SFK 56 - RAD - ING - Inst.Manual - 2007.1_CSA
2. FIRST START-UP
SUPPOR
T CENTER
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P30
MINIMUM HEATING SETPOINT
THROUGH THIS PARAMETER YOU CAN SET THE USER-
ADJUSTABLE MINIMUM HEATING TEMPERATURE.
68 - 104
THE VALUE IS EXPRESSED IN °F
P31
MAXIMUM HEATING SETPOINT
THROUGH THIS PARAMETER YOU CAN SET THE USER-
ADJUSTABLE MAXIMUM HEATING TEMPERATURE.
104 - 160
THE VALUE IS EXPRESSED IN °F
P32
HEATING TIMING
THROUGH THIS PARAMETER YOU CAN SET THE MINIMUM
TIME FOR WHICH THE BURNER WILL BE TURNED OFF ONCE
THE HEATING TEMPERATURE REACHED THE USER SET
TEMPERATURE.
0 - 90
VALUE EXPRESSED IN
MULTIPLES OF 5 SECONDS
(PRE-SET AT 6 X 5 = 30
SECONDS)
P33
HEATING RUN-UP
THROUGH THIS PARAMETER YOU CAN SET THE TIME, DURING
START-UP PHASE, NECESSARY FOR THE WATER HEATER TO
REACH THE MAXIMUM SET POWER (ON THE HEATING SIDE).
0 - 4
0 = (DISABLED)
1 = 50 SECONDS
2 = 100 SECONDS
(SET BY DEFAULT)
3 = 200 SECONDS
4 = 400 SECONDS
P34
ENABLING THE SAFETY CHECK, IN CASE OF INSUFFICIENT
CIRCULATION UPON THE IGNITION.
THE ACTIVATION OF THIS PARAMETER, AGAINST EACH IGNITION
OF THE BURNER, LEADS TO THE VERIFICATION OF THE CORRECT
OPERATION OF THE CIRCULATING PUMP. SHOULD THE PUMP
NOT RUN CORRECTLY, THIS PROTECTS THE HEAT EXCHANGER,
AS WELL THE OTHER PARTS THAT MIGHT BE AFFECTED BY THE
UN-DISSIPATED HEAT.
0 - 1
0 = DISABLED
1 = ENABLED (SET BY DEFAULT)