D9210B Operation & Installation Manual
© 1997 Radionics
Page 22
Door Release Application
The D9210B can be used for door release functions. When used in this
configuration, the strike relay contacts must be supervised. This can be
accomplished with the use of an end-of-line relay commonly used for smoke
detectors. Connecting the D9210B for this application is shown in Figure 6.
Program Point Index in the POINTS handler as Supervisory with Point
Response as “A” (Supervisory on Open and Trouble on Short.
The power supply, end-of-line relay, and the D9210B must be in the same
enclosure or adjacent enclosures connected via conduit not longer than 20 feet.
NOTE: When using the D9210BC, you must use the D8004 Transformer
Enclosure for the power supply transformer.
1
PWR +
7
SDIB
6
SDIA
5
COM
8
T +
10
ZN +
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
12
COM
11
RTE
D9210B
(-)
DOOR A
DOOR A
(+)
-
+
+
-
LO
O
P
ON
0
6
5
4
3
2
1
DA
TA
+
-
Figure 6. D9210B Door Release Application Connections