SFK 56 - RAD - ING - Inst.Manual - 2007.1_CSA
2. FIRST START-UP
SUPPOR
T CENTER
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P05
RECIRCULATION DIFFERENTIAL ACTIVATION
THROUGH THIS PARAMETER YOU CAN ANTICIPATE THE
RECIRCULATION FUNCTION, COMPARED TO THE RECIRCULATION
SET POINT PRESET BY THE END-USER, BY MODIFYING THE
TEMPERATURE DIFFERENCE.
5 - 15
VALUE EXPRESSED IN °C
P06
FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED CORRESPONDING TO THE MINIMUM POWER OF THE
BURNER.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P01).
43 - 255
VALUE EXPRESSED IN HERTZ
(1HZ = 30 RPM)
P07
FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE MAXIMUM FAN
SPEED CORRESPONDING TO THE MAXIMUM POWER OF THE
BURNER.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P01).
43 - 270
VALUE EXPRESSED IN HERTZ
(1HZ = 30 RPM)
P08
STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED
DURING THE START-UP.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P01).
43 - 255
VALUE EXPRESSED IN HERTZ
(1HZ = 30 RPM)
P09
D.H.W RUN-DOWN
THROUGH THIS PARAMETER YOU CAN SET THE TIME NECESSARY
FOR THE WATER HEATER TO REACH THE MINIMUM SET POWER,
AFTER THE BURNER START-UP.
2 - 15
VALUE EXPRESSED IN SECONDS
(FACTORY SET AT 8 SECONDS)
P10
TYPE OF UNIT SELECTION
0 - 1
0 = °C - L/MIN
1 = °F - GPM
P11
EXECUTION PERIOD OF THE OVERHEATING FUNCTION
THROUGH THIS PARAMETER YOU CAN ENABLE AND SET THE
DURATION OF THE EXECUTION PERIOD OF THE OVERHEATING
FUNCTION, DURING WHICH THE CIRCULATING PUMP ACTIVATES
BY DISSIPATING THE HEAT IN EXCESS.
0 - 60
VALUE EXPRESSED IN SECONDS
(FACTORY SET AT 10 SECONDS)