Installation Manual 

 

  

14

17

19

9 10

16

15

25

12
21

13

4

7

2

5

1

22

20

6

18

8

11

3

24

23

21

MAIN COMPONENTS

 

 

KEY 

1. 

FLUE HOOD 

2. 

COMBUSTION CHAMBER  

3. 

ROOM SEALED CHAMBER COVER 

4. 

ROOM SEALED CHAMBER BACK 

5. 

HEAT EXCHANGER  

6. 

FLAT PLATE TYPE EXCHANGER 

7. 

MULTIGAS BURNER  

8. 

HEATING SAFETY THERMOSTAT 

9. 

ELECTRONIC GAS VALVE VK4105  

10. 

ELECTRONIC IGNITION BOARD 

11. 

EXPANSION VESSEL 

12. 

3-SPEED CIRCULATION PUMP WITH AIR VENT 

13. 

AUTOMATIC AIR VENT 

14. 

HEATING CIRCUIT 3 bar PRESSURE RELIEF VALVE 

15. 

WATER PRESSURE GAUGE 

16. 

FILLING TAP 

17. 

WATER PRESSURE SWITCH 

18. 

HEATING SENSOR 

mod. 

RSF 20 E

 

19. 

HOT WATER SENSOR 

20. 

3-WAY DIVERTER VALVE 

21. 

FLOW LIMITER  

22. 

ELECTRONIC FLOWSWITCH 

23. 

BY-PASS 

24. 

AIR PRESSURE SWITCH 

25. 

FAN 

26. 

IGNITION ELECTRODE 

27. 

FLAME IONISATION ELECTRODE 

 

LIMITER 

The boiler is equipped with a variable flow limiter at the cold water inlet. The flow limiter can 
be adjusted by turning the screw in order to obtain the correct flow rate of domestic hot water 

for the specific boiler output. 

 

FLOWSWITCH 

This device gives precedence to domestic hot water and is fitted to boilers which supply 

instantaneous hot water. It allows conversion to hot water even with a minimum hot water 

demand (min. 2 litres), using an electromagnetic principle with electrical switching by means of 

a relay. The device is made of non-toxic, corrosion-proof ZYTEL 101 L plastic material which 
has type approval with non-toxic characteristics and is unaffected by hard water. In addition, a 

filter is fitted before the flowswitch and at the cold water inlet which eliminates any water 

impurities. These features guarantee that the flowswitch operation is highly efficient.

 

mod. 

RSF 24 E

 

 
BY-PASS 

All boilers are fitted with a by-pass. This element is essential in the following cases: 

 

if a two-way zone valve is installed 

 

if thermostat valves are installed in the radiators.  

To adjust the by-pass proceed as follows:  
fit the screwdriver to the plastic screw of the by-pass, bearing in mind that when the slot of the 

screw is horizontal the by-pass is totally open, allowing all the water to pass, while when it is 

vertical the by-pass is totally closed. For partial by-pass flows, use the adjuster screw. 

 

DIVERTER VALVE 

The diverter valve is the device which controls the boiler switching from central heating to d.h. 

water circuit and vice versa.  

the new 3-way valve transparent cover allows to see the operation mode according to the disk 
colour: red disk 

 heating mode; blue disk 

 domestic hot water mode. 

The new 3-way valve does not have the middle position function (in case of motor failure); 

 

DIFFERENTIAL AIR PRESSURE SWITCH FOR FAN CONTROL 

To guarantee maximum safety in flue exhaust, a differential pressure switch is installed on 
room-sealed boilers and on forced draught boilers. This pressure switch automatically controls 

perfect functioning of the fan and the passage of both external air and exhaust flue pipes. 

mod. 

RSF 30 E

 

DOMESTIC HOT WATER WITH STORAGE CYLINDER  –  TA05A027.A0504

 

18

Содержание RSF 30 E

Страница 1: ...504 Technical Specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY ENGLISH INSTALLATION AND MAINTENANCE MANUAL FOR GAS FIRED WALL HUNG BOILERS models RSF 20 E RSF 24 E RSF 30 E TYPE C ROOM SEA...

Страница 2: ......

Страница 3: ...BOILER INSTALLATION page 10 ELECTRICAL CONNECTIONS page 12 BOILER CONTROL PANEL page 13 STARTING UP THE BOILER FOR THE FIRST TIME page 13 MULTIGAS OPERATION page 15 GAS TABLE REGULATING THE GAS PRESSU...

Страница 4: ...9 336 EEC Electromagnetic compatibility GAS DIRECTIVE 92 42 ECC requirements for new hot water boilers fired with liquid or gaseous fuels All RADIANT boilers are constructed according to UNI CIG EC no...

Страница 5: ...to the constructor s instructions Whenever the device is to be put out of service secure all potentially hazardous parts to prevent accidents or damage If the device is sold or transferred to another...

Страница 6: ...ect the operation of the boiler 3 GENERAL WARNINGS BASED ON TYPE OF POWER SUPPLY POWER SUPPLY Electrical safety is achieved only when the device is correctly and efficiently earthed as per current saf...

Страница 7: ...1 bar litres 10 10 10 Continuous hot water drawing with Dt 30 litres min 11 33 13 04 15 25 Max working pressure water bar 6 6 6 Min working pressure water bar 0 3 0 3 0 3 Width mm 410 450 450 Height m...

