D6500 Internally Generated Messages

Signal

D6500 Internal/External Printer

D6000 Mode

D6500 Mode

SIA Mode

Printer Test 

dd/dd tt:tt L8 ACCT  888 [TEST]   ZN   8 hq8888[8t

h1rr8sssssss888s[sss8t 

<header>[NVX]

Busy Seconds dd/dd tt:tt ql BUSY SECONDS bbb% 

RCVR rr

hqlbbbB%t

h1rrlsssssssbbbsBsssst 

<header>[NYBbbb]

Service Req'd

dd/dd tt:tt ql SERVICE REQUIRED  

RCVR rr

hq8888A7t

h1rrlsssssssssssXsss1t 

<header>[NYX]

Set Time

dd/dd tt:tt    TIME SET          

RCVR rr

hq8888A4t 

h1rrssssssssssssXsss2t 

<header>[NJT]

+5V Troubled

dd/dd tt:tt    +5 TROUBLED       

RCVR rr

hq8888T9t

h1rrssssssssssssXsss3t 

<header>[NYP]

+5V Restored

dd/dd tt:tt    +5 RESTORED       

RCVR rr

hq8888R9t

h1rrssssssssssssXsss4t 

<header>[NYQ]

+12V Trouble

dd/dd tt:tt    +12 TROUBLED      

RCVR rr

hq8888T9t

h1rrssssssssssssXsss3t 

<header>[NYP]

+12V Restoral dd/dd tt:tt    +12 RESTORED      

RCVR rr

hq8888R9t

h1rrssssssssssssXsss4t 

<header>[NYQ]

-12V Trouble 

dd/dd tt:tt    -12 TROUBLED      

RCVR rr 

hq8888T9t

h1rrssssssssssssXsss3t 

<header>[NYP]

-12V Restoral  dd/dd tt:tt    -12 RESTORED      

RCVR rr 

hq8888R9t

h1rrssssssssssssXsss4t 

<header>[NYQ]

Phone Troubled

dd/dd tt:tt ql PHONE TROUBLED    

RCVR rr

hqlsssTst

h1rrlsssssssssssXsss5t 

<header>[NLT]

Phone Restored

dd/dd tt:tt ql PHONE RESTORED    

RCVR rr

hqlsssRst

h1rrlsssssssssssXsss6t 

<header>[NLR]

Card Troubled  dd/dd tt:tt ql CARD TROUBLED     

RCVR rr

hqlsssTst

h1rrlsssssssssssXsss7t 

<header>[NYD]

Card Restored dd/dd tt:tt ql CARD RESTORED     

RCVR rr

hqlsssRst

h1rrlsssssssssssXsss8t 

<header>[NYE]

Battery Missing 

dd/dd tt:tt    BATTERY MISSING   

RCVR rr

hq8888T9t

h1rrssssssssssssXsss9t 

<header>[NYM]

Battery Presentdd/dd tt:tt    BATTERY PRESENT   

RCVR rr

hq8888R9t

h1rrssssssssssssXss10t

<header>[NYR]

Low Battery  

dd/dd tt:tt    LOW BATTERY       

RCVR rr

hq8888T9t

h1rrssssssssssssXss11t 

<header>[NYT]

Battery Restore 

dd/dd tt:tt    BATTERY RESTORED  

RCVR rr

hq8888R9t

h1rrssssssssssssXss12t 

<header>[NYR]

AC Troubled

dd/dd tt:tt    AC TROUBLED       

RCVR rr

hqssssPst 

h1rrssssssssssssXss13t 

<header>[NAT]

AC Restored

 

dd/dd tt:tt    AC RESTORED       RCVR rr hqssssEst

h1rrssssssssssssXss14t 

<header>[NAR]

Paper In

dd/dd tt:tt    PAPER IN          

RCVR rr

hq8888R5t

h1rrssssssssssssXss15t 

<header>[NVI]

Paper Out

dd/dd tt:tt    PAPER OUT         

RCVR rr 

hq8888T5t

h1rrssssssssssssXss16t 

<header>[NVO]

Programmer In 

dd/dd tt:tt    PROGRAM MODE IN   

RCVR rr

hq8888T4t

h1rrssssssssssssXss17t 

<header>[NLB]

Programmer Out

dd/dd tt:tt    PROGRAM MODE OUT  

RCVR rr

hq8888R4t

h1rrssssssssssssXss18t 

<header>[NLD]

Содержание D6500

Страница 1: ...74 05313 000 G 10 16 97 1988 1997 Radionics Inc D6500 Security Receiver Computer Interface Installation Manual...

Страница 2: ...dionics Inc assumes no responsibility for inaccuracies and reserves the right to modify and revise this manual without notice It is our goal at Radionics to always supply accurate and reliable documen...

Страница 3: ...s On 8 Logging Only Printer Computer 8 4 THE COMPUTER RS 232 PORT D6515 MPU TERMINATOR 8 4 1 D6500 MODE MESSAGES 8 4 1 1 Message Type 1 Standard Digital Message 9 4 1 2 Message Type 3 Text Message 9 4...

Страница 4: ...er Configuration 61 Messages 61 D6500 COMPUTER INTERFACE INSTALLATION MANUAL SUPPLEMENT 62 ADEMCO CONTACT ID 62 ADEMCO HIGH SPEED 62 ADEMCO 4 1 EXPRESS 63 ADEMCO 4 2 EXPRESS 63 FBI SUPER FAST 64 ACRON...

Страница 5: ...ed with the 6500 Product Handler program The D6500 will respond in different ways to the received messages depending on how the available options are selected in the D6500 MPU program The messages and...

Страница 6: ...g any jumpers make sure the D6500 Receiver is powered down as described in the D6500 Security Receiver Operation and Installation Manual The D6515 MPU Terminator Card can be accessed from the back of...

Страница 7: ...e next message one to silence the buzzer and one to clear the display The buzzer re starts about 45 seconds after the SLNC button is pressed once if the display has not been cleared with a second pres...

Страница 8: ...should be Yes If the printer is not supervised by the receiver there will be no indication at the computer if printer problems occur XON XOFF External Printer XON XOFF should be Yes to receive signals...

Страница 9: ...Yes or No is normally set to Yes All Radionics control communicators using the Modem IIe IIIA2 format differentiate between Fire Restoral after Alarm and Fire Restoral after Trouble Missing Supervisor...

Страница 10: ...ket separator in SIA output mode when messages with event modifiers are sent to automation Usually set to No Sub Subscriber This is a programmable Modem Format only item that determines whether the sp...

Страница 11: ...SLNC button once more to advance to the next message Use caution when pressing the SLNC button because it will clear incoming messages if pressed too many times Supervised Printer Always On When the c...

Страница 12: ...s Ack 4 The Computer RS 232 Port D6515 MPU Terminator Depending on how item Output Format is set there are three ways the D6500 can send information to the COMP RS 232 Port on the MPU Terminator Card...

Страница 13: ...leading ASCII spaces 16 through 17 Event Code This is a 2 byte ASCII TEXT field It defines the type of signal that was received and interpreted by the 6500 Receiver See Figure 5 for a list of valid co...

Страница 14: ...acter of acct ASCII Ninth character of message text 15 Fourth character of acct ASCII Tenth character of message text 16 First character of event code ASCII Eleventh character of message text 17 Secon...

Страница 15: ...uded if applicable to the event SIA Mode labels literal ASCII letters that are output to the automation system are indicated in bold in the Data field account number New label area label area id label...

Страница 16: ...erface Standard are not supported a account number digit 0 F or area number digit 1 8 ai Sked field label c code identification digit d serial device interface digit h hour digit phone number phone li...

Страница 17: ...able header character second line hour phone line or phone index i subzone digit or MASTER combo ID digit 0 F second line user ID or operator ID j Listen In time digit k second line SKED ID l line num...

Страница 18: ...aFRppp 1 10 after Alarm ACCT aaaa AREA a POINT ppp area not reported Fire Restore dd dd tt tt ql ACCT aaaa FIRE RESTORAL h1rrlssssssaaaaHsspppt header aaaa NriaFRppp 1 10 after Trouble Missing ACCT aa...

Страница 19: ...1 10 ACCT aaaa AREA a POINT ppp area not reported Missing Alarm dd dd tt tt ql ACCT aaaa MISSING ALARM h1rrlssssssaaaasMspppt header aaaa NriaUZppp 1 10 ACCT aaaa AREA a POINT ppp area not reported Mi...

Страница 20: ...diiiOJ 1 ACCT aaaa AREA a ID iii area not reported Late Opening By Area dd dd tt tt ql ACCT aaaa LATE TO OPEN h1rrlssssssaaaasOsssst header aaaa NriaOJ 1 D7112 ID not reported ACCT aaaa AREA a area no...

Страница 21: ...asCsiiit header aaaa NidiiiCJ 1 D7112 ACCT aaaa ID iii area not reported Closing Late by Account dd dd tt tt ql ACCT aaaa CLOSING LATE h1rrlssssssaaaasCsssst header aaaa NCJ 1 D7112 ID not reported Cl...

Страница 22: ...Perimeter Delay dd dd tt tt ql ACCT aaaa PERM DLAY ARMED h1rrlssssssaaaasCsssst header aaaa NriaNL 1 D7112 by Area ACCT aaaa AREA a ID not reported Was Force Armed dd dd tt tt ql ACCT aaaa WAS FORCE...

Страница 23: ...d tt tt ql ACCT aaaa F CLOSE LATE h1rrlssssssaaaasCsiiit header aaaa NidiiiCF 1 D7112 by Account ACCT aaaa ID iii Force Close Late dd dd tt tt ql ACCT aaaa F CLOSE LATE h1rrlssssssaaaasCsssst header a...

Страница 24: ...lssssssaaaaSTsssst header aaaa OET 5 D7112 Since Last Call Fail to Call RAM ACCT aaaa BAD CALL TO RAM h1rrlssssssaaaaSTsssst header aaaa ORA 5 Since Last Call User Tamper ACCT aaaa USER TAMPER h1rrlss...

Страница 25: ...y Area ACCT aaaa AREA a Status Perimeter dd dd tt tt ql ACCT aaaa S PERIM DELAY h1rrlssssssaaaaSCsssst header aaaa OriaNL Delay by Area ACCT aaaa AREA a Status Transmitter dd dd tt tt ql ACCT aaaa S R...

Страница 26: ...t header aaaa NriaXWppp 1 6 D7112 ID not reported ACCT aaaa AREA a POINT ppp area not reported Sensor Reset dd dd tt tt ql ACCT aaaa SENSOR RESET h1rrlssssssaaaasNsD27t header aaaa Nria idiiiXIrrr 1 7...

Страница 27: ...e dd dd tt tt ql ACCT aaaa USR CODE CHANGE h1rrlssssssaaaasNsD04t header aaaa NidiiiJVccc D9112 Changed ACCT aaaa CODE ID ccc ID iii User Code dd dd tt tt ql ACCT aaaa USR CODE CHANGE h1rrlssssssaaaas...

Страница 28: ...a NpidddLU D9112 ACCT aaaa SDI ddd Valid Remote Access dd dd tt tt ql ACCT aaaa RAM ACCESS OK h1rrlssssssaaaasRsssFt header aaaa Nph5RS D9112 ACCT aaaa PHONE 5 phone not reported Valid Remote Access d...

Страница 29: ...aaasTsssDt header aaaa NpidddET ACCT aaaa SDI ddd SDI Restoral dd dd tt tt ql ACCT aaaa SDI RESTORAL h1rrlssssssaaaasRsssDt header aaaa NpidddER ACCT aaaa SDI ddd Point Bus Fail dd dd tt tt ql ACCT aa...

Страница 30: ...header aaaa NriaTAppp 1 D7112 Tamper Trouble ACCT aaaa AREA a RF POINT ppp area not reported Transmitter dd dd tt tt ql ACCT aaaa TAMPER RESTORAL h1rrlssssssaaaasRspppt header aaaa NriaTRppp 1 D7112...

Страница 31: ...NBTF D9112 Fire Walk End dd dd tt tt ql ACCT aaa RESTORAL ZN F h1rrlssssssaaaasRsssFt header aaaa NURF D9112 D9112B D7112 Alarm Messages BFSK Alarm dd dd tt tt ql ACCT aaa ALARM ZN z h1rrlssssssaaaas...

Страница 32: ...PENING ZN i h1rrlssssssaaaasOsssit header aaaa NOPi 2 9 Opening By Account dd dd tt tt ql ACCT aaa OPENING REPORT h1rrlssssssaaaasOsssst header aaaa NOP 2 9 D7112 ID not reported Opening By Area dd dd...

Страница 33: ...id Closing by Account dd dd tt tt ql ACCT aaa CLOSING REPORT h1rrlssssssaaaasCsssst header aaaa NCL 2 D7112 ID not reported Closing by Area dd dd tt tt ql ACCT aaa CLOSING ZN z h1rrlssssssaaaasCssszt...

Страница 34: ...tt tt ql ACCT aaa TROUBLE ZN z h1rrlssssssaaaaSTssszt header aaaa OBTz 9 D9112 Status Open by Area dd dd tt tt ql ACCT aaa STATUS REPORT h1rrlssssssaaaasSsssst header aaaa NYY dd dd tt tt ql ACCT aaa...

Страница 35: ...h1rrlssssssaaaasTsssBt header aaaa NBTB 2 Phone Line 2 Fail dd dd tt tt ql ACCT aaa TROUBLE ZN C h1rrlssssssaaaasTsssCt header aaaa NBTC 2 Phone Line 1 Restoral dd dd tt tt ql ACCT aaa RESTORAL ZN B h...

Страница 36: ...a NUR9 Remote Reset dd dd tt tt ql ACCT aaa RESTORAL ZN 9 h1rrlssssssaaaasRsss9t header aaaa NUR9 D9112 Re Boot dd dd tt tt ql ACCT aaa RESTORAL ZN 9 h1rrlssssssaaaasRsss9t header aaaa NUR9 2 D9112 Tr...

Страница 37: ...ql ACCT aaaa TROUBLE ZN z hqlaaaTzt h1rrlssssssaaaasTssszt header aaaa NBTz Trouble 100 816 dd dd tt tt ql ACCT aaaa TROUBLE ZN zyy hqlaaaTzt h1rrlssssssaaaasTszyyt header aaaa NBTzyy Missing Tbl 101...

Страница 38: ...Cst h1rrlssssssaaaaSCsssst header aaaa OCL Status Rpt Closing dd dd tt tt ql ACCT aaaa CLOSING ID i hqlaaaCit h1rrlssssssaaaaSCsssit header aaaa OCLi Cancel not exp dd dd tt tt ql ACCT aaaa CANCEL REP...

Страница 39: ...Phone Troubled dd dd tt tt ql PHONE TROUBLED RCVR rr hqlsssTst h1rrlsssssssssssXsss5t header NLT Phone Restored dd dd tt tt ql PHONE RESTORED RCVR rr hqlsssRst h1rrlsssssssssssXsss6t header NLR Card...

Страница 40: ...ALID REPORT hq8888A2t h1rrlsssssssssssXss26t header aaaa NYN Variable Text dd dd tt tt ql text as received RCVR rr hq8888A3t h3rrltext as receivedt header Atext as rcvd Pulse Error dd dd tt tt ql PULS...

Страница 41: ...ROSS POINT ACCT aaaa POINT ppp Alarm Exit Error dd dd tt tt ql ACCT aaaa ALARM REPORT h1rrlssssssaaaasAspppt header aaaa NidiiiEAppp Area Not Reported ACCT aaaa EXIT ERROR Alarm with Recent Closing dd...

Страница 42: ...ondition ACCT aaaa UPLINK Fire Alarm dd dd tt tt ql ACCT aaaa FIRE ALARM h1rrlssssssaaaasFspppt header aaaa NFAppp Area Not Reported ACCT aaaa POINT ppp Fire Alarm Crossed Point dd dd tt tt ql ACCT aa...

Страница 43: ...ppt header aaaa NBRppp Area Not Reported ACCT aaaa POINT ppp RF Battery Restore dd dd tt tt ql ACCT aaaa RF BATT RESTORE h1rrlssssssaaaasRspppt header aaaa NXRppp Area Not Reported ACCT aaaa POINT ppp...

Страница 44: ...ERVICE END h1rrlssssssaaaasRsssFt header aaaa NTE Swinger Bypass dd dd tt tt ql ACCT aaaa SWINGER BYPASS h1rrlssssssaaaasNspppt header aaaa NUBppp Area and ID Not Reported ACCT aaaa POINT ppp Test Fai...

Страница 45: ...ACCT aaaa ALL PTS TESTED h1rrlssssssaaaasRsssFt header aaaa NTC Area Watch dd dd tt tt ql ACCT aaaa AREA WATCH h1rrlssssssaaaasEsssat header aaaa Nria idiiiTW ACCT aaaa AREA a ID iii Battery Low dd d...

Страница 46: ...rammer ACCT aaaa BY PROGRAMMER header aaaa Npiddd ssxDAiii ACCT aaaa CRD iii x SDI ddd Card Assigned dd dd tt tt ql ACCT aaaa CARD ASSIGNED h1rrlssssssaaaasNsD30t header aaaa NDAiii or By Remote ACCT...

Страница 47: ...RESTORAL h1rrlssssssaaaasNsB01t header aaaa NrggYK SDI Device not reported ACCT aaaa RG g Create Status Report dd dd tt tt ql ACCT aaaa STATUS REPORT h1rrlssssssaaaaSsssst header aaaa NYY Date Changed...

Страница 48: ...aaaa REQUEST TO EXIT h1rrlssssssaaaaADspppt header aaaa NriaDKppp Interlock Deny ACCT aaaa DENIED INTERLOCK ACCT aaaa AREA a POINT ppp Door Request REX Denied dd dd tt tt ql ACCT aaaa REQUEST TO EXIT...

Страница 49: ...a AUTOMATIC ACCT aaaa AREA a POINT ppp Door Unlocked dd dd tt tt ql ACCT aaaa DOOR UNLOCKED h1rrlssssssaaaaAUspppt header aaaa Nria idiiiDOppp By User ACCT aaaa BY USER ACCT aaaa AREA a ID iii POINT p...

Страница 50: ...ssssaaaasNsD34t header aaaa NpidddYX SDI Device Incorrect Response ACCT aaaa INCORRECT RESPONSE ACCT aaaa SDI ddd Fail To Execute dd dd tt tt ql ACCT aaaa FAIL TO EXECUTE h1rrlssssssaaaasNsD34t header...

Страница 51: ...a AREA a ID iii Forced Close Late by Area dd dd tt tt ql ACCT aaaa FORC CLOSE LATE h1rrlssssssaaaasCsiiit header aaaa Nria idiiiCF ACCT aaaa AREA a ID iii Forced Close Perimeter dd dd tt tt ql ACCT aa...

Страница 52: ...1rrlssssssaaaaADspppt header aaaa Nria idiiiDZppp or Door Secured ACCT aaaa AREA a CRD iii x POINT ppp header aaaa Nria idiii ssxDZppp No Entry dd dd tt tt ql ACCT aaaa NO ENTRY INTRLK h1rrlssssssaaaa...

Страница 53: ...aaasTsD15t header aaaa NYF Parameter Checksum Fail dd dd tt tt ql ACCT aaaa PARMS BAD CKSUM h1rrlssssssaaaasTspppt header aaaa NpidddYFppp SDI Device and Point reported ACCT aaaa POINT ppp SDI ddd Per...

Страница 54: ...h1rrlssssssaaaasOspppt header aaaa NriaOZppp ACCT aaaa AREA a POINT ppp Point Closing dd dd tt tt ql ACCT aaaa POINT CLOSING h1rrlssssssaaaasCspppt header aaaa NriaCZppp ACCT aaaa AREA a POINT ppp Poi...

Страница 55: ...T h1rrlssssssaaaasNsD18t header aaaa NidiiiROrrr by USER ACCT aaaa BY USER ACCT aaaa ID iii RELAY rrr Relay Set dd dd tt tt ql ACCT aaaa RELAY SET h1rrlssssssaaaasNsD21t header aaaa NpidddRCrrr by Pro...

Страница 56: ...ql ACCT aaaa SDI RESTORAL h1rrlssssssaaaasRspppt header aaaa NpidddERppp Point reported ACCT aaaa POINT ppp SDI ddd Sensor Reset dd dd tt tt ql ACCT aaaa SENSOR RESET h1rrlssssssaaaasNsD27t header aaa...

Страница 57: ...S FIRE TROUBLE h1rrlssssssaaaaSGspppt header aaaa OriaFTppp ACCT aaaa AREA a POINT ppp Status Missing Alarm dd dd tt tt ql ACCT aaaa S MISSING ALARM h1rrlssssssaaaaSZspppt header aaaa OriaUZppp ACCT...

Страница 58: ...sssaaaaSPsssst header aaaa OYC ACCT aaaa AC FAILURE h1rrlssssssaaaaSPsssst header aaaa OAT ACCT aaaa BATTERY MISSING h1rrlssssssaaaaSTsssst header aaaa OYM ACCT aaaa BATTERY LOW h1rrlssssssaaaaSTsssst...

Страница 59: ...aaa Nria idiiiPA ACCT aaaa AREA a ID iii User Code Added dd dd tt tt ql ACCT aaaa USER CODE ADDED h1rrlssssssaaaasNsD38t header aaaa NidiiiJYccc ACCT aaaa CODE ID ccc ID iii User Code Changed dd dd tt...

Страница 60: ...56 1988 1997 Radionics Inc Signal Internal External Printer 6500 Output Mode SIA Output Mode Watchdog Reset dd dd tt tt ql ACCT aaaa WATCHDOG RESET h1rrlssssssaaaasNsD09t header aaaa NYW Watchdog Res...

Страница 61: ...69 F01 F08 153 168 217 232 70 249 000 169 184 317 332 185 200 417 432 201 216 517 532 217 232 617 632 233 247 717 731 2 These messages are also capable of being transmitted by a D7112 via Modem II 3...

Страница 62: ...OINT in the second line Example dd dd tt tt ql ACCT aaaa FIRE ALARM ACCT aaaa AREA a RF POINT ppp 4 5 Input Command Processing Input devices such as automation systems can send the commands described...

Страница 63: ...as automation systems can cause the D6500 to generate a Link Test message The Link Test message is only generated when the D6500 has received a request from the input device such as an automation syst...

Страница 64: ...sssssssssss sssst 1 Header Character h Optional Check with the computer automation software for compatibility 2 Message Type ASCII 1 Message Type 1 3 through 4 Receiver Number 5 Line Card Number Line...

Страница 65: ...ary J3 D6555 Automation Port Pin Configuration J3 PIN 2 PIN 3 PIN 5 PIN 6 PIN 7 PIN 20 Data In Data Out CTS Out DSR Out Signal Ground DTR In M S K R P N L J D H B G F E C A J3 D6555 Automation Port Pi...

Страница 66: ...Q 1 print E O for new Event or Opening If Q 3 print R C for Restore or Closing If Q 6 print OLD Definition of automation output codes h Header a Contact ID protocol identifier rr Receiver number l Li...

Страница 67: ...Express format Lxx Line number Definition of automation output codes h Header b Ademco 4 1 Express protocol identifier rr Receiver number l Line Card number s Space aaaa Account code X Event code A as...

Страница 68: ...er Fast protocol identifier rr Receiver number l Line Card number s Space aaaa Account code T Zone type ZZ Zone number E Event type t Trailer Zone Event Type Code Table Code Number Zone Event Type 1 F...

Страница 69: ...Line Card number s Space aaaa Account code C Channels 1 8 t Trailer DSC Sur Gard 4 3 and 4 3 with Checksum Receiver sends to computer D6500 Mode hdrrlssssssaaaasEsXYYt SIA Mode LF CRC d seq rec line a...

Страница 70: ...m A 3 Alarm A 4 Close C 5 Open O 6 Alarm A 7 Alarm A 8 Alarm A 9 Restore R 0 Trouble T B CloseGrp C C OpenGrp O D Bypass B E UnBypass H F Cancel Definition of printer output codes ii ZN Zone number ID...

Страница 71: ...ht 330 System peripheral 136 Outdoor 331 Polling loop open Remote Access 137 Tamper 332 Polling loop short 411 Callback request 138 Near alarm 333 Expander module failure 412 Success download access 1...

Страница 72: ...572 24 hour zone bypassed 573 Burg bypassed 574 Group bypassed 575 Swinger bypassed Test Misc 601 Manually triggered test 602 Periodic test report 603 Periodic RF Xmission 604 Fire test 605 Status to...

Страница 73: ...nc 1800 Abbott Street Salinas California 93901 Customer Service 800 538 5807 1997 Radionics Inc Salinas CA USA All rights reserved TM The Radionics logo is a registered trademark of Radionics Inc Sali...

Отзывы: