8

6. 

Firmly tighten the strain relief  or the joint connector (fig. 3/g)

7. 

Lock the connection box with proper screws (fig 3/h)

 

In case you have chose to use a power cable you must:

Choose a cable type H05RN-F or FROR 450/750V;

Identify the correct strain relief according to the diameter of the cable shown in TAB 3;

Always be aware that once the cable is connected, it won’t ever touch the steel parts of the product

Example:
You have purchased the Thermo version 55 HT and you wish to use a power cable for a three-phase connection. Hence, you’ll have to:

1. 

Identify  the  necessary  number  of  conductors:  you  choose  connection  type  “E”  (three-phase),  so  you’ll  get  5  conductors  for  earth,

neutral, L1, L2 and L3.

2. 

Verify the minimum section diameter of the conductors as indicated in TAB 2: 2,5mm2 in this case;

3. 

Choose  which  type  of  wire  you  wish  to  use:  type  FROR  450/750V  5G2,5  (yellow/green  connector  for  earth)  is  necessary  for  the

required needs;

4. 

Verify the exterior diameter of the wire by measuring or contacting the supplier: section of the wire in this case is 12,4 mm

5. 

Identify the strain relief, according to TAB 3: for 12,4 diameter wire you could choose among strain relief with different threads: M20,

PG16 and GAS 5/8”. We choose PG16;

6. 

Verify the hole diameter you will have to drill on the connection box according to the strain relief you wish to use, according to TAB 3:

for PG 16, hole diameter is 23 mm.

7. 

Drill the connection box on the marked spot with a hole diameter according to the previous point (fig. 3/a-b);

8. 

Fix the strain relief to the connection box with the right nut (fig. 3/c-d);

9. 

Insert the cable through the strain relief and connect the power wires (fig. 3/e-f)

10.  Tighten the strain relief (fig. 3/g)
11.  Lock the connection box with 4 proper screws (fig. 3/h).

5.  Using the product

 

No on-off switch or temperature control devices are provided with the product, and switch on/off has to be regulated by special devices to
be included before the installation (es. leakage breaker or thermal magnetic switch).

 

In  versions  with  2  or  3  heating  resistances  there  is  the  possibility  to  realise  independent  power  circuit  to  activate  each  single  heating
element to respond to the demand of reduced heating power when requested. Especially in the 3 heating elements version, we suggest to
realise  one  power  circuit  just for  the  heating  element  in the middle  (phase  L2)  and   a  different  one  for  the  heating  elements  on  the  side
(phase L1 and L3) to maximise, according to the real heating needs, 1/3, 2/3 or the whole product power.

 

Please  mind:  in  the  first  hours  after  installation,  the  product  could  stink  out  the  room  where  it  has  been  installed.  This  is  due  to  the
presence of small residua during the assembly process and does not represent a defect or a malfunction of the product or any risk for the
safety of end users.

6.  Maintenance

 

This product does not require any special maintenance.

 

If the product requires repairing, contact an authorised technical service centre.

 

Before operating on the product please wait until it has chilled.

- GB -

Environment and recycling
Please help us to protect the environment by disposing of the packaging in accordance with the national
regulations for waste processing.
Recycling of obsolete appliances
Appliances with this label must not be disposed off with the general waste. They must be
collected separately and disposed off according to local regulations.

Содержание THERMO

Страница 1: ...questo libretto di istruzioni per future consultazioni Bewaar deze gebruiksaanwijzing zorgvuldig voor toekomstig gebruik Conserver cette notice pour toute consultation ult rieure Es wird gebeten diese...

Страница 2: ...2 2 modello model mod le a b Thermo 22 208 50mm min 1200mm Thermo 39 378 50mm min 1200mm Thermo 55 548 50mm min 1200mm 1 2 1 2 1 2 1 2 b a MIN 1800mm MIN 150mm MIN 500mm MIN 500mm 1 OK NO...

Страница 3: ...e fils min connessione connection raccordement TAB 2 peso weight poids 22 HT 230V mono 1750W 8 0A 50Hz 1 0mm2 A 8 0 Kg 39 BT 230V mono 400 V3 N 1400W 6 4A 50Hz 1 0mm2 B C 11 3 Kg 39 HT 230V mono 400 V...

Страница 4: ...PG16 23 PG13 5 21 PG11 19 PG9 16 GAS 29 GAS 5 8 23 GAS 21 MIN IP54 GAS 3 8 16 3 h a b c e f g L3 L2 L1 N d ATTENZIONE NON SPINGERE I CAVI DENTRO AL PRODOTTO WARNING DO NOT PUSH THE WIRES INSIDE THE PR...

Страница 5: ...e posteriore del pannello ed il soffitto e 180cm fra il prodotto e il pavimento La superficie radiante frontale del pannello deve essere libera e non coperta da oggetti i quali oltre a rendere ineffic...

Страница 6: ...randolo direttamente la sezione del cavo scelto 12 4mm 5 identificare usando la tabella TAB 3 il tipo di pressacavo adeguato per il diametro 12 4mm si possono scegliere i pressacavi con filettatura M2...

Страница 7: ...ing sections 1 and 2 proceed with installation using 4 steel chains that can bear the weight of the product Inside the packaging you will find a plastic bag with 4 steel hooks to install the product F...

Страница 8: ...sert the cable through the strain relief and connect the power wires fig 3 e f 10 Tighten the strain relief fig 3 g 11 Lock the connection box with 4 proper screws fig 3 h 5 Using the product No on of...

Страница 9: ...ter einer Steckdose positioniert und nicht in einem geschlossenen Raum angebracht werden Die vorgeschriebene Installation ist h ngend wobei mindestens 15cm Raum zwischen der R ckseite des Panels und d...

Страница 10: ...reiphasennetz gew hlt daher haben wir 5 Erdleitungen N L1 L2 und L3 13 Den Mindestquerschnitt der Leitungen gem Tabelle TAB 2 berpr fen In unserem Beispiel 2 5mm2 14 Die zu benutzende Kabelart w hlen...

Отзывы: