When the output is not activated there is continuity between the normally closed and common terminals Relay outputs may activate while programming the panel You may wish to di...

Страница 52: ...R 53 EARTH GRO COMMON BATTERY N Maximum Charging Current 1 4 Amps BATTERY POSITIVE ONLY RELAY A RELAY B RELAY C AUX PO 1 2 3 4 5 6 7 8 9 10 CLASS 2 TRANS 16 5 VAC 40 VAC Part No D1640 Internally Fuse...

Страница 53: ...enter with functional keys optimized for local fire alarm control The D1257 is a text display command center for fire annunciation The D1260 boasts an easy to read 4 line by 20 character LCD display w...

Страница 54: ...igure 19 shows the D8132 powering command centers in a stand alone configuration For UL certificated accounts use a UL listed power supply The D8132 is not UL listed as a stand alone power supply Cont...

Страница 55: ...10 4 4 Keyswitch Operation Maintained Contact If the point to which the keyswitch is connected is programmed for a maintained contact an open on the arming circuit arms the area All faulted points ar...

Страница 56: ...D9412G D7412G Operation Installation Guide 43488D Page 56 2002 Radionics D9412G D7412G Arming Devices Notes...

Страница 57: ...equires a separate D9131A Parallel Printer Interface Module The D9131A connects to the printer using a standard parallel printer cable 11 3 1 Switch Settings Switches on the D9131A assign a unique add...

Страница 58: ...mation software A D9133 Serial Interface Module is required for this application 11 5 1 D9133 Serial Interface Module The Radionics D9133 Serial Interface Module is a four wire powered SDI device prov...

Страница 59: ...the Locked or Unlocked position Note Locking the Reset Pin when programming the panel improves upload download time 11 6 1 2 Used as an External Modem The D9133DC can also be used as an external modem...

Страница 60: ...D9412G D7412G Operation Installation Guide 43488D Page 60 2002 Radionics D9412G D7412G SDI Devices Notes...

Страница 61: ...e programmer is disconnected The prompt in Routing must be programmed YES for this report to be sent 12 2 Accessory Connector Use the Accessory Connector to connect the panel to the D928 Dual Phone Li...

Страница 62: ...D9412G D7412G Operation Installation Guide 43488D Page 62 2002 Radionics D9412G D7412G Programmer and Accessory Connections Notes...

Страница 63: ...D9412G D7412G Operation Installation Guide 2002 Radionics Page 63 43488D D9412G D7412G FACEPLATES 13 0 Faceplates 13 1 D9412G Faceplate Figure 23a D9412G Faceplate...

Страница 64: ...D9412G D7412G Operation Installation Guide 43488D Page 64 2002 Radionics D9412G D7412G 13 2 D7412G Faceplate FACEPLATES Figure 23b D7412G Faceplate...

Страница 65: ...allation Guide 2002 Radionics Page 65 43488D D9412G D7412G Appendix A System Wiring Diagrams Issue A Figure 24a D9412G System Wiring Diagram 1 of 3 Appendix A System Wiring Diagrams Issue A A 1 D9412G...

Страница 66: ...D7412G Operation Installation Guide 43488D Page 66 2002 Radionics D9412G D7412G Appendix A System Wiring Diagrams Issue A A 2 D9412G Control Communicator 2 of 3 Figure 24b D9412G System Wiring Diagram...

Страница 67: ...D7412G Operation Installation Guide 2002 Radionics Page 67 43488D D9412G D7412G Appendix A System Wiring Diagrams Issue A Figure 24c D9412G System Wiring Diagram 3 of 3 A 3 D9412G Control Communicator...

Страница 68: ...D7412G Operation Installation Guide 43488D Page 68 2002 Radionics D9412G D7412G Appendix A System Wiring Diagrams Issue A Figure 25a D7412G System Wiring Diagram 1 of 3 A 4 D7412G Control Communicator...

Страница 69: ...D7412G Operation Installation Guide 2002 Radionics Page 69 43488D D9412G D7412G Appendix A System Wiring Diagrams Issue A Figure 25b D7412G System Wiring Diagram 2 of 3 A 5 D7412G Control Communicator...

Страница 70: ...D7412G Operation Installation Guide 43488D Page 70 2002 Radionics D9412G D7412G Appendix A System Wiring Diagrams Issue A Figure 25c D7412G System Wiring Diagram 3 of 3 A 6 D7412G Control Communicator...

Страница 71: ...1 3 6 016 0 1 2 3 056 0 2 096 1 3 017 0 1 2 4 5 6 057 0 3 4 5 6 097 1 4 5 6 018 0 1 2 4 5 058 0 3 4 5 098 1 4 5 019 0 1 2 4 6 059 0 3 4 6 099 1 4 6 020 0 1 2 4 060 0 3 4 100 1 4 021 0 1 2 5 6 061 0 3...

Страница 72: ...1 2 4 6 179 0 3 4 6 219 1 4 6 140 0 1 2 4 180 0 3 4 220 1 4 141 0 1 2 5 6 181 0 3 5 6 221 1 5 6 142 0 1 2 5 182 0 3 5 222 1 5 143 0 1 2 6 183 0 3 6 223 1 6 144 0 1 2 184 0 3 224 1 145 0 1 3 4 5 6 185...

Страница 73: ...cting to the D9412G 40 Installing 42 D8125 POPIT Modules 39 D8127 POPIT Modules 39 D8128D OctoPOPIT 44 Connecting to the D7412G 48 Connecting to the D9412G 47 D8129 OctoRelay 49 D9127 POPIT Modules 39...

Страница 74: ...s Terminals 29 Switched Auxiliary 29 Total Available Power 29 ZONEX 29 Power Supply 25 Primary Power Terminals 25 Printer 57 Programmer 24 Connecting 61 Programmer Connector 61 Programming Standard Fe...

Страница 75: ...D9412G D7412G Operation Installation Guide 2002 Radionics Page 75 43488D D9412G D7412G Operation Installation Guide Notes...

Страница 76: ...2002 Radionics a division of Detection Systems Inc 43488D 08 02 PO Box 80012 Salinas CA 93912 0012 USA Operation D9412G D7412G Customer Service 800 538 5807 Installation Guide Page 76 of 76...

Отзывы: