D2212 Installation Manual

Page  8

© 1996 Radionics

74-07361-000-C 11/11/96

Point Expanders, Wired or RF

Points are connected by wire to D222 keypads, or if RF
Points are used, they transmit to an RF Receiver.

You can expand to 24 points using wired and/or RF point
expanders. On board point numbers are fixed from point 1 to
point 8. If you use an on-board point, you must use its point
number. See the 

D2212 Program Entry Guide (74-07386-

000) for more information.

For UL installations, wire a sounding device (e.g. a buzzer)
to one of the external relays (terminal 11 or 12) and to
terminal 6 (alarm output). See Figure 5. Program the relay
for Function 3 to provide annunciation of troubles for all fire
points (see 

RELAYS in the D2212 Program Entry Guide).

Points Connected to D222 Keypads or D208 Point
Expanders

Points are supervised, non-powered points. The panel
monitors sensor loops for normal, shorted, or open
conditions. Programming for each point determines how the
panel responds to these conditions. See the 

D2212 Program

Entry Guide.

Terminate each sensor loop with a 1.0k 

 end-of-line

resistor. Figure 5 shows Point wiring.

RF Points

RF Points transmit a radio frequency signal to an RF Point
Expander Module. The module decodes the signal and
sends the RF Point status to the D2212.

Burglary Devices

Connect any number (limited by available power) of burglary
devices to any point. Do not combine fire detection and
burglary devices on the same point.

Points 2 to 6

Terminals 15 to 22

Points 2 to 6  are supervised, non-powered points.

The panel monitors sensor loops for normal, shorted, or
open conditions. Programming for each point determines
how the panel responds to these conditions. See the 

D2212

Program Entry Guide .

Terminate each sensor loop with a 1.0k 

 end of line

resistor. Figure 5 shows Point wiring.

Four-Wire Smoke Detectors

Connect any number (limited by available power and the
Authority Having Jurisdiction) of 12 VDC four-wire smoke
detectors to any supervised point. Install a suitable power
supervision device according the manufacturer's instructions.
Route the power for the detectors through a D133/ D134
Relay Module. The relay module must be connected to one
of the panel's external relay outputs programmed for the
reset function. See 

RELAYS in the D2212 Program Entry

Guide for programming instructions.

Heat Detectors and other Dry Contact Initiating Devices

Connect any number (limited by the Authority Having
Jurisdiction).

Burglary Devices

Connect any number (limited by available power) of
burglary devices to any point. Do not combine fire
detection and burglary devices on the same point.

Points 7 and 8

Terminals 23 to 25

Points 7 and 8 are non-powered points that
are not supervised with an end-of-line
resistor.

The D2212 monitors the sensor loops for
Points 7 and 8 for normal (closed) and open
conditions. Programming determines how
the panel responds to these conditions. See
the 

D2212 Program Entry Guide . Figure 5

shows Point wiring.

For UL systems, points 7 and 8 can only
be used for tamper contacts.
 Tamper
contacts must be installed within the
protected enclosure.

Figure 5: Points

15

16

17

20

21

22

19

18

Point 2 Point 3

Point 4Point 5

Point 6

11

12

14

13

Point 1

Powered Sensor Loop

suitable for

Two Wire Smoke

Detectors

2 K 

 Resistor required

at End of Line.

For compatible smoke

detectors see

RPN 73-07358-000.

23

24

25

Point 7

Point 8

10

9

8

RF Receiver

(D208RF or

D216RF)

6

Buzzer

Supervised Points

Open                3.7 - 5.0VDC
Normal             2.0 - 3.0VDC

Short                1.50 - 0.0VDC

1.0 K 

 Resistor

Required at End of Line

A

B

C

D

RF Transmitter

s

s

Supervised Points

Open                8.9 - 13.9VDC

Normal             2.5 - 8.5VDC
Short                0.0 - 2.0VDC

1.0 K 

 Resistor

Required at End of Line

Unsupervised Points

Open 2.4 - 13.9VDC

Normal (Closed)

0.0 - 1.4VDC

No End of Line Resistor

www.PDF-Zoo.com

firealarmresources.com

Содержание D2212

Страница 1: ...74 07361 000 C 11 11 96 1995 1996 Radionics D2212 Control Communicator Installation Manual www PDF Zoo com firealarmresources com ...

Страница 2: ...Communicator for connection to the public telephone network using an RJ38X or RJ31X jack Use the ringer equivalence number REN to determine the number of devices you can connect to the telephone line Excessive RENs on the telephone line may result in devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 Contact the telephone comp...

Страница 3: ...es the following D222 Text Keypad with Point Expansion 4 points Installation Sheet 74 07362 000 User s Reference Card 71 04523 010 Security System User s Guide 71 07374 000 Getting Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Six wire point cable assembly 15 07251 000 Four 1k Ω end of line resistors 30 01098 102 Table of Contents Introduction 3 D2212 Cont...

Страница 4: ...ing Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Battery Order a D126 Battery 12 V 7 0Ah to complete a basic D2212 installation Enclosure Options The D2212 is shipped in the D2203 enclosure If you want to mount the D2212 in one of the optional enclosures listed below order the D2212M and the enclosure of your choice D8103 Universal Enclosure D8108A Attack...

Страница 5: ...wire maximum under the terminal Use a spade lug or splice for larger wire Do not connect any other panel terminals to earth ground The panel s common terminals and terminal 3 earth ground are electrically isolated Transformer Terminals 1 and 2 Connect the transformer to terminals 1 and 2 on the panel before plugging it into the power source Use 18 AWG wire to connect the transformer to the panel W...

Страница 6: ...using Point 1 as a fire point the number of detection devices you can connect to its sensor loop is limited See Point 1 on Page 7 The number of detection devices you can connect to the sensor loops for points 2 to 8 is limited only by the resistance on the loop Resistance must be less than 100Ω with the detection devices connected Continue Connections to the Panel Power Down First Unplug the trans...

Страница 7: ...onnections Warning Do not connect wiring for external devices directly to terminals 11 or 12 Install D133 D134 modules connected to terminals 11 and 12 in the enclosure with the panel as shown in Figure 1 The D133 draws 36mA when energized When both relays are energized the D134 draws 72 mA Connect the Points On Board Points Point 1 Terminals 13 and 14 Point 1 on the D2212 is a powered supervised ...

Страница 8: ...oint wiring Four Wire Smoke Detectors Connect any number limited by available power and the Authority Having Jurisdiction of 12 VDC four wire smoke detectors to any supervised point Install a suitable power supervision device according the manufacturer s instructions Route the power for the detectors through a D133 D134 Relay Module The relay module must be connected to one of the panel s external...

Страница 9: ...dular Phone Jack Premises Phone RJ31X Module Figure 6 RJ31X Phone Jack Program Entry Guide for programming options and keypad programming instructions If you re programming from the keypad or using the D5200 make sure the Standby Switch is locked down See Figure 8 If you re using the D5200 Figure 9 shows the location of the programming jack See the D5200 Programmer Operation Manual for instruction...

Страница 10: ...0 VDC Battery restoral reports sent the keypad returns to normal operation 13 9 VDC Battery float charged Fill out the Point Chart Radionics recommends that you fill out the Point Chart on the Installation Label located on the inside of the D2203 Enclosure cover You must fill out the point chart if you programmed Point 1 for Fire with Verification Digit 1 2 See POINT CODES in the D2212 Program Ent...

Страница 11: ...ch the receiver 10 attempts if two phone number are programmed the panel goes into communication failure The panel clears any reports in its phone buffer The panel sounds a tone at the keypad indicating trouble Pressing the Clear key silences the tone When communication restores a report is acknowledged by the receiver the keypad returns to normal operation Ground Start Some telephone systems requ...

Страница 12: ...Shorted Loop Greater than 0 0 VDC but less than 2 0 VDC Points 7 and 8 Points 7 and 8 are not supervised with EOL resistors Open Loop Greater than 2 4 VDC but less than 13 9 VDC Normal Closed Loop Greater than 0 0 VDC but less than 1 4 VDC Point Response Time The panel scans point sensor loops every 500 milliseconds A point must be faulted for 2 scans one second before the panel initiates an alarm...

Страница 13: ...5 minutes for Commercial Burglary applications For all Commercial Burglary applications the system must be programmed to sound the audible device every time the system is armed Enclosures The D2203 enclosure is suitable for Household Fire and Burglary applications only Enclosure tamper protection causing an immediate alarm signal is required for all burglary applications Radionics offers three opt...

Страница 14: ...electronic vibration sensor directly inside the metal cabinet of the D8108A Do NOT install the sensor within a quarter inch 1 4 of the components or traces of the printed circuit assembly System Chart Household Burglar Grade A Household Fire Household Fire Burglary Combined Central Station Burglary Grade C Police Connected Burglary Local Burglary Proprietary Burglary NFPA Standard 72 72 Min Hours ...

Страница 15: ...es System Wiring Diagram Issue A s s P P P D164 Phone Cord to RJ31X for Phone Line Listed Audible Signaling Device Rated At 10 2 TO 13 9 VDC Do NOT Use Vibrating Type Horns P P P P D133 D134 Relay P P Supervised with 1k Ω EOL Resistor Typical Initiating Devices are Door Contacts NO NC Floor Mats Motion Sensors Glass Break Detectors etc NOT Supervised Normally Closed Typical Initiating Devices are ...

Страница 16: ...moke Detector Head D208 RF Receiver D216 RF Receiver Radionics Inc 1800 Abbott Street Radionics 1 Park Gate Close Bredbury Salinas California 93901 Stockport Cheshire SK6 2SZ England Customer Service 800 538 5807 Technical Support 061 494 0851 The Radionics logo is a registered trademark of Radionics Inc Salinas CA U S A 1995 Radionics Inc Salinas CA U S A All rights reserved D2212 Terminal Quick ...

Отзывы: