9

 Technical Data Roomcontroller 4 Zones

Physical data

Housing:

Dimensions

160  x 91 x 61 (h x b x l)

Material

Plastic, self extinguishing as per UL94-V0

Steering per controller

Number of zones

4

Led indication:

1 LED per zone

Lights continuously in heating mode / Flashing slowly in cooling mode

3 LED's system operation:

Green

Power On

Red

System is in heating mode

Blue

Systeem is in cooling mode

Protection

IP20, EN 60529

Installation

Mounting on DIN-rail

  35 mm

Integrated power supply

50 Watt / 24 Volt

Power Consumption

15VA

Environmental Conditions

Power On:
- temperature

0...+50ºC

- humidity

<85% r.h. (not condensing)

Environmental Conditions

Storage:
- temperature

-25...+65ºC

- humidity

<95% r.h. (not condensing)

3-way valves Connection

Power Consumption

<1VA

Heating

3-Way valve

3 pin connection

Max. wire section Ø 2.5 mm

2

Cooling

3-Way valve

3 pin connection

Max. wire section Ø 2.5 mm

2

Zone Connection

To device

Tension device

(-) GND

Max. wire section Ø 1.5 mm

2

To device

Steering device

Protected output0..10V (max. 10mA)

Max. wire section Ø 1.5 mm

2

To device

Tension device

+24V ( with resettable fuse against overload: I

H

 van 1.1A )

Max. wire section Ø 1.5 mm

2

Thermostat

Tension thermostat

+24V (with resettable fuse against overload: I

H

 van 1.1A )

Max. wire section Ø 1.5 mm

2

Thermostat in

Heating demand

For thermostat with floating contact (met interne pull-down van 200K)

Max. wire section Ø 1.5 mm

2

Thermostat in

Cooling demand

For thermostat with floating contact (met interne pull-down van 200K) 

Max. wire section Ø 1.5 mm

2

Valve

2-Way valve

3 pin connection: 

Max. wire section Ø 2.5 mm

2

230V input connectors

Power in

3 pin connection: N / L / PE

Min. wire section Ø 2.5 mm

2

Standards

EC conformity:
-  EMC guidelines 

89/336/EEC

-  immunity and emissions

EN 60730-1, EN 50081-1, EN61000-6-2

-  electrical safety

EN 60730-1, EN 60730-2-9

Содержание JAGA

Страница 1: ...Canal la tension de sor tie du Jaga Roomcontroller doit tre r gl e au minimum 4 volts F r die Inbetriebnahme der Clima Canal Gebl semotor s den Regler auf mindestens 4 Volt einstellen For startup of...

Страница 2: ...ion 2 LED indication operation mode 3 Connections 4 Connections with External Power Supply 5 Example scheme 1 SECTOR heating 6 Example scheme 1 SECTOR heating cooling 7 Example scheme 2 SECTORS heatin...

Страница 3: ...zone 1 2 3 4 If zone 1 does not demand the next zone with de mand has priority The room thermostats control the overall demand for heating or cooling When heating and cooling is asked at the same time...

Страница 4: ...2 Power On Mode Heating Mode Cooling Manual setting ventilator speed Connection by using screw clamps LED indication operation mode...

Страница 5: ...10 Connections 1 Alternating contact Ohm AC1 25 C Inductive AC3 25 C Nominal charge Maximum switch off tension Min Minimum admissible charge heating standby NO normal open contact NC normal closed co...

Страница 6: ...V Heating Cooling TH TH TH TH GND TOESTELLEN VOEDING 230VAC GND 230VAC 7990 050 31 1 3 7990 051 60 2 5 7990 052 100 4 2 7990 053 240 10 Connections with External Power Supply Power supply DIN rail or...

Страница 7: ...M T Example scheme 1 SECTOR heating 1 SECTOR Bypass with pressure difference regulator Speed control device Two way valve with motor Thermostat Heating system controller Example scheme 1 SECTOR heati...

Страница 8: ...ROOM 1 ROOM 2 ROOM 3 ROOM 4 ROOM 2 ROOM 3 ROOM 4 T M M Example scheme 1 SECTOR heating cooling 1 SECTOR Water Icewater Two way valve with motor Speed control device Bypass with pressure difference re...

Страница 9: ...3 ROOM 4 ROOM 3 ROOM 4 ROOM 1 ROOM 1 ROOM 2 ROOM 2 T M M Example scheme 2 SECTORS heating cooling Water Icewater Two way valve with motor Speed control device Bypass with pressure difference regulato...

Страница 10: ...8...

Страница 11: ...section 2 5 mm2 Cooling 3 Way valve 3 pin connection Max wire section 2 5 mm2 Zone Connection To device Tension device GND Max wire section 1 5 mm2 To device Steering device Protected output0 10V max...

Страница 12: ...1012 versie1 Jaga N V...

Отзывы: