e-mail: [email protected]
3.3 Working space and positioning of BIO
lux
Boiler heating Stove
When determining where to place the Boiler Heating Stove pay attention to the following details:
Boiler Heating Stove must be as close to the chimney as possible, also supply of fresh air
for combustion should be close.
If possible, Boiler Heating Stove should in the largest central room of the
apartment/house which is heated because of better heat radiation effect.
The unit must never be installed in a bedroom or a room that is impossible to separate
from bedroom by the door
The room in which pellet Boiler Heating Stove is installed another heating unit can not be
used, such as a stove ora fireplace, solid fuel and pelet heating units. Necessary
circulation of air through one of these devices is likely to be oppressed by the air supply
to the other unit.
The room in which the Boiler Heating Stove is positioned must be able to let the
ventilation and connectivity with fresh air or with a room that is connected to external
fresh air. This connection is made with non-combustible steel pipes.
For the operation of the unit the power supply of 230 V and 50 Hz is needed. Place the
pellet Heating boiler Stove as close to the connection socket as possible and on this
occasion avoid extension cords.
In case of setting the Boiler heating Stove on the combustible surfaces (floors, laminates,
rugs, carpets, etc.). It is necessary to insulate the unit from such substrates with a plate of
uncombustible materials (steel, ceramics, insulation materials, ceramic fiber, etc.). Such
plates should be sized as to be larger from the base of the heating Boiler Stove (see
Figure 8).
Boiler Heating Stove must be at a safe distance from flammable materials such as wood
and textile, pieces of furniture, curtains, plastic parts etc. The distance must be at least
one meter from such materials.
Distance of the pellet Boiler heating Stob\ve from the solid immovable objects
(walls, columns, etc.) (Figure 8) laterally must be at least 40 cm (Figure 8 measures
B), at the back of 20 cm (Figure 8 measures C) and at the front of 100 cm (Fig. 8 A
measures). This gap distances are necessary because of approaching to hole for
cleaning as well as for access during service interventions.