Страница 8: ...st and the air intake directly to an external wall To insert a bend reduce total flue length by 0 8 m KEY R RETURN G GAS C HOT WATER F COLD WATER A HEATING FLOW Kit B Double exhaust emission twin flue...

Страница 9: ...ORIES AND FLUE DIAPHRAGMS ONLY FLUE KIT 100 60 A F G C R 55 5 65 5 70 78 80 102 720 80 85 280 85 82 286 82 190 35 55 5 G 65 5 R 78 70 C 80 F 102 A 80 130 320 800 198 320 130 720 85 82 280 85 286 82 45...

Страница 10: ...intake directly to an external wall To insert a bend reduce total flue length by 0 8 m KEY R RETURN G GAS C HOT WATER F COLD WATER A HEATING FLOW kit B Double exhaust emission twin flue system with 3...

Страница 11: ...22 mm ininterrupted supply from meter to the isolation cock of the boiler The complete installation must be tested for soundness as described in the above code BS 6400 1985 BS6891 IMPORTANT BOTH THE U...

Страница 12: ...ted less than 2m 6 6ft above a balcony above ground or above a flat roof to which people have access the terminal MUST be protected by a purpose designed guard Where the terminal is fitted within 850m...

Страница 13: ...RACKET MOD 1 CON STAFFA MOD 1 MOD 2 KIT H MOD 1 MOD 2 MOD 1 KIT A 82 53 R HEATING RETURN G GAS C HOT WATER F COLD WATER A HEATING FLOW FIXING KIT Fig 3 Fig 1 WATER CONNECTIONS To facilitate installati...

Страница 14: ...r in accordance with law no 46 of 5th March 90 see p 18 mod RSF 20 E RSF 24 E ANTI FREEZE SYSTEM ANTI FROST SYSTEM Radiant boilers are equipped with an Anti Freeze system which comes into operation wh...

Страница 15: ...cated in the instrument panel as follows A Turn off the electrical power supply at the mains B Remove the boiler front casing C Undo the two screws on the panel and turn it to the position shown in fi...

Страница 16: ...lied is the same as the type for which the boiler has been tested and approved see plate data make sure the unit is properly earthed make sure there are no flammable liquids or materials in the immedi...

Страница 17: ...the gas data plate to check maximum gas pressure value turn ON a hot water tap and check that the maximum pressure is equal to that stated on the gas data plate to check the minimum gas pressure close...

Страница 18: ...no 7 spanner The jets must be fitted with new gaskets reassemb Fig 2 mod RSF 24 E le the entire d new max e gas setting g plate and replace it with the new one pplied in the conversion kit burner uni...

Страница 19: ...Main burner 17Jets jet mm 1 20 0 75 0 75 Consuption 15 C 1013 mbar m3 h 3 65 Consuption 15 C 1013 mbar kg h 2 72 2 68 REGULATING THE GAS PRESSURE Maximum and minimum modulation pressures N B The follo...

Страница 20: ...pacity in kW mod RSF 20 E For 27 kW output boilers G20 G30 31 L P G NATURAL GAS 0 5 10 15 20 25 30 35 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 Gas pressure in mbar Output capacity in kW mod RS...

Страница 21: ...proval with non toxic characteristics and is unaffected by hard water In addition a filter is fitted before the flowswitch and at the cold water inlet which eliminates any water impurities These featu...

Страница 22: ...7 1 PWM 12 light blue 10 11 grey black RS light blue brown 13 14 16 15 L 12 11 9 10 8 7 6 5 4 3 2 N 56 1 5 bar PAC brown black M3 55 brown brown light blue black 59 57 58 60 61 PWM CONNECTOR FOR SM654...

Страница 23: ...rol fig 5 or to the terminal block fig 3 dotted line on the terminals marked SE SE he remote control connection cable must pass through a channel which is separate from any system supplied with power...

Страница 24: ...imit safety sensor for pressure limit Check the exhaust flue safety device Check the max and min modulation pressures and the modulation Check that the electrical connection conforms to the descriptio...

Страница 25: ...Check the flue pipe n Check cable connection 04 Water deficiency in the system o Water pressure in the system insufficient stop below 0 5 bar p Water pressure switch cable disconnected q Water pressur...

Страница 26: ...066LA GAS VALVE VK4105 G1112 EL MIDY S13 SF16 VENTED 37016LA EXHAUST FAN ES 30 108 G00 0416 43157LP SEALING CLIPS KIT FOR MULTIPLEX GROUP 58012LP MAIN HEAT EXCHANGER 20K 2003 58015LP MAIN HEAT EXCHANG...

Страница 27: ...RSF 24 E 43002LA WASHER D 18 5x10 2x2 1 2 AFM34 43135LA 3 WAY VALVE FLANGE WASHER MPLEX 43139LA PLATE EXCHANGER O RING MULTIPLEX 43145LA 3 WAY VALVE MOTOR O RING MULTIPLEX 43150LA EPDM O RING FOR BRA...

Страница 28: ...T HAVE BEEN CAREFULLY PREPARED BUT WE RESERVE THE RIGHT TO MAKE CHANGES AND IMPROVEMENTS IN OUR PRODUCTS WHITCH MAY AFFECT THE ACCURANCY OF THE INFORMATION CONTAINED IN THIS LEAFLET E OE ALL RIGHTS RE...

Отзывы: