background image

© 2003 Radionics, a division of Detection Systems, Inc.
PO Box 80012, Salinas, CA 93912-0012, USA
Customer Service: (800) 538-5807; Technical Support: (888) 886-6189

50084D
Installation Guide

04/03

D6680

Page 4 of 4

3.4.1

Installation Instructions

 

Remove AC power and lock out the circuit breakers prior to installation.

1.  Mount the gang box to the

wall or supporting
structure.

2.  Insert a gang box partition

into the gang box. The
partition will divide the
gang box into two
sections. The large
section contains the high
voltage wiring; the small
section contains the low
voltage wiring.

3.  Punch out a conduit

knockout in the high
voltage side of the gang
box. Bring the 110 VAC
wiring through the
knockout hole and into the
gang box as required by
the local Authority Having
Jurisdiction, NFPA and the
NEC.

Gang Box

Cover Plate

Transformer

Duplex Outlet

Low Voltage

Section

Cover

Gang Box

Partition

Figure 7: D8004 Installation

4.  Connect the isolated 110 VAC wiring to the duplex outlet.

5.  Mount the duplex outlet to the cover plate using the #6 machine screws, nuts and lockwashers provided.

Mount the cover plate to the gang box with the #10 screws provided with the gang box.

6.  Energize the power to the circuit(s) and, using a voltmeter, test the duplex outlet for proper voltage.

7.  Punch out a conduit knockout in the low voltage side of the gang box. Bring the low voltage wiring through

the knockout hole and into the gang box as required by the local Authority Having Jurisdiction, NFPA and
the NEC.

8.  Connect the low voltage wiring to the transformer.

9.  Plug the transformer into the bottom outlet of the duplex outlet. Secure the transformer to the duplex outlet

using the screw provided.

10.  Attach the cover to the cover plate with the four #6 self-tapping screws provided.

4.0

Programming

Refer to the 

D6600 NetCom System Guide (P/N: 46542) for information on how to program the D6680.

5.0

Additional UL Requirements

The D6680 must be installed in the same room as the D6600 Central Station Receiver and within
50 ft. (15.2 m) of the D6600 Central Station Receiver.

5.1

UL 864 Fire System Installations

The D6680 must be installed in accordance with NFPA 72.

5.1.1

Required Accessories

 

AE1 or AE2 Enclosure

 

D8004 Transformer Housing

Содержание D6680

Страница 1: ... not attempt to connect both Ethernet ports simultaneously The D6680 does not have routing capabilities The D6680 has the following items on the Network Interface end of the unit 1 10BASE T Ethernet Port refer to Figure 2 2 10BASE FL Ethernet Port Transmit Not Used 3 10BASE FL Ethernet Port Receive Not Used 4 Network LEDs 5 Power Plug 1 1 1 RJ 45 10BASE T Ethernet Port Figure 2 RJ 45 Ethernet Jack...

Страница 2: ...port Diagnostic LEDs Network Transmit Network Receive Good Link Collisions Channel 1 Status Channel 2 Status Diagnostic Compatibility Ethernet Version 2 0 IEEE 802 3 D6600 Power Requirements 9 to 30 VDC or 9 to 25 VAC External adapter included Power Consumption 3 W AC Current Required UPS Standby Current 35 mA Power Input AC nominal operating range 120 or 240 VAC AC maximum operating range 100 to ...

Страница 3: ...nstalling the D6680 in the AE1 or AE2 enclosure the correct mounting holes must be found on the back wall of the enclosure Only these holes line up correctly to allow the D6680 to be secured with two screws Once the holes are found proceed to mount the D6680 1 Place the D6680 against the back wall of the enclosure 2 Line up the side mounting holes on the D6680 with the enclosure mounting holes ind...

Страница 4: ... cover plate using the 6 machine screws nuts and lockwashers provided Mount the cover plate to the gang box with the 10 screws provided with the gang box 6 Energize the power to the circuit s and using a voltmeter test the duplex outlet for proper voltage 7 Punch out a conduit knockout in the low voltage side of the gang box Bring the low voltage wiring through the knockout hole and into the gang ...

Отзывы: