Confirm by pressing
P3
, after that, the
Auger Calibration
or
Fan Calibration
selection display appears on the display. The display will be marked
Auger Calibration
,
with the keys
P4 ili P6
select what you want to change and confirm with the key
P3
.
Changing the doser work time Auger Calibration
If you have chosen
Auger Calibration
the display will indicate the current calibration value
(Set: 0, mostly 0), with the key
P4
increase the value of the dosing time, and the key
P6
you reduce the dosing time. Values are from -5 to 5, (lower calibration setpoint = lower
doser loading times in operating modes, higher calibration setpoint = higher doser loading
times in operating modes), when you select a numerical dosing value, confirm again with the
key
P3
. Return to the basic display (Figure 17) by pressing the button
P1
.
Fan Calibration fan speed change
If you have chosen
Fan Calibration
the display will indicate the current calibration value
(Set: 0, mostly 0), with the key
P4
increase the value of the fan speed, and the button
P6
you reduce the fan speed value. Values are from -5 to 5, (lower calibration setpoint =
lower fan speed in operating modes, higher calibration setpoint = higher fan speed in
operating modes), when you select the numerical fan speed value confirm with
P3
.
Return to the basic display (Figure 17) by pressing the button
P1
.