background image

P:

 0800 357 1233 

E: 

[email protected]  

W: 

www.centralheating.co.nz

ALIGNING THE SECTIONS

Carefully slide the second section next to the first so that the nipples 
align with the connections correctly.

CONNECTING THE SECTIONS

Mark how far to insert the nipple key by placing it over the top of 
the radiator so that the end aligns with the nipples to be turned. 
Slide the key in from the open end of the waterway until it engages 
into the nipple that needs tightening. Keep the key as parallel to the 
floor as possible for easier insertion; forcing the key will jam it in the 
waterway. Once the key is inserted enough, check the end of the key 
has fully engaged in the internal lugs inside the nipple. 

One turn at a time, rotate the nipple using the nipple key. This will 
pull the two sections together. After one turn, repeat with the other 
nipple. Continue to alternate between the nipples, one turn at a time, 
until the two sections are pulled together. It is important to keep the 
sections parallel to one another.

When the sections are connected, tighten the joints so the gaskets are 
firmly compressed. A tightening torque of 100 lbf-ft must be applied. 

Do not test with air.