INSTALLATION INSTRUCTIONS
20
Flue type - kit A
Horizontal concentric flue kit Ø60/100 mm adjustable through 360
°.
Discharges exhaust fumes and draws air from atmosphere.
Discharges exhaust gases and draws
combustion air by means of two concentric
ducts. The external duct draws the combustion
air while the internal duct discharges the
exhaust fumes.
The discharge duct can be connected directly to the
outside or can be connected to a suitable combined
flue system.
MAXIMUM FLUE LENGTH: 3 m
The
maximum
flue length (linear equivalent) is
obtained by summing the length of linear pipe
and the equivalent lengths of each bend fitted.
The
linear equivalent
is intended as being the total
length of the duct from the connection with the
combustion chamber of the appliance, excluding the
first bend.
The linear equivalent of additional bends is as
follows:
Ø 60/100 x 90° bend = 0.8 m.
Ø 60/100 x 45° bend = 0.5 m.
N.B.
:
USE ONLY RADIANT TYPE -APPROVED
FLUE SYSTEMS FOR DISCHARGING EXHAUST
GASES AND DRAWING COMBUSTION AIR.
60
10
0
10
6
190
187